Install the Ground

 

IMPORTANT:

 An earth ground rod is strongly recommended and should be no 

further than 12 feet (3.7 m) from the controller and use a minimum of 12 gauge 
wire in most cases. The type and length of earth ground rods vary by region. 
Contact the AHJ (Authority Having Jurisdiction) in the municipality where you 
plan to install the controller for correct grounding materials and installation 
procedures.

1.   Connect the ground wire (12 AWG or larger) to the controller ground lug. 

2.   Run the wire from the controller to suitable earth ground. 

NOTE:

 Shield connections on boards should not be connected to ground lug.

ON

Ground wire

12 AWG minimum

Earth ground rod

Other ground sources within 

12 feet of access control panel

Ground to 

existing 

electrical 

system

Electrical

panel

Ground to 

metallic cold 

water pipe

12 feet (3.7 m) maximum

NOTE:

 Keep ground wire as 

straight as possible.

Check national 
and local codes 
for proper depth

Typical ground

Ground Connection

To AVOID damaging gas, power or 
other underground utility lines, 
contact underground utility locating 
companies BEFORE digging.

PRE-INSTALL

NETWORK

PROGRAMMING

INSTALL

ACCESS CONTROL

INTRODUCTION

Содержание ACXL

Страница 1: ...Large Display Access Controller INSTALLATION MANUAL Model ACXL...

Страница 2: ...BEFORE installing locks or devices on ANY doors that may be fire exits Use of egress push buttons may not be legal Single action exits may be required ALWAYS obtain proper permits and approvals in wri...

Страница 3: ...8 Mount the Controller 9 Controller Overview 10 Power Internet Board Overview 11 Door Board Overview 12 Install the Ground 14 Connect Power 15 NETWORK 3 Connect Internet 16 Validate Setup 16 ACCESS CO...

Страница 4: ...Pliers Measuring tape Work Gloves Conduit Bender Conduit Cutter Reamer Hack Saw Center Punch Tool Hammer 7 64 Drill Bit PROVIDED NOT SHOWN Hardware for Camera Kit Installation Manual Controller Carto...

Страница 5: ...y Refer to the accessory page for compatible accessories Network Compatibility RJ 45 Wired Ethernet Wi Fi Compatibility 802 11 a b g n Wi Fi Range Up to 500 feet 152 4 m Open Air Line of Sight range w...

Страница 6: ...22 AWG Shielded 500 feet 152 4 m Postal Lock Box 2 Conductor 18 24 AWG 250 1000 feet 76 2 304 8 m NOTE Main power supply and control wiring MUST be run in separate conduits Conduits must be UL approv...

Страница 7: ...PRE INSTALL NETWORK PROGRAMMING INSTALL ACCESS CONTROL INTRODUCTION located on inside of the controller door and on the display when powered up 2 SIP Provider 3 Setup a LiftMaster Cloud Account NOTE I...

Страница 8: ...kouts with a hammer Banging on the knockouts may result in shock to the circuit boards which could cause permanent damage 1 Turn the key clockwise and open the controller 2 Identify which knockouts ne...

Страница 9: ...ller is properly sealed to prevent damage to the controller from moisture PRE INSTALL NETWORK PROGRAMMING INSTALL ACCESS CONTROL INTRODUCTION Pedestal Mount 1 4 x 1 1 2 Ribbed Neck Security Bolt 4 Goo...

Страница 10: ...CATION CAMERA MOUNTING BRACKET RADIO ANTENNA Wi Fi ANTENNA POSTAL LOCK SWITCH DISPLAY TOUCHSCREEN SPEAKER LOCK POSTAL LOCK LOCATION PROXIMITY READER LOCATION CAMERA LOCATION MICROPHONE RADIO ANTENNA C...

Страница 11: ...er Internet Board Overview ON Display Backlight Display Touch RADIO ANTENNA Connection to Control Board Door Board 1 Door Board 2 ETHERNET POWER Power Connection for Control Board Auxiliary Power not...

Страница 12: ...ess control inputs outputs on the Door Boards that work in conjunction to control up to 4 access points INPUT OUTPUT USED FOR Wiegand Input Proximity Readers RFID Receiver and Keypads Request to Exit...

Страница 13: ...ty 2 0 Radio Antenna if applicable Used for transmitters and wireless gate communication 1 Secure the radio antenna to the desired knockout on the controller 2 Connect the radio antenna cable to the P...

Страница 14: ...und lug 2 Run the wire from the controller to suitable earth ground NOTE Shield connections on boards should not be connected to ground lug ON Ground wire 12 AWG minimum Earth ground rod Other ground...

Страница 15: ...e power supply Black is negative and red is positive 2 Remove the PWR INPUT terminal block from the Power Internet Board 3 Connect the power supply wires to the PWR INPUT terminal block red to 12V and...

Отзывы: