Champion Pump CPSE10 Series Скачать руководство пользователя страница 6

TROUBLE SHOOTING

 

CAUTION!

 Always disconnect the pump from the electrical power source before handling

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations

If operating problems persist, the following chart may be of assistance in identifying and correcting them

 

MATCH "CAUSE" NUMBER WITH CORRELATING "CORRECTION" NUMBER. 

 

NOTE: Not all problems and corrections will apply to each pump model.  

PROBLEM 

 

CAUSE 

 

CORRECTION 

 

Pump will not run.  

1. Poor electrical connection, blown fuse, 
tripped breaker or other interruption of 
power, improper power supply. 
2. Motor or switch inoperative (to isolate 
cause, go to manual operation of pump). 
2a. Float movement restricted.  
2b. Switch will not activate pump or is 
defective  
3. Insufficient liquid level.  

Pump will not turn off.  

2a. Float movement restricted. 
2b. Switch will not activate pump or is 
defective  
4. Excessive inflow or pump not properly 
sized for application.  
9. Pump may be air locked.  
14. H-O-A switch on panel is in "Hand" 
position.  

Pump hums but does not run  

1. Incorrect voltage  
8. Impeller clogged, loose on shaft, worn     
or damaged, inlet plugged.  

Pump delivers insufficient capacity  

1. Incorrect voltage  
4. Excessive inflow or pump not properly 
sized for application. 
5. Discharge restricted.  
6. Check valve stuck closed or installed 
backwards.  
7. Shut-off valve closed. 
8. Impeller clogged, loose on shaft, worn 
or damaged, inlet plugged.  
9. Pump may be air locked.  
10. Pump stator damaged / torn.  
16. Improper impeller face clearance   
17. Three Phase units rotating incorrectly 

Pump cycles too frequently or runs 
periodically when fixtures are not in use.  

6. Check valve stuck closed or installed 
backwards.  
11. Fixtures are leaking  
15. Ground water is entering basin.  

Pump shuts off and turns on independent 
of switch, (trips thermal overload 
protector). 

CAUTION: 

Pump may start 

unexpectedly. Disconnect power supply. 
High AMPS  

1. Incorrect voltage  
4. Excessive inflow or pump not properly 
sized for application.  
8. Impeller clogged, loose on shaft, worn 
or damaged, inlet plugged. 
12. Excessive water temperature 
16. Improper impeller face clearance  

Pump operates noisily or vibrates 
excessively.  

4. Operating at too high / low of pressure 
5. Discharge restricted.  
8. Impeller broken or clogged.  
13. Piping attachments to building 
structure too rigid or too loose.  
17. Three Phase units rotating incorrectly 

1. Check all electrical connections for security. Have 
electrician measure current in motor leads. If current is 
or-20% of locked rotor amps, impeller is probably 
locked. If current is 0, overload may be tripped. Remove 
power, allow pump to cool, then re-check current. 
 
2a. Reposition pump or clean basin as required to 
provide adequate clearance for float.  
 
2b. Disconnect level control. Set ohmmeter for a low 
range, such as 100 ohms full scale and connect to level 
control manually and check to see that ohmmeter shows 
zero ohms for closed switch and full scale for open 
switch. (Float Switch)  
 
3. Make sure liquid level is at least equal to suggested 
turn-on point. 
 
4. Re-check all sizing calculations to determine proper 
pump size. 
 
 5. Check discharge line for restrictions, including ice if 
line passes through or into cold areas.  
 
6. Remove and examine check valve for proper 
installation and freedom of operation. 
 
7. Open valve. 
 
8. Check impeller for freedom of operation and 
condition. Clean impeller and inlet of any obstruction. 
 
9. Loosen union slightly to allow trapped air to escape. 
Verify that turn-off level of switch is set so that the 
suction is always flooded. Clean vent hole. 
 
10. Remove & examine for damage. Replace pump 
stator if required.  
 
11. Repair fixtures as required to eliminate leakage  
 
12. Check pump temperature limits & fluid temperature.  
13. replace portion of discharge pipe with flexible 
connector.  
 
14. Turn to automatic position.  
 
15. Check for leaks around basin inlet and outlets.  
 
16. Check impeller to volute face clearance (See 
Service) 
 
17.  THREE PHASE UNITS:  Check Proper Rotation 

Page 6  

Содержание CPSE10 Series

Страница 1: ......

Страница 2: ......

Страница 3: ...he provisions of the warranty contact your installer For future reference record the following information Pump Model ____________________Pump Serial ______________________ Installer__________________...

Страница 4: ...r winding thermal protection Thermal protection shall not be used as a motor overload device A separate motor overload device must be provided in accordance with NEC Codes In the event of an overload...

Страница 5: ...al Chamber Oil Drain all oil from seal chamber and dispose of properly per local and environmental standards Set unit on its side with plug upward and refill with new oil approximately 13oz Apply pipe...

Страница 6: ...upply High AMPS 1 Incorrect voltage 4 Excessive inflow or pump not properly sized for application 8 Impeller clogged loose on shaft worn or damaged inlet plugged 12 Excessive water temperature 16 Impr...

Страница 7: ...Page 7...

Страница 8: ...Page 8...

Страница 9: ...ron Upper Lower Carbon Ceramic SHAFT 416 Stainless Steel Buna N Elastomer MOTOR 1 PHASE 3450 RPM 60 Hz 300 Series Stainless Steel Hardware Includes Overload Protection In The Motor BEARING UPPER LOWER...

Страница 10: ......

Страница 11: ...oor_____________ Was equipment stored ___________How long _________________________________ Liquid being pumped______________________________________________________ Debris in bottom of station ______...

Отзывы: