background image

© 2010 UTC Fire & Security. All rights reserved. 

1 / 10 

P/N 3100010 • REV 7 • ISS 04AUG10 

 

5540M Tone Generator and 5532M 

Speaker/Amplifier Installation Sheet 

 

Description 

Edwards Tone Generator and Speaker/Amplifiers are 
intended for industrial applications where high audible output 
and microcomputer reliability are required.  The Adaptatone 
Millennium Series are UL and cUL Listed as Audible Signal 
Appliances for use in the hazardous locations listed in 
Table 1. 

The 5532B Speaker/Amplifiers are UL Listed and CSA 
Certified as Audible Signaling Appliances. 

The 5532M-Y6 is additionally UL Listed in a Speaker and 
Amplifier category, when powered with 120V/240 VAC 50/60 
Hz, for use in conjunction with the 5541M-Y6 Millennium 
System Master either for emergency/evacuation, non-fire, or 
for supplementary fire alarm control panel accessory 
applications (see Instructions for 5541M-Y6, part 3100471). 

The Tone Generator operates from local power.   It 
accommodates up to four normally-open contacts on its 
inputs.  The tone that sounds in response to an active input 
is determined by setting miniature programming switches 
inside the unit.  Table 6 has switch settings for setting tones. 

Four tones may be programmed into the Tone Generator at 
any time.  These tones operate on a pyramid-type priority 
system.  The tone programmed on SW1 overrides the tones 
programmed on SW2, SW3, and SW4.  The tone on SW2 
overrides the tones programmed on SW3 and SW4.  
Likewise, the tone on SW3 overrides the tone programmed 
on SW4.  The tone programmed on SW4 has the lowest 
priority and cannot override any other programmed tone. 

Speaker/Amplifiers are heavy-duty, stand-alone signaling 
devices that operate from local power and sound a tone 
programmed at the Tone Generator.  Speaker direction and 
the output level are easily adjustable.  Up to 2500 of these 
Speaker/Amplifiers can be connected in parallel to the tone 
output of a single tone generator. 

Recording a Voice Message (5540MV 
Series) 

WARNING

:  High voltage is present when product is 

energized. 

Four five-second messages (or one twenty-second 
message) can be recorded on the voice module unit.  Refer 
to Figure 16. 

1.  Put switches A and B on the programming dipswitch in 

the proper position for the message to be recorded 
(Figure 16).  For programming a message longer than 
five seconds, use Message Location 1. 

 

Message 
Location 

Start Switch 

Settings 

Switch B 
Settings 

1 0 

Sec 

CLOSED 

CLOSED 

2 5 

Sec 

OPEN 

CLOSED 

3 10 

Sec 

CLOSED 

OPEN 

4 15 

Sec 

OPEN 

OPEN 

 

2.  Put switch PGM on the programming dipswitch in the 

“CLOSED”  position for programming mode (Figure 16). 

3.  Press and hold the record button while speaking clearly 

into the microphone to record your message.  Release 
the button when recording is complete. 

4.  To test the message, press and hold PLAY while in 

programming mode. 

NOTE:  This will play only the current location. 

WARNING:

  High volume may cause harm to personnel in 

close proximity. 

5.  Adjust the volume as necessary.  Set the main volume 

using the potentiometer on the main board (Figure 14 - 
Figure 16) and then set the voice volume using the 
potentiometer on the voice module board (Figure 16). 

Содержание 5532M

Страница 1: ...on SW3 overrides the tone programmed on SW4 The tone programmed on SW4 has the lowest priority and cannot override any other programmed tone Speaker Amplifiers are heavy duty stand alone signaling devices that operate from local power and sound a tone programmed at the Tone Generator Speaker direction and the output level are easily adjustable Up to 2500 of these Speaker Amplifiers can be connecte...

