Wiring connection for gas cooker
To allow for disconnection of the appliance after installation,
the plug must be accessible after installation, or a functional switch
must be provided near the appliance in an accessible position.
gas connection
Read these points before connecting to the gas supply:
• The cooker inlet connection point has a ½” BSP external
thread. See Diagram below.
• A NG regulator or a LPG test point fitting is supplied.
• It is recommended to fit the regulator or test point fitting to
the appliance connection point, then fit either hard piping
or a high level flexible connection (AS5601 clause 5.12.1.8)
which is then attached to the consumer hard piping.
• Ensure installation allows withdrawal of appliance.
Restraining Device
Anchor Points
Grill Shutter
Pressure test point
NG Regulator
(P/No. 294-001-032)
1/2” BSP
Internal Thread
Connection
Gas
Point
150mm
650mm
Gas Flo
w
operation on universal/propane
1. The appliance inlet fitting provided MUST be orientated
so that the pressure nipple is accessible.
2. The inlet fitting has ½” BSP internal thread at the inlet
and outlet.
operation on sng
• If the cooker is to be used with SNG, then the grill burner
MUST be modified by the replacement of the shutter,
which fits into the throat of the grill burner.
• A conversion kit can be obtained from by contacting the
Customer Care Centre
Restraining Device
Anchor Points
Grill Shutter
Pressure test point
NG Regulator
(P/No. 294-001-032)
1/2” BSP
Internal Thread
Connection
Gas
Point
150mm
650mm
Gas Flo
w
1. Remove the control panel.
2. Remove the existing NG shutter securing screw (refer
diagram) and slide upwards to disengage from grill burner.
3. Slide the SNG shutter into position and secure with screws.
testing the gas cooker
WARNING
warning
You MUST test the cooker after installation, before you hand
it over to the customer.
You MUST have a manometer and a connecting tube.
installation
Chef 540 Upright Cooker INSTALLATION 19