CET Electric Technology
98
5.10.4.2
High-speed Data Recorder Setup Data Structure
Offset
Property
Description
Format
Range
+0
RW
Trigged Mode
UINT16
0=Disabled
1=Triggered by Timer
2=Triggered by Setpoint
+1
RW
Recording Mode
UINT16
0=Stop-When-Full
1=First-In-First-Out
+2
RW
Recording Depth
UINT16
0 to 65535
+3
RW
Recording Interval
UINT32
1 to 60 (cycles)
+5
RW
Recording Offset
UINT16
0~43200 s
+6
RW
Number of Parameters
UINT16
0 to 16
+7
RW
Parameter 1
UINT16
Please refer to Appendices A and B
for a complete list of the Data
Recorder Parameters and the default
configuration for each DR,
respectively.
+8
RW
Parameter 2
UINT16
+9
RW
Parameter 3
UINT16
+10
RW
Parameter 4
UINT16
+11
RW
Parameter 5
UINT16
+12
RW
Parameter 6
UINT16
+13
RW
Parameter 7
UINT16
+14
RW
Parameter 8
UINT16
+15
RW
Parameter 9
UINT16
+16
RW
Parameter 10
UINT16
+17
RW
Parameter 11
UINT16
+18
RW
Parameter 12
UINT16
+19
RW
Parameter 13
UINT16
+20
RW
Parameter 14
UINT16
+21
RW
Parameter 15
UINT16
+22
RW
Parameter 16
UINT16
Table 5-48 HS DR Setup Data Structure
Notes:
1)
The High-speed Data Recorder can be triggered by Setpoints (
Triggered by Setpoint
) or on a time basis using the meter clock (
Triggered
by Timer
).
For
Triggered by Setpoint
, when the Setpoint goes active, the Data Recorder starts to record, and when the Setpoint becomes
inactive, the Data Recorder stops.
2)
If
Recording Depth
is set to “
0
”, the Data Recorder will be disabled.
3)
Recording Offset
should be set to zero for
High-Speed Data Recorder
.
4)
Appendix A
provides a list of available parameters for data recording. Parameters 0 to 28 are available for high-speed data recording.
If
Number of parameters
is set to
0
, the Data Recorder is disabled.
5)
Modifying
Recording Mode
,
Recording Depth
,
Recording Interval
,
Recording Offset
,
Number of Parameters
and
Parameters 1 to 16
will clear the DRx Log and reset the DRx Pointer to “0”.
5.10.4.3
Standard Data Recorder Setup Data Structure
Offset
Property
Description
Format
Range
+0
RW
Trigged Mode
UINT16
0=Disabled, 1=Triggered by Timer
2=Triggered by Setpoint
+1
RW
Recording Mode
UINT16
0=Stop-When-Full
1=First-In-First-Out
+2
RW
Recording Depth
UINT16
0 to 65535
+3
RW
Recording Interval
UINT32
1 to 3456000 (seconds)
+5
RW
Recording Offset
UINT16
0 to 43200 (seconds)
+6
RW
Number of Parameters
UINT16
0 to 16
+7
RW
Parameter 1
UINT16
Please refer to Appendices A and
B for a complete list of the Data
Recorder Parameters and the
default configuration for each
DR, respectively.
+8
RW
Parameter 2
UINT16
+9
RW
Parameter 3
UINT16
+10
RW
Parameter 4
UINT16
+11
RW
Parameter 5
UINT16
+12
RW
Parameter 6
UINT16
+13
RW
Parameter 7
UINT16
+14
RW
Parameter 8
UINT16
+15
RW
Parameter 9
UINT16
+16
RW
Parameter 10
UINT16
+17
RW
Parameter 11
UINT16
+18
RW
Parameter 12
UINT16
+19
RW
Parameter 13
UINT16
+20
RW
Parameter 14
UINT16
+21
RW
Parameter 15
UINT16
+22
RW
Parameter 16
UINT16
Table 5-49 Standard DR Setup Data Structure