Страница 2: ...eaker to the approximate desired position WARNING To ensure integrity of the Adaptatone assembly when adjusting the speaker direction make sure threads in the enclosure remain fully engaged and do not turn speaker more than 360 degrees from the original factory installed position Ensure that the 4 collar gaskets part number P 041930 0362 are in place on each cover screw before securing the signal ...

Страница 3: ...e generator select the appropriate method of wiring to the input board from Figure 7 Figure 13 Connect the tone generator as shown d For 5532B AQ 5532BDV2 AQ and 5532BHV AQ models connect power source to the speaker amplifiers at TS2 Polarity must be observed for DC models e For 5532B Y6 5532BDV2 Y6 5532BHV Y6 and 5532B N5 models connect incoming power to wire leads from power supply For Y6 models...

Страница 4: ...lock TB1 input circuit Figure 4 Wiring the 5532M series speaker amplifier Figure 5 Wiring the 5540M series tone generator Figure 6 Wiring the 5540MV series tone generator with voice messaging Figure 7 Wiring an open collector transistor to tone generator input board ...

Страница 5: ...r to Applications Engineering for compatibility with earlier versions of Adaptatone Figure 9 Connecting 24 V input board of tone generator to a PLC Refer to Table 5 Figure 10 Wiring multiple dry relay contacts to 24 V tone generator input board method 2 Figure 11 Wiring multiple dry contacts to 120 V tone generator input board ...

Страница 6: ...to 120 V tone generator input board Refer to Table 5 Figure 13 Wiring audio output of tone generator to speaker amplifier audio coupler board Figure 14 5532M Series PC board locations Figure 15 5540M Series PC board locations Figure 16 5540MV Series PC board locations ...

Страница 7: ...P N 3100010 REV 7 ISS 04AUG10 7 10 Figure 17 Connecting to the 5532B series speaker amplifiers ...

Страница 8: ...6 125 VDC 250 VDC 120 VAC 50 60 Hz 240 VAC 50 60 Hz 0 10 A 0 02 A 0 10 A 0 10 A 0 20 A 0 10 A 0 31 A 0 20 A Speaker Amplifier Standard Volume 5532M AQ 24 VDC 24 VAC 50 60 Hz 0 10 A 0 10 A 0 74 A 1 3 A 5532M N5 120 VAC 50 60 Hz 0 10 A 0 36 A 5532M Y6 125 VDC 250 VDC 120 VAC 50 60 Hz 240 VAC 50 60 Hz 0 10 A 0 02 A 0 10 A 0 10 A 0 21 A 0 10 A 0 32 A 0 20 A 5532B AQ 24 VDC 36 VDC 24 VAC 60 Hz 24 VAC 5...

Страница 9: ...Whoop OFF OFF OFF ON OFF ON 600 1250 Hz upward sweep in 4 s and repeat 05 Beep OFF OFF OFF ON ON OFF 470 Hz 0 55 s on 0 55 s off 06 Chime 1 OFF OFF OFF ON ON ON 700 Hz percussive repeat at 1 Hz 07 Fast Whoop OFF OFF ON OFF OFF OFF 600 1250 Hz upward in 1 s and repeat 08 Hi Lo OFF OFF ON OFF OFF ON 780 to 600 Hz alternately 0 52 s each 09 Rapid Siren OFF OFF ON OFF ON OFF 600 1250 Hz up and down sw...

Страница 10: ...OFF OFF 1207 Hz and 493 Hz alternately 0 002 s each 2C Warning 2 ON OFF ON ON OFF ON 2336 Hz and 493 Hz alternately 0 005 s each 2D Warning 2 Beep ON OFF ON ON ON OFF 0 500 s of 2336 Hz and 493 Hz each alternating for 0 005 s followed by 1 s delay 2E Caution ON OFF ON ON ON ON 453 Hz for 0 040 s 235 Hz for 0 020 s 235 Hz for 0 160 s 260 Hz for 0 050 s 260 Hz for 0 1009 s 235 Hz for 0 050 s 2F Mult...