201066 - 6500W OPEN FRAME INvERTER

TROUbLESHOOTING

33

Problem

Cause

Solution

Engine starts and shuts off right away.

If equipped, when CO Shield

®

 shutoffs 

occur due to accumulating carbon 
monoxide (CO) and if the red LED light 
blinks on the panel.

Move generator to an open, outdoor area. Point 
exhaust away from people and buildings. Move 
to fresh air and get medical help if sick, dizzy, or 
weak.

Make sure there are no objects creating 
obstructions within 5 feet of the generator. 
Obstructions in the vicinity of the generator 
may trap carbon monoxide emissions near the 
generator and cause the engine to shutoff.   

If the generator’s exhaust is facing into the 
wind, the exhaust may be blown back into 
the generator’s operating area, creating an 
accumulation of CO emissions and triggering an 
engine shutoff. To avoid an engine shutoff, turn 
the generator 45° in either direction to allow 
the exhaust emissions to blow away from the 
generator. If engine shutoff events continue, 
readjust and align the exhaust with the wind 
direction to blow away from the generator.

If equipped, when CO Shield

®

 shutoffs 

occur due to system fault and if the 
yellow LED light blinks on the panel.

Start by confirming yellow LED light blinks when/
if generator shuts off. If CO Shield

®

 continues to 

sense the fault and shuts off, contact technical 
support.

Both CO Shield

®

 LEDs not blinking 10 

times upon start up.

Starting the generator within 1 minute 
after being manually shutoff, not a CO 
shutoff event.

Wait 1 minute before trying to restart the 
generator. The LEDs should then blink ten (10) 
times.

Generator cannot supply enough power 
or overheating.

Generator is overloaded.

Review load and adjust. See “Connecting 
Electrical Loads.”

Dirty air filter.

Clean or replace air filter.

Choke in wrong position.

Move choke until it stops under RUN position or 
push in completely.

Engine is running but no AC output.

Poor cord connection.

Check all connections.

Circuit breaker is open.

Reset circuit breaker. Check all circuit breakers.

Loose wiring.

Inspect and tighten wiring connections.

GFCI tripped.

Reset GFCI receptacle breakers by first pushing 
the TEST button then the RESET button until 
green LED illuminates. Contact the help line.

AC Overload: Button illuminated red

Reduce AC load and press Overload Reset Button 
until illuminated green.

Other.

Contact the help line.

Содержание 201066

Страница 1: ...ons and illustrations in this manual are as accurate as known at the time of publication but are subject to change without notice This product meets the requirements of the PGMA Portable Generator Man...

Страница 2: ...all carbon monoxide risks you ll be better prepared to protect your family from this colorless oderless threat CARBON MONOXIDE SAFETY THE BIG PICTURE KNOW THE SYMPTOMS Headache Nausea Shortness of br...

Страница 3: ...o Economy Mode 24 12V DC Regulated Automotive Style Outlet 24 Parallel Operation 25 Stopping the Engine 25 Moving the Generator 25 Operation at High Altitude 26 Maintenance 26 Cleaning the Generator 2...

Страница 4: ...fort has been made to ensure the accuracy and completeness of the information in this manual at the time of publication and we reserve the right to change alter and or improve the product and this doc...

Страница 5: ...g parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long hair and remove jewelry D...

Страница 6: ...nce is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and turned on CAUTION Exceeding the generator s running capacity can damage the g...

Страница 7: ...into the generator at the gas station Always use an approved container to transfer the fuel to the generator DO NOT overfill the gasoline tank Always keep gasoline away from sparks open flames pilot...

Страница 8: ...eado o d bil Aller l air frais et obtenir de l aide m dicale si malade tourdi ou faible ACTION LABEL ETIQUETA DE ACCI N TIQUETTE D ACTION Colors APN 3429 L SF Rev A Size 225 x 85 mm Artwork Notes 2mm...

Страница 9: ...fore operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into utility...

Страница 10: ...ge of available power from generator being used RV Ready Receptacle Choke Pull choke knob to CHOKE position Run Push choke knob to RUN position Locking Receptacle SYMBOL MEANING 12V Direct Current Cir...

Страница 11: ...dy them and learn their meaning Proper interpretation of these symbols will allow you to more safely operate the product Starting the Engine DANGER Move generator outside and far away from windows doo...

Страница 12: ...ngine by filtering dust and debris from the intake air 4 Recoil Starter Used to manually start the engine 5 Never Flat Wheels 8 in 20 3 cm 6 Control Panel See Control Panel section 7 Quick Drain Tube...

