componentsthe or checking the next checks; 

 

(9) key is invalid 

a), check whether the output pin of the button is normal, or replace; 

b),  check  whether  the  voltage  of  display  board  is  5V,  otherwise,  check  the  power  supply  circuit  or 

connecting wire; 

c), If all above are normal, check whether the main chip is normal, or replace the main chip. 

 

 

4

Electric control panel detection

 

  red power indicat( LED1) is not bright: 

a), check whether the LED1 is damaged, if damaged,please replace the diode; 

b), check whether the input and output voltage of the 7812 and 7805 is normal (7812 input 14V, output 

is about 12V,7805 input 12V, the output 5V), if damaged,replace the related device or check downward; 

c),  check  whether  the  bridge  rectifier  diodes  D1-D4  is  normal,if  the  damaged,please  replace  related 

diode; 

d), check whether the power supply transformer of input and output is normal (input is about AC220V, 

the output is about AC14V), if it is damaged,replace the transformer. 

 

  Green light LED2 does not shine or the phase sequence protection 

a),  check  whether  the  light-emitting  diode  LED2  damaged,  if  not  normal,then  the  replace  the 

light-emitting diode; 

b), check whether the Q5 (9014) collector voltage is normal, if not normal,then the replace    9014; 

c), check whether the relay RY3 is normal, if not normal,then the replace the relay; 

d), check whether the resistance of the R7-R10 is normal, if not normal,then the replace    the related 

resistance; 

e),  check  whether  the  phase  sequence  of  the  three-phase  power  supply  is  normal,  if  not  ,then  the 

replace phase sequence.

 

  No-voltage for over-current detection circuit 

a), check whether the rectifier diodes D5-D8 is normal, if not normal,replace related diode; 

b), check whether the current transformator L1 is normal (resistance of 

 

  foot should be around a 

few hundred ohms),if abnormal,replace it.

 

  Over-current protection too long or too short. 

Check whether capacity of capacitance E3, E6 is normal (the normal over-current protection is about   

20s ~35s), replace if it is not normal,

 

    appear over-current protection 

a),  check  whether  the  integrated  block  LM311  (7)  feet  IC3  is  normal,if  not  normal,check  IC3.if 

damage, replace it, 

b), check whether triode 9012 is normal.if abnormal,replace it, 

c),  check  the  voltage  of  over-current  relay  coil  is  normal  (about12V),  if  it  normal,check  whether  the 

relay damage.

 

⑥ 

no defrost signal temperature signal (defrosting relay can’t break) 

a),check whether the temperature sensor is normal(measure sensor resistance), if the resistance is too 
large or too small or even infinite, or 0Ω, then replace sensor; 
b),  check  whether  the  voltage  of  the  defrost  relay  coil  is  normal(about  12V),  if  it’s  normal,  check 

whether the relay damage. 

 

 

Содержание CS-25V3A-MA114A

Страница 1: ...1 CHIGO Service manual Room airconditioner Split Wall Mounting Type NOTE Before servicing the unit please first read the service manual and then contact with your service center if meet problem...

Страница 2: ...B Wiring diagram page 4 5 C Installation page 6 D Exploded view and part list page 16 E Components fault and test methods page 20 F Failure display page 29 G Troubleshooting page 31 H Usual failure an...

Страница 3: ...3 A Summary 1 indoor unit 2 outdoor unit 3 remote controller...

Страница 4: ...4 B Wiring diagram Wiring diagram INDOOR CS 25V3A MA114A CS 35V3A MA114A...

Страница 5: ...5 Wiring diagram OUTDOOR CS 25V3A Y4N CS 35V3A Y4P...

Страница 6: ...d test again Ensure the air conditioner works normally If it is the problem of air conditioner report it to the vendor 9 During installation if the service people find that the user s power supply has...

Страница 7: ...the air conditioner 17 Pressure gauge For measuring the working pressure of the air conditioner system 18 Level gauge or plummet 1 pc 19 Putty scraper 1 pc 20 Hex wrench 1 set 21 Electric probe 22 Sa...

Страница 8: ...ter to measure the power voltage which shall be within 10 of the rated voltage Use special line for the power supply of air conditioners and ensuring that the capacity of entire supply line branch lin...

Страница 9: ...below the indoor unit The indoor unit shall be able to blow the cold and hot air evenly to everywhere of the room According to the power supply mode powered by indoor or outdoor unit and the length of...

Страница 10: ...ightly for 90 before stop 3 Route the pipe along the left side This step is the same as the above step The only difference is that the bending angle is higher than that in the previous step that is it...

Страница 11: ...ut of the room and put it onto the support with care Fix with 4 bolts 10mm Note The installation people working on the 2nd floor or higher must wear safety belt The outdoor unit must be tied securely...

Страница 12: ...e a connection pipe with expanded mouth coat frozen oil evenly onto the connector of the 2 way 3 way valve and the expanded mouth Put the expanded mouth and connector on the same straight line and rot...

Страница 13: ...position and tighten every nut and check for leakage The connector with leakage problem should be reinstalled Pipe Wrapping and Wall Hole Blocking Sort the pipeline in good order Use pipe bender when...

Страница 14: ...s are away from the machine do check it s safe before turn the power on Power supply connection Before installation and safety inspection electrification is strictly forbidden Power connection shall b...

Страница 15: ...f disassembling and cleaning the filter net replacing the air filter to the user and instruct them to operate until they are skillful The outdoor unit shall be ventilated so as to prevent sundries fro...

Страница 16: ...G LOUVER 4 CONNECTING LEVER 5 WATER RESISTANT RING OF WATERPOUT 6 LOUVER SUPPORT POLE 7 GUIDE BEARING 8 OUTLET PART 9 BASE 10 CROSS FLOW FAN 11 BEARING 12 EVAPORATOR 13 EVAPORATOR PLASTIC LEFT PLATE 1...

Страница 17: ...IGHT PLATE 1 26 EVAPORATOR RIGHT PLATE 2 27 MOTOR PLATEN 28 TUBE TEMP SENSOR 29 ROOM TEMP SENSOR 30 ELECTRIC CONTROL PLATE 31 TRANSFORMER 32 TERMINAL BOARD 33 WIRE CLIP 34 ELECTRIC BOX 35 INDOOR MOTOR...

Страница 18: ...18 2 Outdoor CS 25V3A Y4N CS 35V3A Y4P...

Страница 19: ...op panel 10 Rear Grill 11 Four way valve assembly 12 Intake pipe for the condensor 13 Suction pipe 14 Capillary Assy 15 Suction pipe 16 Discharge pipe 17 Electrical boxes 18 Right panel 19 Large handl...

Страница 20: ...ed or broken 2 AC motor of indoor and outdoor unit 1 General inspection Testing method In the case of non power twist motor rotor by hand meanwhile shaking motor checking is there any rust whether blo...

Страница 21: ...ultimeter black pen connect base red pen connect other two feet and the resistance should be a few hundred ohm otherwise the transistor damaged 10 Infrared Receiver Module choose diode from multimeter...

Страница 22: ...heck voltage of high medium and low wind relay the normal voltage is DC12V c for the tap fan check whether the relay is normal or may replace relay d check whether the AC power supply circuit is norma...

Страница 23: ...eck whether the relay RY3 is normal if not normal then the replace the relay d check whether the resistance of the R7 R10 is normal if not normal then the replace the related resistance e check whethe...

Страница 24: ...t means loss tangent has exceeded the limitvalue 0 0018 Check capacitance check by pointer type multimeter if the pointer oscillation amplitude is bigger than the standard capacitance that means capac...

Страница 25: ...t circuit and outlet the open circuit 2 Coil Open circuit check by multimeter select the appropriate range measure the resistance if the resistance is that means transformer coil open circuit or open...

Страница 26: ...hen the most for crystal 2 ceramic oscillator is damaged 4 Show insufficiency Testing method make sure the unit running installed battery to remote control press various function keys Fault judgement...

Страница 27: ...ck torque Self positioning Torque under the action of this torque step motor should not lose not jitter non skid 3 Resistance test short circuit Measure resistance of each winding by universal meter i...

Страница 28: ...esistance is or tens of thousands of ohms means insulating property is good if the measured resistance of the smaller or 0 means core screen has been destroyed 4 Check on running Testing method make s...

Страница 29: ...oor units F1 1 lighten 2 Indoor ambient temp sensor fault F2 2 lighten 3 Indoor coil temperature sensor fault Include Inlet middle of pipe outlet F3 3 lighten 4 Indoor fan fault F4 4 lighten Outdoor p...

Страница 30: ...arts 1 Evaporator temp protection P1 lighten 1 Outdoor parts 1 Overheat over current protection of inverter module P2 lighten 2 2 Over current protection P3 lighten 3 3 Compressor discharging temp pro...

Страница 31: ...rd is defective Replace P C board Connect CN properly Replace TA sensor Is CN TP1 sensor connector connected properly Is TP1 sensor resistance value 5KO at 25 normal Indoor P C board is defective Repl...

Страница 32: ...tor connector Replace indoor fan motor Replace main P C board Replace bearing YES YES YES NO NO NO Turn off indoor unit and rotate cross flow fan by hand when the unit is on standby Is it possible to...

Страница 33: ...defective Is resistance value of room sensor Tr and heat exchanger sensor TP1 normal Room sensor or heat exchanger sensor is defective Replace room sensor or heat exchanger sensor Compressor is defect...

Страница 34: ...START STOP button Does radio sound is affected by remote control when a signal is transmitted at distance of 5 cm from radio Does indoor unit start to operate by automatic restart function Is transmi...

Страница 35: ...e beeper beep Is the display all off Check the connector on display PCB connected to control PCB Check the display PCB itself Is the unit display normal Does outdoor unit run Does the compressor run n...

Страница 36: ...fuse of indoor PCB burn out Change a good remote does the air conditioner running Is the power supply no problem Does the 12V and 5V of indoor PCB have Replace PCB normal Does the electric switch cut...

Страница 37: ...the set temperature The condenser blocked by dust or others clean the dust and dirt Too much quantity of refrigerant take the redundant refrigerant out Blockage in airinlet or air outlet Clear the obs...

Страница 38: ...sor suction or venting capability is very poor Replace this compressor Four way valve slight mixes up Let the four way valve moving continually Replace the four way valve if it can t move The capillar...

Страница 39: ...ectric outlet missing phrase for supply voltage Match right power supply voltage is too low install voltage regulator The main fuse burn out Replace fuse The voltage dependent resistor has been burst...

Страница 40: ...door motor rusted or electromagnetic noise Replace this motor The cross flow fan collides with the slot basis Reconfigure The noise of the refrigerant moving Readjust the position of the H L pressure...

Страница 41: ...g between the bending tube and the PCB s wire A lot of evaporator fins fall down to lead to bad flow Renovate these faulty fins The indoor unit didn t install correctly according to the requirement Pl...

Страница 42: ...42 I User s Manual...

Страница 43: ...43 The name of each part and its function...

Страница 44: ...44 Remote controller...

Страница 45: ...45 Use of remote controller Operating machine in selected modes...

Страница 46: ...46...

Страница 47: ...47 Basic principles and performances Features of Heating Operations Methods of maintenance...

Страница 48: ...48...

Страница 49: ...49...

Страница 50: ...50...

Отзывы: