100565 - 2000W PORTABLE INVERTER GENERATOR

OPERATION

17

Grounding

Your generator must be properly connected to an appropriate 
ground to help prevent electric shock.

 

WARNING

Failure to properly ground the generator can result in 
electric shock.

A ground terminal connected to the frame of the generator has 
been provided (see 

Controls and Features

 for terminal location). 

For remote grounding, connect of a length of heavy gauge 
(12 AWG minimum) copper wire between the generator ground 
terminal and a copper rod driven into the ground. We strongly 
recommend that you consult with a qualified electrician to 
ensure compliance with local electrical codes.

OPERATION

Generator Location

NEVER operate the generator inside any building, including 
garages, basements, crawlspaces and sheds, enclosure or 
compartment, including the generator compartment of a 
recreational vehicle. Please consult your local authority. In 
some areas, generators must be registered with the local 
utility. Generators used at construction sites may be subject 
to additional rules and regulations. Generators should be on 
a flat, level surface at all times. (Even while not in operation) 
Generators must have at least 5 ft. (1.5 m) of clearance from 
all combustible material. In addition to clearance from all 
combustible material, generators must also have at least 3 ft. 
(91.4 cm) of clearance on all sides to allow for adequate cooling, 
maintenance and servicing. Generators should never be started 
or operated in the back of a SUV, camper, trailer, in the bed of 
a truck (regular, flat or otherwise), under staircases/stairwells, 
next to walls or buildings, or in any other location that will not 
allow for adequate cooling of the generator and/or the muffler. 
DO NOT contain generators during operation. Allow generators 
to properly cool before transport or storage.

Install battery-operated carbon monoxide alarms or plug-in 
carbon monoxide alarms with battery back-up in your home 
according to the manufacturer’s instructions.

Place the generator in a well-ventilated area. DO NOT place the 
generator near vents or intakes where exhaust fumes could 
be drawn into occupied or confined spaces. Carefully consider 
wind and air currents when positioning generator.

Failure to follow proper safety precautions may void 
manufacturer’s warranty.

 

WARNING

Do not operate or store the generator in rain, snow, or wet 
weather.

Using a generator or electrical appliance in wet conditions, 
such as rain or snow, or near a pool or sprinkler system, 
or when your hands are wet, could result in electrocution.

 

WARNING

During operation the muffler and exhaust fumes produced 
will become hot. If adequate cooling and breathing space 
are not supplied, or if the generator is blocked or contained, 
temperatures can become extremely heated and may lead 
to fire.

Grounding

A ground terminal connected to the frame of the generator has 
been provided (see Controls and Features for terminal location).

Neutral Floating*

 

Neutral circuit 

IS NOT

 electrically connected to the frame/

ground of the generator.

 

The generator (stator winding) is isolated from the frame 
and from the AC receptacle ground pin.

 

Electrical devices that require a grounded receptacle pin 
connection will not function if the receptacle ground pin is 
not functional.

Neutral Bonded to Frame*

 

Neutral circuit 

IS

 electrically connected to the frame/ground 

of the generator.

 

The generator system ground connects lower frame 
cross-member below the alternator. The system ground is 
connected to the AC neutral wire.

* See your model's outlet panel for specified type of grounding.

Surge Protection

Electronic devices, including computers and many 
programmable appliances use components that are designed 
to operate within a narrow voltage range and may be affected 
by momentary voltage fluctuations. While there is no way to 
prevent voltage fluctuations, you can take steps to protect 
sensitive electronic equipment. 

 

Install UL1449, CSA-listed, plug-in surge suppressors on the 
outlets feeding your sensitive equipment.  
Surge suppressors come in single- or multi-outlet styles. 
They’re designed to protect against virtually all short-
duration voltage fluctuations.

Содержание 100565

Страница 1: ...rating the product Failure to do so could result in serious injury This manual should remain with the product Specifications descriptions and illustrations in this manual are as accurate as known at t...

Страница 2: ...Generator 20 Maintenance 21 Cleaning the Generator 21 Changing the Engine Oil 21 Cleaning and Adjusting the Spark Plug s 21 Cleaning the Air Filter 22 Cleaning the Spark Arrestor 22 Replacing Fuel Lig...

Страница 3: ...lways exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be satisfied with...

Страница 4: ...ting parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long hair and remove jewelr...

Страница 5: ...ould result When starting engine pull the starter cord slowly until resistance is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and tu...

Страница 6: ...from the gasoline tank Only fill or drain gasoline outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Always use an approved fuel container to tran...

Страница 7: ...afety Symbols C UNLEADED FUEL ONLY Minimum octane rating of 85 Maximum 10 ethanol GASOLINA REGULAR SOLAMENTE 85 octanos como m nimo M ximo de etanol de 10 ESSENCE SANS PLOMB SEULEMENT Indice d octane...

Страница 8: ...s before operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into util...

Страница 9: ...ow you to more safely operate the product SYMBOL MEANING Engine START Engine RUN Engine STOP Run out of fuel Stopping the generator Choke Run Overload Reset Switch Overload SYMBOL MEANING Low Oil Leve...

Страница 10: ...N position 4 Turn EZ Start dial clockwise to the full CHOKE position 5 Pull the starter cord 6 Move the EZ Start dial to the RUN position 7 Plug in desired device Stopping the Engine 1 Turn off and un...

Страница 11: ...r 1 Carrying Handle Used to lift or carry the unit 2 Recoil Starter Used to manually start the engine 3 EZ Start Dial Used to start and stop the generator 4 Outlet Panel See Outlet Panel section 5 Pow...

Страница 12: ...d Indicator Light When ON generator is overloaded and power to receptacles is cut 3 Low Oil Level Indicator 3a Off Oil level OK 3b Yellow Oil level low Unit will shut down or not start until oil is at...

Страница 13: ...rical loads 1 Ground Terminal Consult an electrician for local grounding regulations 2 Circuit Breakers Push Reset Protects the generator against electrical overloads 3 Parallel Outlets Used for paral...

Страница 14: ...against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may c...

Страница 15: ...ated ball bearing that requires no additional lubrication for the life of the bearing NOTICE The recommended oil type is 10W 30 automotive oil 20 0 20 40 60 Ambient temperature Recommended Oil Type 80...

Страница 16: ...ew on the gasoline cap and wipe away any spilled fuel CAUTION Use unleaded gasoline with a minimum octane rating of 85 and an ethanol content of 10 or less by volume DO NOT light cigarettes or smoke w...

Страница 17: ...structions Place the generator in a well ventilated area DO NOT place the generator near vents or intakes where exhaust fumes could be drawn into occupied or confined spaces Carefully consider wind an...

Страница 18: ...Rotate the EZ Start dial to 75 of the full choke position for only one pull of the recoil starter If generator does not start after first pull rotate the dial to the RUN position for the next three pu...

Страница 19: ...start some electric driven equipment Following the steps listed under Power Management will guarantee that only one device will be starting at a time Power Management Use the following formula to con...

Страница 20: ...generator Parallel Operation The Champion model 100565 is parallel ready and can be operated in parallel with another Champion unit to increase the total available electrical power A Champion model 1...

Страница 21: ...erator through the cooling slots and damage the generator windings It can also contaminate the fuel system 1 Use a damp cloth to clean exterior surfaces of the generator 2 Use a soft bristle brush to...

Страница 22: ...he filter in the assembly 8 Reattach the air filter cover 9 Reinstall the maintenance cover and tighten the cover screw securely Cleaning the Spark Arrestor 1 Allow the engine to cool completely befor...

Страница 23: ...cell 5 Insert the small spring back into the pocket of the upper cover and press the upper cover into place to complete the installation Adjusting the Governor WARNING Tampering with the factory set g...

Страница 24: ...p and clog the carburetor if it isn t used or drained within 2 4 weeks 1 Be sure all appliances are disconnected from the generator 2 Add a properly formulated fuel stabilizer to the gasoline tank 3 S...

Страница 25: ...rom storage 1 Be sure the EZ Start dial is in the STOP position 2 Add gasoline to the generator according to Add Fuel Gasoline 3 Move the EZ Start dial to the START position 4 After 5 minutes check th...

Страница 26: ...80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change the type of engine oil used based on t...

Страница 27: ...s Diagram 61 57 17 58 59 53 50 51 49 62 63 64 65 66 62 31 32 1 33 35 31 5 6 7 8 71 77 69 72 74 75 78 79 70 76 10 16 18 19 20 21 16 22 23 24 16 30 29 28 54 56 25 26 38 39 40 48 47 46 45 44 1 2 13 15 14...

Страница 28: ...acket 3 33 62 200402 00 Protector Rear Cover Black 1 34 1 896 05 Split Washer 5 1 35 62 200410 00 Rotary Knob Protector Rear Cover 1 Part Number Description Qty 36 1 819 0414 3 Sunk Screw M4 14 4 37 6...

Страница 29: ...e DC12V 1 72 1 5783 0516 3 Bolt M5 x 16 Green 1 73 1 862 05 Lock Washer 5 Toothed 2 74 1 97 1 05 3 Washer 5 Green 1 75 1 6170 05 3 Nut M5 Green 2 76 62 01 4 2 Control Panel 1 77 5 1213 920 20Amp Circu...

Страница 30: ...86 14 84 83 82 91 89 85 17 16 23 24 22 25 26 15 14 20 21 6 13 19 18 74 75 76 77 78 79 28 29 30 27 31 32 33 2 34 35 36 35 80 52 25 53 54 55 56 57 58 60 61 63 64 65 66 72 71 70 62 59 42 48 14 49 47 50...

Страница 31: ...y 1 37 2 01 026 Stud Bolt M6 x 88 2 38 81 130002 00 Gasket Insulator 1 39 81 130001 00 Insulator Carburetor 1 Part Number Description Qty 40 81 130003 00 Gasket Carburetor 1 41 62 130000 00 Carburetor...

Страница 32: ...81 101501 00 Cap Spark Arrester 1 93 62 081200 00 Middle Shield Muffler 1 94 1 70 0616 Inside Hexagonal Bolt M6 x 16 1 95 1 845 4817 Tapping Screw ST4 8 x 17 4 96 62 081300 00 Terminal Shield Muffler...

Страница 33: ...OR ENGINE IGNITION COIL 5 20R AC COIL SUB COIL O Y L C G Y L R R R Y Y R W TCI UNIT R R B G Y G Y G Y C CARNATION A AMETHYST O ORANGE POWER PANEL CONTROL PANEL CIRCUIT BREAKER 20A W W R C 8A 4 5 6 3 2...

Страница 34: ...ogged spark arrestor Clean spark arrestor Generator cannot supply enough power or overheating Generator is overloaded Review load and adjust See Connecting Electrical Loads Dirty air filter Clean or r...

Страница 35: ...nent Normal maintenance is not covered by this warranty and is not required to be performed at a facility or by a person authorized by CPE Other Exclusions This warranty excludes Cosmetic defects such...

Отзывы: