CXRC1 Controller Operation Cont’d
In order to change any settings on the controller you will need to hold
down the menu button for about 5-10 seconds in order to enter into the
main menu.
Once in the main menu, you can select “Dew Pt Offset”, this setting is
the offset to which the controller will target the output water temp
based on the highest dew point read (the highest reading of any
individual sensor).
The dew point offset is a target in relationship to the dew point.
Example: if the offset is +4F and the highest dew point read from the
sensors is 54F then the controller will target an output temp of 58F. If
the setting is -4F and the sensors are reporting a dew point of 54F then
the target would be 50F.
The Dew Pt Offset is configurable to target an output water temp below
the dew point in cases where you have a sealed system and a known R
value between the surface of the water and the surface that is in contact
with the rooms air temperature. See temperature selection section.