100565 - 2000W PORTABLE INVERTER GENERATOR

OPERATION

18

Starting the Engine

1.  Make certain the generator is on a flat, level surface. 

2.  Disconnect all electrical loads from the generator. Never 

start or stop the generator with electrical devices plugged 
in or turned on.

3.  Turn the fuel cap vent lever to the “ON” position.

4.  Turn EZ Start dial counterclockwise to the full CHOKE 

position.

5.  Pull the starter cord slowly until resistance is felt and then 

pull rapidly.

6.  As the engine warms up, move the EZ Start dial to the RUN 

position.

 

NOTICE

Keep EZ Start dial in “CHOKE” position for only 1 pull of 
the recoil starter. If generator does not start after first pull, 
rotate the EZ Start dial to the RUN position for the next 
three pulls. Too much choke leads do spark plug fouling and 
engine flooding.  This will cause the engine not to start.

 

NOTICE

For gasoline restarts with hot engine in hot ambient 
> 86°F (30°C):

 Rotate the EZ Start dial to 75% of the 

full choke position for only one pull of the recoil starter. If 
generator does not start after first pull, rotate the dial to the 
RUN position for the next three pulls. Too much choke leads 
do spark plug fouling and engine flooding. This will cause 
the engine not to start.

 

NOTICE

For gas starting in cold ambient < 59°F (15°C): 

The 

choke must be in 100% of the “CHOKE” position for recoil 
start procedures. Do not over-choke. As soon as the engine 
starts, turn the EZ Start dial to the RUN position.

 

NOTICE

If the engine starts but does not continue to run make 
certain that the generator is on a flat, level surface. The 
engine is equipped with a low oil sensor that will prevent the 
engine from running when the oil level falls below a critical 
threshold.

Connecting Electrical Loads

Let the engine stabilize and warm up for a few minutes after 
starting.

Plug in and turn on the desired 120 or 240 (if applicable) Volt AC 
single phase, 60 Hz electrical loads.

 

DO NOT connect 3-phase loads to the generator.

 

DO NOT connect 50 Hz loads to the generator.

 

DO NOT overload the generator.

Содержание 100565

Страница 1: ...rating the product Failure to do so could result in serious injury This manual should remain with the product Specifications descriptions and illustrations in this manual are as accurate as known at t...

Страница 2: ...Generator 20 Maintenance 21 Cleaning the Generator 21 Changing the Engine Oil 21 Cleaning and Adjusting the Spark Plug s 21 Cleaning the Air Filter 22 Cleaning the Spark Arrestor 22 Replacing Fuel Lig...

Страница 3: ...lways exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be satisfied with...

Страница 4: ...ting parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long hair and remove jewelr...

Страница 5: ...ould result When starting engine pull the starter cord slowly until resistance is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and tu...

Страница 6: ...from the gasoline tank Only fill or drain gasoline outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Always use an approved fuel container to tran...

Страница 7: ...afety Symbols C UNLEADED FUEL ONLY Minimum octane rating of 85 Maximum 10 ethanol GASOLINA REGULAR SOLAMENTE 85 octanos como m nimo M ximo de etanol de 10 ESSENCE SANS PLOMB SEULEMENT Indice d octane...

Страница 8: ...s before operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into util...

Страница 9: ...ow you to more safely operate the product SYMBOL MEANING Engine START Engine RUN Engine STOP Run out of fuel Stopping the generator Choke Run Overload Reset Switch Overload SYMBOL MEANING Low Oil Leve...

Страница 10: ...N position 4 Turn EZ Start dial clockwise to the full CHOKE position 5 Pull the starter cord 6 Move the EZ Start dial to the RUN position 7 Plug in desired device Stopping the Engine 1 Turn off and un...

Страница 11: ...r 1 Carrying Handle Used to lift or carry the unit 2 Recoil Starter Used to manually start the engine 3 EZ Start Dial Used to start and stop the generator 4 Outlet Panel See Outlet Panel section 5 Pow...

Страница 12: ...d Indicator Light When ON generator is overloaded and power to receptacles is cut 3 Low Oil Level Indicator 3a Off Oil level OK 3b Yellow Oil level low Unit will shut down or not start until oil is at...

Страница 13: ...rical loads 1 Ground Terminal Consult an electrician for local grounding regulations 2 Circuit Breakers Push Reset Protects the generator against electrical overloads 3 Parallel Outlets Used for paral...

Страница 14: ...against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may c...

Страница 15: ...ated ball bearing that requires no additional lubrication for the life of the bearing NOTICE The recommended oil type is 10W 30 automotive oil 20 0 20 40 60 Ambient temperature Recommended Oil Type 80...

Страница 16: ...ew on the gasoline cap and wipe away any spilled fuel CAUTION Use unleaded gasoline with a minimum octane rating of 85 and an ethanol content of 10 or less by volume DO NOT light cigarettes or smoke w...

Страница 17: ...structions Place the generator in a well ventilated area DO NOT place the generator near vents or intakes where exhaust fumes could be drawn into occupied or confined spaces Carefully consider wind an...

Страница 18: ...Rotate the EZ Start dial to 75 of the full choke position for only one pull of the recoil starter If generator does not start after first pull rotate the dial to the RUN position for the next three pu...

Страница 19: ...start some electric driven equipment Following the steps listed under Power Management will guarantee that only one device will be starting at a time Power Management Use the following formula to con...

Страница 20: ...generator Parallel Operation The Champion model 100565 is parallel ready and can be operated in parallel with another Champion unit to increase the total available electrical power A Champion model 1...

Страница 21: ...erator through the cooling slots and damage the generator windings It can also contaminate the fuel system 1 Use a damp cloth to clean exterior surfaces of the generator 2 Use a soft bristle brush to...

Страница 22: ...he filter in the assembly 8 Reattach the air filter cover 9 Reinstall the maintenance cover and tighten the cover screw securely Cleaning the Spark Arrestor 1 Allow the engine to cool completely befor...

Страница 23: ...cell 5 Insert the small spring back into the pocket of the upper cover and press the upper cover into place to complete the installation Adjusting the Governor WARNING Tampering with the factory set g...

Страница 24: ...p and clog the carburetor if it isn t used or drained within 2 4 weeks 1 Be sure all appliances are disconnected from the generator 2 Add a properly formulated fuel stabilizer to the gasoline tank 3 S...

Страница 25: ...rom storage 1 Be sure the EZ Start dial is in the STOP position 2 Add gasoline to the generator according to Add Fuel Gasoline 3 Move the EZ Start dial to the START position 4 After 5 minutes check th...

Страница 26: ...80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change the type of engine oil used based on t...

Страница 27: ...s Diagram 61 57 17 58 59 53 50 51 49 62 63 64 65 66 62 31 32 1 33 35 31 5 6 7 8 71 77 69 72 74 75 78 79 70 76 10 16 18 19 20 21 16 22 23 24 16 30 29 28 54 56 25 26 38 39 40 48 47 46 45 44 1 2 13 15 14...

Страница 28: ...acket 3 33 62 200402 00 Protector Rear Cover Black 1 34 1 896 05 Split Washer 5 1 35 62 200410 00 Rotary Knob Protector Rear Cover 1 Part Number Description Qty 36 1 819 0414 3 Sunk Screw M4 14 4 37 6...

Страница 29: ...e DC12V 1 72 1 5783 0516 3 Bolt M5 x 16 Green 1 73 1 862 05 Lock Washer 5 Toothed 2 74 1 97 1 05 3 Washer 5 Green 1 75 1 6170 05 3 Nut M5 Green 2 76 62 01 4 2 Control Panel 1 77 5 1213 920 20Amp Circu...

Страница 30: ...86 14 84 83 82 91 89 85 17 16 23 24 22 25 26 15 14 20 21 6 13 19 18 74 75 76 77 78 79 28 29 30 27 31 32 33 2 34 35 36 35 80 52 25 53 54 55 56 57 58 60 61 63 64 65 66 72 71 70 62 59 42 48 14 49 47 50...

Страница 31: ...y 1 37 2 01 026 Stud Bolt M6 x 88 2 38 81 130002 00 Gasket Insulator 1 39 81 130001 00 Insulator Carburetor 1 Part Number Description Qty 40 81 130003 00 Gasket Carburetor 1 41 62 130000 00 Carburetor...

Страница 32: ...81 101501 00 Cap Spark Arrester 1 93 62 081200 00 Middle Shield Muffler 1 94 1 70 0616 Inside Hexagonal Bolt M6 x 16 1 95 1 845 4817 Tapping Screw ST4 8 x 17 4 96 62 081300 00 Terminal Shield Muffler...

Страница 33: ...OR ENGINE IGNITION COIL 5 20R AC COIL SUB COIL O Y L C G Y L R R R Y Y R W TCI UNIT R R B G Y G Y G Y C CARNATION A AMETHYST O ORANGE POWER PANEL CONTROL PANEL CIRCUIT BREAKER 20A W W R C 8A 4 5 6 3 2...

Страница 34: ...ogged spark arrestor Clean spark arrestor Generator cannot supply enough power or overheating Generator is overloaded Review load and adjust See Connecting Electrical Loads Dirty air filter Clean or r...

Страница 35: ...nent Normal maintenance is not covered by this warranty and is not required to be performed at a facility or by a person authorized by CPE Other Exclusions This warranty excludes Cosmetic defects such...

Отзывы: