Figure 4-3 Login Interface
5)
Once the log-in credentials are confirmed, the following page appears.
Figure 4-4 Basic Settings
4.2 Ethernet
The
P1 (Ethernet)
port’s settings can be configured here based on the actual situation. Click
Save
to
confirm your changes. Please be reminded that the
IP Address
and
Default Gateway
for the Ethernet
port should be in the same subnet.
Figure 4-5 P1 Settings
4.3 Serial Port
The PMC-1302 comes standard with two RS-485 ports: P2 and P3. All setup parameters such as
Baudrate
,
Data Bits
,
Parity
,
Stop Bits
,
IP Port
and
Timeout
can be configured here to match the
settings of the downstream RS485 devices. Please be reminded that the
IP Port
number of the Serial
Gateway feature for P2 (default = 20000) and P3 (default = 20001) should be different. Click
Save
to
confirm your changes. The following table shows the setup parameters for P2 and P3. Most setup
parameters are basic and self-explanatory. Please note that the
Packet
Timeout (ms)
parameter refers
to the timeout setting for the IP connection instead of the serial connection, meaning that the IP
connection will be closed if there are no activities between the application software and the
PMC-1302 ESG for the specified amount of time. This is to prevent a potential lock up of the IP
connection at the PMC-1302 ESG if the application software fails to close the IP connection for some
unknown reasons. It is recommended that the default
Packet
Timeout
of 300 seconds be used.