I-MICN-01.doc 

 Issue 

06 

  Mar10 

   

 

 

 

2

 

 
 
 
 

                                           IOM – 

MICRONEX - ZONE 2

 

FLOODLIGHT (ATEX, Ex n)

 

 

 

Type(s) of Protection 

Ex nR (Non-Sparking) (Restricted Breathing)

 

 Protection 

Standard 

EN 50021

 

 

Area of Application 

Zone 2 areas to BS EN 60079-10 and installation to BS EN 60079-14

 

 ATEX 

Equipment 

Classification 

Group II  Category 3 G

 

 Equipment 

Coding 

      II 3 G  Ex nR II  T3  Tamb 40ºC

 

 Certificate  

Type Examination EECS  BAS98ATEX3054

 

 Ingress 

Protection 

IP66 and IP67 to BS EN 60529

 

 

 

 

 

CE Mark 

 

 
 
 
 

Declaration of 
compliance with 
standards 

 

The CE marking of this product applies to "The Electrical Equipment (Safety) 
Regulations 2006", "The Electromagnetic Compatibility Regulations 2004", the “Waste 
Electrical and Electronic Equipment Regulations 2006” and the "Equipment and 
Protective Systems intended for use in Explosive Atmospheres Regulations 1996". 
[This legislation is the equivalent in UK law of EC directives 2006/95/EC, 2004/108/EC

 

and 2002/96/EC respectively].         
        
The Equipment is declared to meet the provisions of the ATEX directive (94/9/EC) by 
reason of the EC Type Examination and compliance with the Essential Health and 
Safety Requirements.  
I MacLeod    Technical Manager 

 
 

 

 

SPECIAL CONDITIONS FOR SAFE USE 

 
None 

 

1.0   

Introduction - Micronex Floodlight

 

The type of protection is Ex nR using a restricted breathing enclosure. 
 

Note: 

 

The maximum ambient and surface temperature ratings are as indicated in TABLE 0. 

 

2.0   

Application

 

The luminaire is designed to be safe in normal operation. 
The luminaire should not be used in conditions where there are environmental, vibration or shock conditions 
above the normal expected levels for fixed installations. 
The gaskets should not be exposed to hydrocarbons in liquid or high concentration vapour states. 
The body material is made from marine grade aluminium, copper free (

BS1490 LM6)

, powder coated. 

The luminaire is suitable for applications where Category 3 apparatus can be used.  The application is for 
ignitable gas atmospheres.  The type examination does not address suitability for dusts or portable applications. 
 
 

 

Table 1

 

Maximum Ambient and Surface Temperature Rating 

 

 

Wattage 

Lamp 

Ambient Temp

T Rating 

Cable Rating 

 

Cable Rise 

 70W 

SON/TS, 

MBI/TS 40ºC 

T3 

75oC 30oC 

 
 

 

Table 2

 

Starting and Running Currents 

 

 Lamp 

Start 

Run A 

PFC µF

 

 

 70W 

HPS 

0.55 

0.40 

10 

 

 70W 

MBI 

0.55 

0.40 

10 

 

 

Содержание Micronex 70W HPS

Страница 1: ...s should be followed at all times and this data should be used as a guide only C ha l m i t L i gh t i ng T a m b M I C R O N E S I M P L E X C H A L M I T L I G H T I N G L T D V C E 600 3 8 8 H I L L I N G T O N R O A D G L A S G O W U K S I T E 0 9 9 0 _ S O N TS _ 24 0 3 T S E R N o 9 8 W O P 6 6 6 7 _ S U P PL Y LA M P 70 W 3 0 T O 4 0 C I I 3 G B A S 9 8 A T E X 4 0 5 4 I S O LA TE S U P P L...

Страница 2: ...ion and compliance with the Essential Health and Safety Requirements I MacLeod Technical Manager SPECIAL CONDITIONS FOR SAFE USE None 1 0 Introduction Micronex Floodlight The type of protection is Ex nR using a restricted breathing enclosure Note The maximum ambient and surface temperature ratings are as indicated in TABLE 0 2 0 Application The luminaire is designed to be safe in normal operation ...

Страница 3: ...r factor 0 85 EMC EN 55015 Terminals 6mm as standard through wiring and looping has current limit of 16A Tamb Storage 40 C to 80 C Storage Luminaires should be stored in cool dry conditions preventing ingress of moisture and condensation Lamps Lamps suitable for RX7 lampholders in accordance with EN 60838 Fuse and Refer to tables 2 and 3 for starting and running currents and fuse ratings Also refe...

Страница 4: ...ed continuously at more than 6 10 of the rated supply voltage of the control gear or tapping The user must determine the actual underlying site supply and purchase or adjust accordingly Care must be taken if connecting to the nominal 230V UK Public Supply In some cases the luminaires have multi tapped control gear which can be set to a range of voltages The tappings are shown on the control gear a...

Страница 5: ...r looping Standard 300 500V cable is suitable The cable makeup must be suitable to ensure the obtaining of a restricted breathing enclosure when the cable gland assembly is fitted It is strongly advisable to use a high quality and well filled cable with direct entry into restricted breathing luminaires 3 6 2 Cable Glands Cable glands and sealing plugs when installed must maintain the restricted br...

Страница 6: ...See also Section 3 4 4 0 Overhaul The unit is largely made of materials which are very corrosion resistant This allows the unit to be completely stripped cleaned then re built with new electrical parts as required The internal wiring is 1 0mm flexible silicone rubber insulated An H T sleeve is fitted to the ignitor cable All the spares required are available Please state the model number lamp deta...

Страница 7: ...d electronic components All electrical components may give off noxious fumes if incinerated 6 1 Lamps Discharge lamps in modest quantities are not special waste The outer envelope should be broken in a container to avoid possible injury from fragmentation avoid inhaling dust This applies to the UK there may be other regulations on disposal operating in other countries Note Do not incinerate lamps ...

Отзывы: