aXis CONTROLLER HOME STANDBY GENERATOR

INSTALLATION

33

When the icon remains lit, the battery charging should be checked 
and the condition of the batteries. Follow reset procedures 
contained in the manuals specific to your model to clear or 
correct.

Requires Maintenance

 

The RED icon will be lit if the HSB generator is ready for 
maintenance.

Fault protection-continued

In all cases when the icon is RED, this is an indicator that the 
HSB has registered a fault and must be corrected. Only the “LOW 
BATTERY” and “MAINTENANCE” icons will not latch out or shut 
down the HSB. ALL other RED icon faults will latch out, shut down, 
disable starting and light the RED icon on the aXis Controller 
Module and the Exterior Fault Code icon on the backside of the 
HSB.

Approximate Engine Starter Crank Cycle Times

10 seconds ON

10 seconds OFF

(5 Cycles Total)

If the HSB fails to start, the “OVER CRANK” icon will be lit on the 
aXis Controller module and the exterior fault code indicator icon on 
the backside of the HSB.

Fault Code Reset

In the event a fault has occurred push OFF button to reset then 
MAN or AUTO button to re-arm. 

 

WARNING

All faults should be taken seriously and corrected before reset 
process is performed.

aXis CONTROLLER MODULE PAD

The aXis Controller module is equipped to provide monitoring and 
protection for the HSB. 

AUTO

MAN

OFF

MODE

ARRÊT

Power ON (24VDC)

After batteries are installed the engine control module will perform 
self-diagnostic. Hours will appear on screen.

Power save mode will dim, then shut off the LCD after 1 minute 
with no input. To turn the screen back on press the   button.

MAN

This button allows verification that the HSB power delivery 
circuit is functional. The engine will start in manual mode. Safety 
procedures should be followed.

Prior to placing the aXis Controller module in the “MAN” mode, 
the UTILITY, ATS active and LOAD Icon will be lit.

AUTO 

This button allows automatic delivery of power from the HSB when 
there is a utility power outage. With the controller in the AUTO 
position and the HSB not running (standby mode), the UTILITY, 
ATS active and LOAD icon will be lit (view left to right), this 
indicates the household is using Utility power. AUTO position is the 
standby ready position.

OFF 

This button closes and shuts down the engine signals. It prevents 
the automatic operation of the generator. OFF is required when all 
maintenance or service are being performed on or around the unit.

MODE

This button allows user to cycle through screens of the aXis 
Controller module.

Cycles through available menus in run mode:

 

DCV (first screen) – indicates current battery voltage

 

HZ – indicates alternator frequency

 

ACV – indicates alternator voltage 

 

HR – indicates total run hours on Home Standby

 

 – Check button is used when programing of the aXis 

Controller module.

Содержание aXis

Страница 1: ...d understood before operating the product Failure to do so could result in serious injury This manual should remain with the product No part of this publication may be reproduced or used in any form b...

Страница 2: ...uently Asked Questions or Call our Customer Care Team Toll Free at 1 877 338 0999 Tech Bulletins Product Registration This manual must be used with Champion Power Equipment CPE manuals Installation Ma...

Страница 3: ...5 Master Mixing Assembly Jets Carburetor System 15 Alternator Overview 16 Unpacking 16 Installation 17 Placement Installation Guidelines for Champion Home Standby Generators to Reduce the Risk of Fire...

Страница 4: ...maintenance this product should bring years of satisfying service Every effort has been made to ensure the accuracy and completeness of the information in this manual at the time of publication and w...

Страница 5: ...warnings they give are not substitutes for proper accident prevention measures DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNIN...

Страница 6: ...njury user must read and understand operator s manual before using this product Eye protection Always wear eye protection with side shields marked to comply with ANSI Z87 1 Wear personal protective eq...

Страница 7: ...aXis CONTROLLER HOME STANDBY GENERATOR Safety 7 SYMBOL MEANING Sever hazard rotating blade Crush hazard top...

Страница 8: ...al equipment to live Inform your electrical provider immediately if a loss of power would cause you or anyone in your household to experience a medical emergency Installation Hazards WARNING Have only...

Страница 9: ...e first and then connect the NEGATIVE NEG or battery cable 2 Remove taped fuse from the panel and reinstall into the aXis Controller module Carbon Monoxide Hazards DANGER Generator must be installed a...

Страница 10: ...properly purge the fuel lines and leak test according to applicable codes before placing the generator in service Be sure to regularly inspect the fuel system for leaks NEVER operate the generator if...

Страница 11: ...VERTENCIA K 109 152 Colors LPN 2483 L SF Rev A Size 45 x 124 mm Artwork Notes 3mm corner radius 2mm safe margin to be printed on white substrate Revision Changes This artwork belongs to Champion Power...

Страница 12: ...tas Vea la secci n de seguridad en el manual del operador para m s detalles DANGER DANGER PELIGRO K 109 485 152 Colors LPN 2470 L SF Rev A Size 311 x 131 mm Artwork Notes 3mm corner radius 2mm safe ma...

Страница 13: ...ety Labels and Hang Tags 13 Safety Serial Model Nameplate Label Locations The safety labels have specific placement and must be replaced if they are unreadable damaged or missing C A B a Serial number...

Страница 14: ...minum with cast iron sleeves Ignition system Solid state magneto Spark plug F7RTC NGK BPR7ES Governor Mechanical Starter Electric 24V DC Oil capacity 1 6 qt 1 5 L Oil Type 5W 30 Full Synthetic RPM 360...

Страница 15: ...leeve Cylinder Head Automotive harden valves and seats Ignition System Solid state magneto Governor Mechanical Starter Electric 24V DC RPM 3 600 Oil Capacity 1 6 qt 1 5 L Champion 754cc Engine Torque...

Страница 16: ...re spring loaded to maintain contact A RED wire connects to the positive brush and a BLACK wire to the negative brush Rectified and regulated excitation current as well as current from the field boost...

Страница 17: ...combustible materials outside the enclosure Annex A Explanatory Material A 4 1 2 2 Means of demonstrating compliance are by means of full scale fire tests or by calculating procedures such as those gi...

Страница 18: ...s and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure Intertek Group PLC performed a full scale fire test under a worst case fire...

Страница 19: ...openings If prevailing winds cause blowing or drifting you may consider building a windbreak planting trees or shrubs within the guidelines and codes applicable Watch out for roof overhangs Snow ice...

Страница 20: ...eir signature under the consignor s memo of loss or damage If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claims procedures Parts damaged in shipp...

Страница 21: ...0 Wiring of the HSB 1 FUEL REQUIREMENTS AND RECOMMENDATIONS The following NG and LPG fuel information is provided to assist the fuel installer This information should not be deemed to be all inclusive...

Страница 22: ...e black iron or steel to avoid reacting with the sulfur in the fuel DANGER NG is highly explosive Even the slightest spark can ignite and cause an explosion which could cause burns fire or explosion r...

Страница 23: ...kage is permitted Safety is important Gas pipe sizing is critical to the proper operation of the HSB The HSB fuel inlet size has no bearing on the proper gas pipe size running to the HSB Gas supply an...

Страница 24: ...ion requires to run on LPG an orifice in the Master Mixer Assembly carburetor system must be changed The LPG orifices are shipped with the HSB Jet Change Procedures 1 Remove breather tube 1 by looseni...

Страница 25: ...r joint compound approved for use with LPG NG on all threaded fittings to reduce the possibility of leakage Install a sediment trap downstream of the HSB shut off valve as close to the inlet as possib...

Страница 26: ...0 degrees F can deliver for 30 seconds Starting cranking Cycle Battery is designed to deliver large bursts of power for a short time as needed to start an engine Starting batteries are intended to hav...

Страница 27: ...led electrolyte is to be washed down with an acid neutralizing agent A common practice is to use a solution of one pound 500 grams bicarbonate of soda to one gallon 4 liters of water The bicarbonate o...

Страница 28: ...ntary voltage fluctuations While there is no way to prevent voltage fluctuations you can take steps to protect sensitive electronic equipment Install UL1449 CSA listed plug in surge suppressors on the...

Страница 29: ...o 2 fuses built into the board On the left side of the module there is a 250VAC 5A mini fuse protecting the system from an over voltage between the alternator and the relays The second fuse is an auto...

Страница 30: ...and deactivate the aXis controller preventing future starts This switch should be used in instances where the HSB needs to stay off regardless of utility power presence When the switch is in the OFF p...

Страница 31: ...BLUE icons will be lit when the HSB is performing the weekly exercise period Refer to Setting Exercise Time to establish the weekly exercise period When the exercise period is complete the icon will...

Страница 32: ...ged or if they have failed It is extremely important to follow all cautions and warning per the battery manufacturer concerning installation service maintenance and replacement procedures Hz Over Spee...

Страница 33: ...oring and protection for the HSB AUTO MAN OFF MODE ARR T Power ON 24VDC After batteries are installed the engine control module will perform self diagnostic Hours will appear on screen Power save mode...

Страница 34: ...ight Saving Time DST 7a Set DST on or off using the mode button 7b for next 8 Hours for maintenance reminder H 8a Set hours for maintenance using the mode button 8b for next 9 Exercise 9a Set exercise...

Страница 35: ...iency you must follow the battery manufacturers safety instructions warnings and proper maintenance procedures Feature benefits include reverse polarity protection short circuit protection overload pr...

Страница 36: ...uired for exterior installations by code The enclosure has knockouts on the bottom and side and requires water tight connections when installed outside per code This enclosure can also be used inside...

Страница 37: ...side for the enclosure requires water tight fasteners grommets when installed outside per code This enclosure can also be used inside HSB Test SPEED SETTING NO LOAD Do NOT move forward until the HSB g...

Страница 38: ...w being delivered to the ATS and is electrically hot The feeder lines and terminals are now live Contact with these connections will result in extremely hazardous and possibly fatal electrical shock 9...

Страница 39: ...ere removed for HSB Test and Checking Automatic Operation This check is now complete Installing Standby Generator to non aXis Controller ATS OTE N This section is only for those looking to install the...

Страница 40: ...not crank turn over 1 HSB set in OFF mode Place the HSB controllers in the AUTO position 2 Battery not connected or loose corroded posts or wires Connect the batteries according to owner s manual cle...

Страница 41: ...oor wiring connections 8 ATS problems LED Indicators In all cases when the GREEN icons are lit this is an indicator that the HSB is performing properly In all cases when the RED icons are lit this is...

Страница 42: ...leshooting HSB 42 HSB ATS Model Serial Reference ATS Back up Circuits HSB Model Number HSB Serial Number Fuel Type LPG NG ATS Model Number ATS Serial Number ATS circuits powered Date Installed Dealer...

Страница 43: ...ssful activation of the unit Unit should be Registered and Proof of Purchase and Maintenance must be available Warranty is transferable between ownership of original installation site Warranty only ap...

Страница 44: ...is compromised Failures due but not limited to normal wear and tear accident misuse abuse negligence or improper installation As with all mechanical devices the Champion engines need periodic part s...

Страница 45: ...NY INCIDENTAL OR CONSEQUENTIAL DAMAGES EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF CHAMPION POWER EQUIPMENT S NEGLIGENCE Some states do not allow the exclusion or limitation of incidental or consequen...

Отзывы: