2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL 

 

 

 

 

 

             

                     |   6

USER RESPONSIBILITIES

BS5839-1 is the British Standard code of practice for the design, installation, commissioning and maintenance of fi re detection 
and fi re alarm systems for buildings. Section 7 of the standard (User
Responsibilities) states that a named responsible person should be appointed to supervise all matters pertaining to the fi re 
alarm system {clause 47.2a}.
Highlighted below is a summary of the main functions of the responsible person is expected to carry out with regard to 
BS5839-1 only. It does not highlight any other responsibilities that may be required of the user or responsible person that is 
listed in documentation such as the Employers Guide to Fire Safety, the
Fire Precautions (Workplace) regulations and/or any other legislation relevant to the premises. If in doubt, the fi re authority 
can advise on the fi re legislation that applies to any given building.
For countries outside the UK, diff erent user responsibilities may apply.

BS5839-1 states the responsible person should:

(The bracketed numbers {xx} identify the BS5839-1 clauses to which the summary refers).
1 Ensure the fi re alarm panel is checked daily to confi rm there are no faults on the system {47.2b}.
2 Ensure arrangements are in place for the test, maintenance and regular servicing of the system with regard to Section 6 of 
the standard {47.2c}.
Important: Clause 44 of BS5839-1 recommends weekly and monthly tests that should be carried out by the user/responsible 
person - please refer to the bottom of this section for further details.
3 Ensure the system log book is kept up to date by recording fi re signals, fault signals, work on the system, etc, and make sure 
it is available for inspection at all times {47.2d/48}.
4 Ensure that all relevant occupants of the protected premises are instructed in the proper use of the system {47.2e}.
5 Take steps to limit the number of false alarms on the system {47f }.
6 Ensure the eff ectiveness of the system is not impaired by ensuring there is a space of at least 500mm in all directions around 
and below every fi re detector and that all manual call points are unobstructed and easy to see {47g}.
7 Liaise with all relevant building engineers, decorators, etc., to ensure any changes to (or maintenance of ), the building’s 
fabric does not compromise the protection given by the fi re alarm system, create faults or false alarms {47h}.
8 Ensure that any structural or occupancy changes planned for the building are done so with due and early consideration 
given to any changes that may be required to the fi re system {47h}.
9 Ensure that a selection of spare parts are held as appropriate within the premises {47j}.

Routine weekly and monthly testing to be undertaken by the user/responsible person:

To meet the requirements of Clause 44 of BS5839-1 we recommend the following tests are carried out at approximately the 
same time each week, during normal working hours:
Note: It is essential any alarm receiving centre is contacted before and after these tests to avoid unwanted alarms and to con-
fi rm the fi re signal is correctly received.
• Carry out an indicator lamp test to check all Zone lights show and the beeper sounds.
• Operate a manual call point or smoke/heat detector to test the fi re alarm.
• Check that the alarm sounders operate.
• Reset the system by pressing the Silence/Resound Sounders button and Control Panel Reset button.
• Verify that no manual call points or smoke/heat detectors are obstructed in any way.
• Test a diff erent zone each week using a diff erent call point or detector so all are tested in rotation.

Monthly attention:

 Ensure authorised service personnel verify the system’s standby power supply (or supplies) are in good 

working order.

Quarterly and periodic inspection, testing, servicing and maintenance

It is the user’s responsibility to ensure that an ongoing periodic plan is in place that meets Clause 45
(Inspection and Servicing) of BS5839-1. The work required to meet this Clause must be carried out by a competent person 
with specialist knowledge of fi re detection and alarm systems.
The standard recognises this will normally be an outside specialist fi re alarm servicing organisation.

Please note:

 the above summaries do not replace Sections 6 and 7 of BS5839-1 but are intended to help the user gain a 

greater understanding of his or her responsibilities. We strongly recommend the named responsible person familiarises them-
selves with the full and current standard.

Содержание AlarmSense 2 ZONE

Страница 1: ...ANEL CHANNEL SAFETY SYSTEMS t 0845 884 7000 Petersfield Business Park f 0845 884 6000 Bedford Road Petersfield Hampshire e sales channelsafety co uk GU32 3QA w www channelsafety co uk AlarmSense 2 4 8...

Страница 2: ...controls and indicators available on this fire alarm panel including Control level definition How to access the panel s secure user functions What the indicator lights mean Fire Conditions 8 How an al...

Страница 3: ...EL 3 System Set Up Data Chart 13 Details of how the system has been set up Fire Alarm Log Book 14 A place for you to record details of events such as fires false alarms call outs etc Certificate of In...

Страница 4: ...and by a competent organisation A full itemised report of the installation should be obtained at least annually KEY FEATURES The key features chart below illustrates different features available in t...

Страница 5: ...d the fire alarm panel continuously moni tors all connections between detectors manual call points and sounders and also checks it s own power supply and back up batteries for faults If a fault is det...

Страница 6: ...s are unobstructed and easy to see 47g 7 Liaise with all relevant building engineers decorators etc to ensure any changes to or maintenance of the building s fabric does not compromise the protection...

Страница 7: ...the panel into access level two the Authorised User state see below 2 Authorised User Controls access level two To avoid unauthorised changes to critical parts of the fire alarm system controls such...

Страница 8: ...hing Yellow The panel is in the disablement selection state Page 10 Disablements Steady Yellow Part of the system has been manually disabled and or one or more of the fire zones have a delay applied t...

Страница 9: ...iggered into alarm whilst the alarm sounders are silenced the panel will Automatically reactivate the alarm sounders if programmed to do so Flash the General Fire light and appropriate Fire Zone light...

Страница 10: ...of a fault condition Mute the panel s internal sounder by pressing the Silence Internal Sounder button the panel does not have to be in access level two to do this Record the fault s in the Fire Alarm...

Страница 11: ...s at a slower rate than the General Disablement light the option is enabled If the light flashes at the same rate as the General Disablement light the option is disabled 3 If necessary press the Enabl...

Страница 12: ...tion of disabling or enabling output delays is only available if delays have been programmed into the fire alarm panel by the installation engineer If a delay has been programmed into the panel the Ou...

Страница 13: ...Chart page 13 What happens when there is a fire alarm condition on a delayed zone Should an alarm occur on a delayed zone the panel will Flash its General Fire and appropriate Fire Zone light s Sound...

Страница 14: ...applies to all pairs of zones which are set up for coincidence There must be alarms on both zones i e zone 1 and zone 2 before the alarm sounders and outputs turn on If only one of the zones i e zone...

Страница 15: ...ments of the certificate which is a criminal offence In order to satisfy the requirements of BS5839 1 the following must be recorded The name of the responsible person Brief details of the maintenance...

Страница 16: ...AL FIRE ALARM CONTROL PANEL 16 Details of tests including fire drills actual fire alarms disablements or enablements and faults should be recorded here False alarms and maintenance work should also be...

Страница 17: ...2 4 8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL 17...

Страница 18: ...2 4 8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL 18...

Страница 19: ...2 4 8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL 19 False alarms Maintenance work...

Страница 20: ...refore before this user manual is handed over the following installation certificate and commissioning certificate overleaf should be completed as appropriate by the relevant installation commissionin...

Страница 21: ...fore before this user manual is handed over the following commissioning certificate and the installation certificate overleaf should be completed as appropriate by the relevant installation commission...

Страница 22: ...VENTIONAL FIRE ALARM CONTROL PANEL CHANNEL SAFETY SYSTEMS t 0845 884 7000 Petersfield Business Park f 0845 884 6000 Bedford Road Petersfield Hampshire e sales channelsafety co uk GU32 3QA w www channe...

Отзывы: