FUNCTIONALITY OVERVIEW OF THE PUSH BUTTONS P1, P2, P3 & RESET

P1+P2+P3

  P1 
  P1 + P2
  P2 + P3 
  P1 + P3 
  P2
  P3
  DIP „RADIO“ + P1 
  DIP „RADIO“ + P2 

  RESET

  Manual operation. The gate wings can be moved electrically in a manual mode. Activate Function: Push P1+P2+P3

  simultaneously. The LED LEARN starts to 

 ash as long as feature is activated. Button P1 operates Motor1. Button P2 operates

  Motor2. Deactivate: Wait for 20 seconds or disconnect logic board power. If wings close at 

 rst reverse wires red and blue.

  For automatic programming of the automatic travel distance limits of the gate.
  For the advanced programming of the travel distance limits of the gate
  Electric lock delay time
  Wing delay adjustment.
  Automatic closing time. Requires also P2 to con

 rm.

  Software-reset to factory defaults. Push & hold for 10 seconds. Does not reset the remote control memory (see section “radio”).
  Programming Remote for Channel 1. Command for both motors (wings)
  Programming Remote for Channel 2. Command for single motor (Motor1).

  Program Internet Gateway or Door Monitor Note: The RESET button does not perform a reset of this particular control board

  to factory defaults . It is only meant to program the Internet Gateway and the Door Monitor. See function P3 for resetting the

  board to factory default settings.

Button    

    Function

       6/16 en

  DESCRIPTION OF TERMINALS

  DESCRIPTION       FUNCTION

  L  

 

    connector L 230V supply

  N  

 

    connector N 230V supply

  30VDC    

    connector for an external battery

  Motor MASTER       motor 1 (master opens 

 rst) red/blue

  Motor SECOND       motor 2 (Second opens second) red/blue

  To check correct polarity refer to section basic setting and

  functionality P1+P2+P3 & RESET

  24V/150mA  

    

 ashing light (accessory)

  Motor1 MASTER

  BRN    

    brown cable

  GRN    

    green cable

  WHT    

    white cable

  YEL  

 

    yellow cable

  Motor2 SECOND

  BRN    

    brown cable

  GRN    

    green cable

  WHT    

    white cable

  YEL  

 

    yellow cable

  Light Contact  

    gate monitor/ yard lighting

  PED  

 

    key switch

  COM    

    negative pole

  STOP    

    stop switch

  Key symbol  

    key switch

  COM    

    negative pole

  PHOTO3  

    photocells 3 (open)

  PHOTO2  

    photocells 2 (close & open)

  PHOTO1  

    photocells 1 (close)

  COM    

    negative pole

  EDGE    

    safety edge with 8.2KOhms

  8.2kOhms

  E-lock symbol  

    connection for E-lock control board

  INPUT 24VAC  

    24V power input from transformer.

 

 

    can be connected with any polarity.

  Transformer 230VAC  230V supply to transformer. Can be

    

 

    connected with any polarity.

  250V/2A  

    fuse 250V/2A fast-blow (2x included)

  DESCRIPTION OF LED´S (LIGHT EMITTING DIODE)

  DESCRIPTION   COLOUR  

STATUS

  Stop  

 

green  

 

Stop Switch

    ON: 

Stop 

Active

 

 

 

 

OFF: OK (Requires wire bridge if  

    no 

switch 

is 

connected)

  Edge    

green  

 

Safety Edge 8.2KOhm

    ON: 

Activated

    OFF: 

OK 

(Requires 

8.2KOhm 

    resistor 

if 

not 

used)

  “Key symbol”  

red  

 

Key-switch 2-wing opening

    ON: 

Activated

    OFF: 

OK

  PED  

 

red  

 

Key-switch 1-wing opening

    ON: 

Activated

    OFF: 

OK

  PHO 1    

red  

 

Photocell 1 (close)

    ON: 

OK, 

photocell

    connected 

(no 

problem)

    OFF: 

No 

photocells 

connected

  PHO 2    

red  

 

Photocell 2 (open & close)

    (Refer 

to 

photocell 

1)

  PHO 3    

red  

 

Photocell 3 (open)

    (Refer 

to 

photocell 

1)

  LEARN   

yellow    

Programming indicator

    ON: 

(

 ashing)

    programming 

is 

active

    OFF: 

off

  DGN    

red  

 

Diagnostic, Refer to page 15

  CH1  

 

red  

 

Remote control

    programming 

2-wing 

opening

 

 

 

 

ON: New remote can be

    programmed

    OFF: 

off

  CH2  

 

red  

 

Remote control programming

 

 

 

 

1-wing opening (Refer to CH1)

Содержание LYN300 Series

Страница 1: ...atické pohony bran modely LYN300 LYN400 série SCS300 Instrucciones Automatismos de puerta automáticos modelos LYN300 LYN400 SCS300 de las series O ËÁ Â ÙfiÌ ÙÔÈ ÌË ÓÈÛÌÔ ÁÎ Ú fi ÔÚÙ ÌÔÓÙ Ï LYN300 LYN400 SCS300 Series Útmutatók SCS300 as sorozatba tartozó LYN300 as és LYN400 as automatikus garázsajtó Upute Automatski pogoni vrata modeli LYN300 LYN400 SCS300 serije Istruzioni Automazioni per cancell...

Страница 2: ... 2 0 m 3 0 m 4 0 m 5 0 m 6 0 m 250 kg 180 kg 160 kg 140 kg Wing Weight Wing Size LYN300 LYN300 LYN400 LYN400 0 m 0 5 m 1 0 m 1 5 m 2 0 m 2 5 m 3 0 m 250 kg 180 kg 160 kg Wing Weight Wing Size SCS300 3 5 m 4 0 m ...

Страница 3: ...6 DESCRIPTION OF LEDS 6 FUNTIONALITY OVERVIEW OF THE PUSH BUTTONS P1 P2 P3 RESET 6 OPTIONAL ACCESSORIES 7 PHOTOCELLS 8 RADIO AND RADIO PROGRAMMING 8 PROGRAM INTERNET GATEWAY my Q DOOR MONITOR 9 LOOP DETECTOR USAGE 10 DIP SWITCH SETTINGS 11 WING DELAY ADJUSTMENT 11 INITIAL OPERATION BASIC SETTING 12 14 TIMER TO CLOSE AUTO CLOSE 14 FORCE TORQUE OF MOTOR 14 DISPOSAL BATTERY DISPOSAL 14 INDICATION OF ...

Страница 4: ...o check with your gate manufacturer for an opener installation reinforcement kit Activate opener only when the gate is in full view free of obstructions Do not allow children to play near the gate Humidity and water destroy the control board Make sure under all circumstances that water humidity or dammed up water cannot penetrate the control board covering Frequently examine the installation for i...

Страница 5: ...optional Is mounted on the outside The gate is opened by key or by entering a number 7 Contact strip optional Safeguards the gate on being touched Contact strips can be mounted on the gate or on the pillars If required contact strips must be mounted at a height of up to 2 5m 2 16 en CONTROL BOX The control consists of several components exterior installation box 1 cover for box 1 control 1 transfo...

Страница 6: ...s C Fasten transformer on to baseplate using the large screw and large washer D Put the 4 large closure screws through cover of the box Fasten 2 of them left or right approx 2cm into the box After that the cover can be opened to the side E Close box on a trial basis turning the screws all the way in If the lid does not close completely then the box is not fitted to the wall evenly and is therefore ...

Страница 7: ...h identical colours distribution box IP65 cable screw joints and fastening material 041ASWG 0482 50 Cable 50m for professional use Consists of 50m of cable 6 pole with identical colours Cut only as much as you need for the current installation General wiring sizes The numbers mentioned in the table below are minimum requirements It is always possible to use larger diameters 230Volt Supply Power to...

Страница 8: ...CM475 BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW RADIO MODULE Model 207399 230 VAC 50 RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE not required not required RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW ART SUB Closed position Open position external battery ...

Страница 9: ...D motor 2 Second opens second red blue To check correct polarity refer to section basic setting and functionality P1 P2 P3 RESET 24V 150mA flashing light accessory Motor1 MASTER BRN brown cable GRN green cable WHT white cable YEL yellow cable Motor2 SECOND BRN brown cable GRN green cable WHT white cable YEL yellow cable Light Contact gate monitor yard lighting PED key switch COM negative pole STOP ...

Страница 10: ...ith 829EV door monitor allows optical and acoustical monitoring of the gate position The gate can also be closed with the device BACKUP BATTERY OPTIONAL The terminals serve to reload an externally installed storage battery The integrated recharger is loaded and in case of power failure the battery provides power A new fully charged storage battery may provide power for more than 24 hours Storage b...

Страница 11: ... LED flashes photocell disables control board Connection between 1 COM Active when gate is closing reverses gate to open Connection between 2 COM Active when gate is closing and opening Connection between 3 COM Active when gate is opening holds gate in present position until photocell is cleared continues when cleared RADIO AND RADIO PROGRAMMING PROGRAM DELETE REMOTE CONTROLS The receiver has two c...

Страница 12: ...the LEDs will blink 3 times and go out 7 The App will tell you if programming was successful and will prompt you to assign a name to the gate PROGRAM DOOR MONITOR Using the RESET Button on the control board 1 Connect power to the door monitor Position the door monitor in a convenient visible place inside the house If this place is too far from the gate opener the connection may not be possible or ...

Страница 13: ... truck but do not comply with regulations as single protection since they do not detect people The loop detector control board output is wired as NO signal to the 8 2KOhm safety edge output In case you use safety edges as well Check the functionality you need before installation Interrupt loop DIP OPEN STEP must be on Shadow loop DIP OPEN STEP must be off Other options for loop detectors can be re...

Страница 14: ...CS SUB RADIO The DIP RADIO is required to program remote controls For programming procedure please refer to page 8 section radio OFF No programming of remote controls possible ON Programming of remote controls possible Important Switch off DIP RADIO if not in use Wing Delay Adjustment The delay of one wing is required to open and close the wings correctly and to operate the wings with a safe dista...

Страница 15: ...anged any time later after completion of the installation Now connect the mains supply 230V to the control board BASIC SETTING 1 Press buttons P1 P2 and P3 simultaneously for approx 2 3 seconds until yellow LED flashes 2 Monitor the gate Press and hold P1 for 1 2 seconds The wing with motor 1 opens If motor 1 closes it is wired incorrectly and the red and blue wires of the motor cable must be rever...

Страница 16: ...When the learn LED goes out the programming has finished PROGRAMMING TRAVEL DISTANCES ADVANCED NOTE In this mode P1 must be pressed 9 times With every time the button is pressed a position time is stored This allows programming of SOFT STOP slow travel in order to adjust to application Long or short phases of SOFT STOP are possible 1 Both wings must be closed 2 Press P1 and P2 for approx 5 6 second...

Страница 17: ...r changes to the installation rust or inappropriate lubrication it may have to be repaired The control board complies with the latest EU guidelines One of these guidelines specifies that the closing forces at the gate edge must not exceed 400N 40 kg for the last 500 mm before the door is CLOSED Above 500 mm the maximum force at the gate edge must not exceed 1400 N 140 kg If this cannot be ensured a...

Страница 18: ...nstallation A Object obstructs safety edge B Defective safety edge C Power too low or broken wire in supply Power supply to control board is too low A Defective supply 230V or malfunctioning contact B Broken wire in supply cable copper cable C The battery accessory to operate the gate whilst power failure is dead EEPROM Fault Power up failed Only LYN SCS Release lever OPEN Defect on relay or major...

Страница 19: ... 2 Find and rectify fault s see description of diagnostic LEDs 3 Check photocell connection programming 4 Check terminals and connections 1 Program transmitter 2 Check photocells check diagnostic LEDs 3 DIP RADIO must be off Program travel distance See initial operation diagnosis LED re program travel distance consult dealer specialist 1 Check manual especially 1 2 Motor 2 If motor is moving check...