4.8 Thermal insulation of pipe

1)

Apply thermal insulation to the pipes at the gas side and the liquid side respectively;

2)

Use closed-cell thermal insulation materials, with the flame retardant grade of B1 and high temperature resistance of 120℃ ;

3)

Outer  diameter  of  copper  pipe  ≤

φ12.7 and thickness of 

thermal  insulation  cotton  ≥  15mm;  outer  diameter  of  copper  pipe  ≥ 

φ15.88 and 

thickness of 

thermal insulation cotton ≥ 20mm.

4)

The nut joints of the indoor unit shall be performed thermal insulation

5.1 Outdoor unit wiring

!

NOTE

·

  The power supplies for the indoor and outdoor units shall be separately designed.

·

  The power supply must be designed with a sub-circuit, and equipped with a current leakage protector and a manual switch.

·

  All  indoor  units  in  the  same  system  shall  be  arranged  on  the  same  power  circuit,  and  shall  be  turned  on/off  the  power  simultaneously.  It  is  not 

allowed to equip each indoor unit with a power switch.

·

  The connecting wire system and the refrigerant pipe system of the indoor unit shall be incorporated into the same system.

·

  To  reduce  the  interference,  the  indoor  and  outdoor  communication  cables  shall  use  two-core  or  three-core  shielded  twisted-pair  cables  instead  of 

ordinary multi-core cables.

·

  Conform to related national electrical standards.

·

  Electrical wiring shall be done by a professional electrician.

Single-phase

Three-phase

Power Supply

220-

240V 50Hz

Power Line (mm2)

4

.0

40

/

30

Power 

kW)

10.5

Breaker/Fuse (A)

Signal Wire of Indoor/Outdoor Units (mm) (Signal Wire of 

Weak Current)

380V 50Hz

5×2.5

25/20

three-core shielded cable 3×1.0 (two-core shielded cable 2×1.0)

Single-phase

Three-phase

220-

240V 50Hz

3×6.0

63/45

14/16

380V 50Hz

5×2.5

25/20

Table 5-1 Outdoor Unit Wiring

5

 

Electrical Wiring

Fig. 5

-

1

 Electrical Wiring of Single-phase Outdoor Units

Fig. 5-2 Electrical Wiring of Three-phase Outdoor Units

X   

Y   

E

P

  

Q

    

E

Indoor unit

Outdoor unit

Y/G

L

 

N

Three-core 
shielded cable 

Single-phase power supply
220V-50Hz

Single-phase power supply
220V-50Hz

   

L   

N

Y/G

   

P   

Q   

E

Single-phase power supply
220V-50Hz

Three-phase power supply

 

380V3N-50Hz

Three-core 
shielded cable 

L1 L2 L3

Indoor unit

Outdoor unit

Y/G

   

P   

Q   

E

   

L   

N

Y/G

N

   

P   

Q   

E

X   

Y   

E

Содержание CMV-MINI

Страница 1: ...ppearance of your air conditioner is different from that of the air conditioner in the Manual it will not affect its operation and use Please read this Manual before use carefully and keep this Manual...

Страница 2: ......

Страница 3: ...Table of Contents 1 Safety Precaution 1 2 Key Points for Construction Inspection 1 3 Installation of Outdoor Unit 2 4 Installation of Connecting Pipe 4 5 Electrical Wiring 10 6 Trial Run 14...

Страница 4: ......

Страница 5: ...ction Inspection 2 1 Arrival of goods and open case inspection 1 When receiving the machine check if there is any damage in transportation If any surface or internal damage is found please inform the...

Страница 6: ...installation and maintenance 2 No barrier at the air inlet and the air outlet and away from strong wind 3 Dry and ventilated 4 The flat supporting surface is able to bear the weight of the outdoor uni...

Страница 7: ...o be careful to hoist the machine 4 Don t hold the suction inlet of the housing or it will be deformed 3 5 Installation and maintenance space of outdoor unit 1 Provide a firm and adequate foundation t...

Страница 8: ...nnecting pipe Threaded connection Gas side connecting pipe Liquid side connecting pipe Welding 4 Installation of Connecting Pipe 4 1 Refrigerant pipe 1 Flaring Use a pipe cutter to cut the refrigerant...

Страница 9: ...efrigeration system When fastening the nut too strong force will damage the flared socket but too weak force will result in leakage Please refer to the tightening torque in the table above to fasten t...

Страница 10: ...e diameter Pipe Capacity of Outdoor Unit kW Dimension of Main Pipe mm L 30m 1 L 30m 1 Liquid pipe 9 52 Liquid pipe 15 88 Liquid pipe 9 52 Liquid pipe 15 88 10 5 9 52 15 88 9 52 19 05 14 16 Table 4 3 D...

Страница 11: ...7...

Страница 12: ...refrigerant pipe is installed and connected to the indoor unit and before the connecting pipes between the indoor and outdoor units are connected to the valves of the outdoor units refill the nitrogen...

Страница 13: ...t keep the vacuum pump on for 1 2h 4 6 Refilling volume of refrigerant The refilling volume of refrigerant R410A is calculated according to the diameter and length of the pipe at the liquid side of th...

Страница 14: ...tem of the indoor unit shall be incorporated into the same system To reduce the interference the indoor and outdoor communication cables shall use two core or three core shielded twisted pair cables i...

Страница 15: ...shielding net shall be connected to the ground Never connect the power line strong current to the terminal block of the signal line weak current Otherwise the power board will be burnt out 5 2 Wiring...

Страница 16: ...play Control parameters only for use of development personnel Control parameters only for use of development personnel Spot check Content 1 2 3 4 5 6 7 8 9 10 No Spot check Content 12 13 14 15 16 17 1...

Страница 17: ...utes 12 14 16and 18kW are effective 8 and 10kw have no such faults Display H6 for 3 times within 100 minutes 6 Trial Run 6 1 Inspection and confirmation before debugging 1 Check and make sure the refr...

Страница 18: ...olume of refrigerant before delivery see the nameplate refilling volume of refrigerant corresponding to the length of pipe 3 B Calculate the indoor volume B m by the minimum volume Critical concentrat...

Страница 19: ......

Страница 20: ...ong CHIGO Heating Ventilation Equipment CO LTD Address Chigo Industrial District Nanhai Foshan Guangdong China P C 528244 Tel 86 757 8836905 Fax 86 757 88783793 4006 757 555 Hotline Web http www chigo...

Отзывы: