Menu - 5 - Combustion rate control mode
X X
X X
DISPLAY
ACTION
CONFIGURATION
wait 5 ”
Combustion rate control mode OFF
Switching on the combustion rate
control mode. Central heating output
reach the maximum power set in
menu 4 section 9.
Central heating temperature is
displayed in celsius degrees.
The 3 dots indicate that the
combustion rate control is ON at
maximum output.
Switching the combustion rate
down to minimum power.
Central heating temperature is
displayed in celsius degrees.
The dot indicates that the
combustion rate control is ON at
minimum output.
Switching on the combustion rate to
maximum output set in menu 4
section 9.
Central heating temperature is
displayed in celsius degrees.
The 3 dots indicate that the
combustion rate control is ON at
maximum output.
X X
Switching off the combustion rate
control mode.
press once
press once
press once
press once
Effect
Display
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode if operator leave menu 5
- after 15 minutes if there is no actions on keyboard
Note : As soon as the combustion rate control mode is on, Central Heating and Domestic Hot Water keys are
inactive.
press once