102006 - AUTOMATIC TRANSFER SWITCH WITH aXis CONTROLLER™ MODULE

IMPORTANT SAFETY INSTRUCTIONS

4

IMPORTANT SAFETY INSTRUCTIONS

 

WARNING

Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Instructions for Champion Automatic 
Transfer Switch with aXis Controller

TM

 

Module

THE CHAMPION AUTOMATIC TRANSFER SWITCH WITH aXis 
CONTROLLER

TM

 MODULE IS NOT FOR “DO-IT-YOURSELF” 

INSTALLATION. It must be installed by a qualified electrician 
thoroughly familiar with all applicable electrical and building 
codes.

This manual has been prepared for familiarizing servicing dealer/
installer with the design, application, installation and servicing of 
the equipment.

Read the manual carefully and comply with all instructions.

This manual or a copy of this manual should remain with the 
switch. Every effort has been taken to make sure that the contents 
of this manual are accurate and current.

The manufacturer reserves the right to change, alter or otherwise 
improve this literature and the product at any time without prior 
notice and without any obligation or liability whatsoever.

The manufacturer cannot anticipate every possible circumstance 
that might involve a hazard.

The warnings in this manual, tags and decals affixed to the unit 
are, therefore, not all-inclusive. If using a procedure, work method 
or operating technique the manufacturer does not specifically 
recommend follow all codes to ensure safety for personnel.

Many accidents are caused by failing to follow simple and 
fundamental rules, codes and precautions. Before installing, 
operating or servicing this equipment, read the SAFETY RULES 
carefully.

The publications that cover the safe use of ATS and installation 
are the following NFPA 70, NFPA 70E, UL 1008 and UL 67. It is 
important to refer to the latest version of any standard/code to 
ensure correct and current information. All installations must 
comply with local municipal, state and national codes.

before Installation

 

WARNING

Per OSHA 3120 Publication; “lockout/tagout” refers to 
specific practices and procedures to safeguard individuals 
from the unexpected energization or startup of machinery 
and equipment, or the release of hazardous energy during 
installation, service or maintenance activities.

 

WARNING

Be certain that the power from the utility is turned off and all 
backup sources are locked out before starting this procedure. 
Failure to do so could result in serious injury or death. Be 
aware, automatic start generators will start upon loss of utility 
mains power unless locked in the “off” position. 

Consult the generator operator manual section to locate the 
ATS CONTROL and ENGINE CONTROL modules to make sure 
both switches are in the OFF position.

 

CAUTION

Consult with your Local municipal, State and National 
electrical codes for proper mandatory wiring methods.

Содержание 102006

Страница 1: ...his manual contains important safety precautions which should be read and understood before operating the product Failure to do so could result in serious injury This manual should remain with the pro...

Страница 2: ...atic Transfer Switch with aXis ControllerTM Module 6 Panel Board Safety Information 7 Unpacking 8 Location and Mounting 8 Electrical Grommet s 8 Installation Wiring for ATS Utility Socket 9 Wiring the...

Страница 3: ...e Please always exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be sati...

Страница 4: ...operating technique the manufacturer does not specifically recommend follow all codes to ensure safety for personnel Many accidents are caused by failing to follow simple and fundamental rules codes...

Страница 5: ...ntial and privileged and shall not be disclosed to or used by or for outside parties without the explicit consent of Champion Power Equipment 152 Alternate Power Source 2 This switch will not transfer...

Страница 6: ...ls and features Save this manual for future reference Champion Automatic Transfer Switch with aXis ControllerTM Module 1 aXis Controller 2 Antenna 3 Generator L1 and L2 Terminals 4 Battery Charger Fus...

Страница 7: ...5 Wire land 5 B B BLACK 6 Wire land 6 B R RED A 120VAC circuit must be installed for battery charging From ATS fuse block or distribution panel install L1 and N to Wire land 2 and 3 respectively Autom...

Страница 8: ...or future reference TOOLS REQUIRED NOT INCLUDED 5 16 in Hex Wrench Mounting Hardware Line Voltage Wire 1 4 in Flat Screwdriver Conduit Fittings Location and Mounting Install the ATS as close as possib...

Страница 9: ...a wire brush All power cables must enter the enclosure through the enclosure knockouts 1 Determine where the flexible liquid tight conduit will pass through the building from the inside to outside Whe...

Страница 10: ...voltage controls route your low voltage wiring into the ATS using code appropriate conduit and fittings Connect the wiring to pin 1 and pin 2 of either AC1 or AC2 as shown in the diagram above Please...

Страница 11: ...lled HSB Off ATS will control the start of the HSB using the AC2 Relay In this setting the AC2 can not be used to manage a load Pins 1 and 3 of the AC2 connector will be used for the HSB startup signa...

Страница 12: ...here are three tabs located at the top of the page ATS GEN and LMM Each tab will display the status for the Transfer Switch Home Standby Generator or Load Management Module s respectively 4 When finis...

Страница 13: ...ICATIONS aXis ControllerTM Module Automatic Transfer Switch Model Number 102006 Enclosure Style NEMA 3R outdoor Maximum Amps 200 Nominal Volts 120 240 Load Management Circuits 4 Weight 43 lbs 19 6 kg...

Страница 14: ...he life of a part or the equipment as a whole Installation Use and Maintenance This warranty will not apply to parts and or labor if the product is deemed to have been misused neglected involved in an...

Отзывы: