Chiltrix Inc.
Purging Air From DHW Tank & Fan Coils
If a DHW tank is installed, it should be the first device on the loop as shown. The G1 valves should
always be as close to the CX34 as possible. The tank should be as close to the G1 valve as possible.
To purge the air from its coil, remove the actuator from the valve body and rotate the valve stub 90°
clockwise to force the water through the coil. Return the valve stub back to its original position
when all of the air is purged. Close the input valve to each fan coil except the first coil (1). Turn the
pump on and run it, when the bubbles stop coming out of the discharge hose turn on the ball valve
on coil (2), wait for the bubbles to stop, then do the same for coil number (3), then (4). All CX
Chillers have a flow switch installed in the loop. Air in the system may cause a flow switch alarm; the
controller will display a P05 error code.
All CXI fan coils have an air purge screw near the water inlet port, always purge the fan coils before
starting the chiller. The CX34 chiller also has a bleeder valve with a ¼” clear tube attached to it
located near the brazed plate heat exchanger.
Fan Coil Flow Balancing (Performed at time of commissioning)
Proper and even flow through each fan coil is important for both heating and cooling. , (Coil
temperature can be displayed by pressing the up and down temperature arrow keys at the same
time), This can be done with balancing valves or ball valves installed at each fan coil supply or return
pipe. This must be done with the CX34 in heating mode, set loop AC target to the maximum temp
setting for commissioning.
DO NOT DO THIS IN COOLING MODE OR DAMAGE MAY OCCUR.
Adjust valve positions until each fan coil has the same leaving fluid temperature, with all CXIs set to
max manual fan speed and in heating mode. When all leaving fluid temps are the same, the units
are properly balanced. If a fan coil is powered on but the fan isn’t running, there is a good possibility
that there is air trapped in that particular part of the loop. Also verify the parameters with the CXI
FCU manual, page 34.
http://www.chiltrix.com/documents/Chiltrix-hydronic-FCU-ver-1.5.pdf
Note – while only one ball valve per CXI is needed for balancing, best-practice would be to use 2
valves, one on supply and one on return, so that the fan coil unit could be isolated if needed.
30
Содержание CX34-4
Страница 4: ...Chiltrix Inc www chiltrix com CX34 Components 4 ...
Страница 18: ...Chiltrix Inc www chiltrix com Electric Connections and Component Locator 18 ...
Страница 19: ...Chiltrix Inc www chiltrix com CX34 System Wiring Diagram 19 ...
Страница 25: ...Chiltrix Inc www chiltrix com G3 VALVE Seasonal Switch Valve G3 Ports 25 ...
Страница 34: ...Chiltrix Inc www chiltrix com 34 Language Screen Screen Saver ...
Страница 35: ...Chiltrix Inc www chiltrix com 35 Touch Screen Fixing Calibration Time Setting ...
Страница 52: ...Chiltrix Inc www chiltrix com 52 ...
Страница 53: ...Chiltrix Inc www chiltrix com 53 ...
Страница 54: ...Chiltrix Inc www chiltrix com 54 Chiltrix CX34 Internal Pump Wilo Yonos PARA RS 25 7 5 PWM1 Ku ...