Fault Codes
Condensing Pool Heater
24
22/12/08
DISPLA
Y
LOCK / RESET
GREEN
YELLOW
RED
LED1
RED
RED
LED2
FRONT P
ANEL
ON PCB
EXPLANA
TION
‘P’ alternating with ‘oc’ = Pool sensor open circuit
OR
No
network detected if a Master in a multiple heater inst
allation
‘P’ alternating with ‘cc’ = Pool sensor short circuit
‘F’ alternating with ‘oc’ = Heat Exchanger
Flow sensor open circuit
‘H’ alternating with ‘oc’ = Heat Exchanger
Combustion sensor open circuit
‘H’ alternating with ‘cc’ = Heat Exchanger
Combustion sensor short circuit
‘F’ alternating with ‘cc’ = Heat Exchanger
Flow sensor short circuit
‘Err
’ alternating with ‘4’
= Pool potentiometer open circuit
‘Err
’ alternating with ‘5’
= Pool potentiometer short circuit
For all of the above.
T
urn of
f, correct problem and turn back
on again and the display and operation will be normal.