Страница 13: ...ntrol 8 Circuit Breakers Push Reset Protects the generator against electrical overloads RECEPTACLES A t 120V AC 30A RV NEMA TT 30R May be used to supply electrical power for operation of 120 Volt AC 3...

Страница 14: ...ion Example 6 hours Total Run Time Total run time of the generator since first operation Example 16 hours Power Meter Power Output percentage Example 100 Output Intelligauge with Power Meter and CO Sh...

Страница 15: ...cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radi...

Страница 16: ...ty 1 BEFORE filling the engine with oil or gasoline tip the generator onto its recoil end Tip onto the flattened cardboard box the generator came in or other protective surface so as to not scratch th...

Страница 17: ...If running generator in extreme temperatures refer to the Recommended Engine Oil Type chart 20 0 20 40 60 Ambient temperature Recommended Engine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37...

Страница 18: ...lean fresh regular unleaded gasoline with a minimum octane rating of 87 and an ethanol content of 10 or less by volume y b c DO NOT mix oil with gasoline 1 Remove the gasoline cap 2 Slowly add gasolin...

Страница 19: ...your Specifications section for specified type of grounding OPERATION CO Shield Carbon Monoxide CO Detection and Auto shutoff System CO Shield technology monitors the accumulation of carbon monoxide...

Страница 20: ...after it was manually shut off This does not occur if generator shut off from a high CO event If CO Shield system experiences a fault and no longer provides protection the generator is shutoff automat...

Страница 21: ...erly cool before transport or for storage purposes Failure to follow proper safety precautions may result in personal injury damage to the generator and void the manufacturer s warranty WARNING During...

Страница 22: ...hree attempts Too much choke leads to spark plug fouling and engine flooding This will cause the engine not to start NOTICE For gasoline starting in cold ambient temperature 59 F 15 C Keep the choke i...

Страница 23: ...entify the highest starting wattage of all devices identified in step 1 Add this number to the number calculated in step 2 Starting wattage is the surge of power needed to start some electric driven e...

Страница 24: ...times of reduced electrical output Eco Mode allows the engine speed to idle during periods of non use The engine speed returns to normal when an electrical load is connected When the economy switch is...

Страница 25: ...s plugged in or turned on 2 Let the generator run at no load for several minutes to stabilize internal temperatures of the engine and generator 3 Turn the fuel valve to the OFF position 4 Press the en...

Страница 26: ...tion at lower elevations the originally supplied standard main jet must be used Operating the engine with the wrong engine configuration at a given altitude may increase its emissions and decrease fue...

Страница 27: ...DO NOT screw in the dipstick while checking Cleaning and Adjusting the Spark Plug 1 Remove the spark plug cable from the spark plug 2 Use a spark plug socket tool not included or a 13 16 in 21 mm sock...

Страница 28: ...e Governor WARNING Tampering with the factory set governor will void your warranty The air fuel mixture is not adjustable Tampering with the governor can damage your generator and your electrical devi...

Страница 29: ...l and appropriate hose if necessary under the carburetor drain bolt to avoid spillage 5d When gasoline stops flowing from the carburetor replace and tighten the carburetor drain bolt and be sure to pr...

Страница 30: ...g stored follow the below steps when removing from storage 1 Be sure the engine switch is in the OFF position 2 Add gasoline to the generator according to Add Fuel 3 Turn the fuel valve to the ON posi...

Страница 31: ...20 40 60 Ambient temperature Recommended Engine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Full Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and eng...

Страница 32: ...when CO Shield shutoffs occur due to accumulating carbon monoxide CO and if the red LED light blinks on the panel Move generator to an open outdoor area Point exhaust away from people and buildings Mo...

Страница 33: ...ipped when CO Shield shutoffs occur due to system fault and if the yellow LED light blinks on the panel Start by confirming yellow LED light blinks when if generator shuts off If CO Shield continues t...

Страница 34: ...n wrong position Move choke until it stops under RUN position or push in completely Repeated circuit breaker tripping Overload Review load and adjust See Connecting Electrical Loads Faulty power cords...

Страница 35: ...or connected incorrectly to any electrical component Normal maintenance is not covered by this warranty and is not required to be performed at a facility or by a person authorized by CPE Other Exclusi...

Страница 36: ...condition exits CPE will repair your small off road engine SORE and equipment at no cost to you including diagnosis parts and labor MANUFACTURER S WARRANTY COVERAGE This Emissions Control System is w...

Страница 37: ...shall be warranted for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replace...

Страница 38: ...Mounting Brackets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or other p...

Отзывы: