Notes:
1)
The Standard Data Recorder can be triggered by Setpoint (
Triggered by Setpoint
) or on a time basis using the meter clock (
Triggered
by Timer
).
For
Triggered by Setpoint
, when the Setpoint goes active, the Data Recorder starts to record, and when the Setpoint becomes
inactive, the Data Recorder stops.
2)
If the
Recording Depth
is set to
0
, the Data Recorder will be disabled.
3)
Recording Offset
can be used to delay the recording by a fixed time from the
Recording Interval
. For example, if
Recording Interval
is
set to 3600 (hourly) and
Recording Offset
is set to 300 (5 minutes), the recording will take place at 5 minutes after the hour every hour,
i.e. 00:05, 01:05, 02:05…etc. The programmed value of
Recording Offset
should be less than that of
Recording Interval
.
4)
Appendix A
provides a list of available parameters for data recording. All parameters are available for standard data recording. If
Number of parameters
is set to
0
, the Data Recorder is disabled.
5)
Modifying
Recording Mode
,
Recording Depth
,
Recording Interval
,
Recording Offset
,
Number of Parameters
and
Parameters 1 to 16
will clear the DRx Log and reset the
DRx Pointer
to “0”.
5.10.5
Interval Energy Recorder Setup Registers
Register
Property
Description
Format
Range
Default
7700
RW
Recording Mode
UINT16
0=Disabled,
1=Stop-When-Full
2= First-In-First-Out
2
7701
RW
Recording Depth
UINT16
0 to 65535
5760
7702
RW
Recording Interval
UINT16
1 to 65535 mins
15
7703
RW
Start
Time
High-order Byte: Year
UINT16
0-99 (Year-2000)
10
Low-order Byte:
Month
1 to 12
10
7704
RW
High-order Byte: Day
UINT16
1 to 31
14
Low-order Byte: Hour
0 to 23
14
7705
RW
High-order Byte:
Minute
UINT16
0 to 59
46
Low-order Byte:
Second
0 to 59
00
7706
RW
Number of Parameters
UINT16
0 to 5
5
7707
RW
Parameter 1
UINT16
0=kWh Import,
1=kWh Export
2=kvarh Import,
3=kvarh Export
4=kVAh
0
7708
RW
Parameter 2
UINT16
1
7709
RW
Parameter 3
UINT16
2
7710
RW
Parameter 4
UINT16
3
7711
RW
Parameter 5
UINT16
4
Table 5-50 Interval Energy Recorder Setup Registers
Notes:
1)
If
Recording Depth
is set to
0
, the Energy Log is disabled.
2)
When the current time meets or exceeds the
Start Time
, the
Interval Energy Recorder
starts to record.
3)
Modifying
Recording Depth
,
Recording Interval
,
Start Time
,
Number of Parameters
and
Parameters 1 to 5
will clear the Energy Log
and reset the
Energy Log Pointer
to “0”.
5.10.6
Waveform Recorder (WFR) Setup
The iMeter 6 provides 2 Waveform Recorders, each with a fixed
Recording Depth
of 128. Each WFR can
simultaneously capture 3-phase Voltage and Current signals at a maximum resolution of 256 samples per cycles.
Register
Property
Description
Format
Range
Default
7600
RW
WFR Log 1
Reserved
UINT16
-
-
7601
RW
Format
UINT16
0~4
0
7602
RW
Reserved
UINT16
-
-
7603
RW
Pre-fault Cycles
UINT16
0 to 20
4
7604
RW
WFR Log 2
Reserved
UINT16
-
-
7605
RW
Format
UINT16
0~4
0
7606
RW
Reserved
UINT16
-
-
7607
RW
Pre-fault Cycles
UINT16
0 to 20
6
Table 5-51 Waveform Recorder Setup Parameters
Notes:
1)
The valid WFR formats (# of samples/cycle x # of cycles) include 0~4, which are 16x320, 32x160, 64x80, 128x40 and 256x20,
respectively.
2)
Modifying the Setup Parameters of WFRx will clear the WFRx Log and reset WFRx Pointer will be reset to “0”.