Cetetherm Midi Wall IQHeat
Installation, service and operating instruction
22
9
Service instructions
To avoid the risk of scalding, make sure that no-one draws any water while servicing the
substation.
Grey marked service actions must be carried out by an authorized service technician.
NOTE:
Make sure that the Midi Wall substation has been correctly installed.
For more information about IQHeat, see
User instruction IQHeat Doc-1552
.
9.1
Tap water, service instructions
9.1.1
Tap water too cold
Reason
Action
District heating supply too low
Check the primary inlet temperature
The temperature can be checked by means of the energy meter,
minimum 65ºC, or at the district heating medium supply.
The hot water drain temperature can be monitored on the control panel
display, see
User instruction IQHeat Doc-1552
chapter
Hot water
circuit
.
District heating strainer clogged
See
10.1 Check if the district heating strainer is blocked.
Hot water valve and actuator does not
work
See
10.2 Check the function of the heating and hot water valve and
actuator
9.1.2
Tap water too warm
Reason
Action
Hot water valve and actuator does not
work
See
10.2 Check the function of the heating and hot water valve and
actuator
9.1.3
Hot water temperature unstable
Reason
Action
Pending differential pressure
Check available differential pressure and the primary inlet
temperature
The temperature can be checked by means of the energy meter,
minimum 65ºC, or at the district heating medium supply.
Faulting settings for drain hot water
Check pre-set parameters on control panel display
Check set value for drain hot water, see
User instruction IQHeat Doc-
1552
chapter
Hot water circuit.
District heating strainer clogged
See
Check if the district heating strainer is blocked
DHWC pump is not running
Check that the electrical power is on.
See