Chemtrac Systems, Inc.
Page 28
Therefore, it is recommended to change the Man Output value to match the
AUTO pump output value prior to switching mode. Failing to do so can result in
a significant change in the pump output when switching from AUTO to MAN
control.
w
SCV Setpoint:
The SCV setpoint is the SCV value that the controller is
programmed to maintain when in AUTO mode. The SCV setpoint value can be
changed from
-1000 to +1000
at one unit increment by pressing the
p
or
q
key,
see Section 3.7 for determine the optimum setting. To determine the setpoint,
the operator must first adjust the chemical feed manually until an optimum
dosage is reached. Once the optimum dosage has been reached, the operator
simply records the Streaming Current Value seen on the display and enters this
as the Setpoint value. It is important that the correct polarity (+/-) be entered
when programming the setpoint.
x
Proportion Band:
The Proportional Band setting determines the level of
response, or amount of change to the pump output, when the SCV deviates from
the setpoint. The Proportional Band value can be changed from
1 to 1000
at 1
unit increment by pressing the
p
or
q
key, see Section 3.7 for determine the
optimum setting.
y
Integral Time:
The Integral Time setting determines how much adjustment is
made to the pump output while the SCV is away from the setpoint. The Integral
Time value can be changed from
1 to 1000
at 1 unit increment by pressing the
p
or
q
key, see Section 3.7 for determining the optimum setting.
z
PID Rate:
The PID Rate function serves to improve the controller’s response
when higher Proportional Band and Integral Time settings appear to be too
responsive for the application. The PID Rate setting is usually left at 1 for most
applications since proper setting of Proportional Band and Integral Time are
capable of providing proper response. Higher PID Rate settings will serve to
buffer the responsiveness of the controller. The PID Rate setting should not
exceed 10. The PID Rate value can be changed from
1 to 20
at 1 unit increment
by pressing the
p
or
q
key, see Section 3.7 for determining the optimum
setting.
{
MAIN Function Key
: Pressing this key will ignore any setting modifications on
this screen and brings up the MAIN screen.
|
SAVE Function Key:
Pressing this key will save current setting modifications
and brings up the MAIN screen.