Health and Safety document No 635, “Electricity at
Work Regulations”.
Detailed recommendations are contained in the
following British Standard Codes of Practice.

Codes of Practice.

BS.6798 Installation of gas fired hot water boilers of
rated input not exceeding 70kW.
BS.5440: Part1 and Part 2. Flues (for gas appli-
ances of rated input not exceeding 60kW).
BS 6891 Specification for installation of low pressure
gas pipework.
BS5482:1 Code of practice for domestic butane &
propane gas burning installations.
Building Regulations Part L1.

IMPORTANT

.

It is important that no external

control devices are directly connected to this appli-
ance - unless covered by these ‘Installation and
Servicing Instructions’ or otherwise recommended
by the manufacturer. If in doubt, please enquire.
Any direct connection of a control device not
recommended by the manufacturer could infringe
the Gas Safety (Installation & Use) Regulations, the
above regulations and the normal appliance war-
ranty.

Manufacturer’s notes must NOT be taken, in any
way, as overriding statutory obligations.

Location of Heater

The Heater MUST be installed on a flat and level
floor, capable of adequately supporting the weight of
the Heater and any ancillary equipment.
Provision is provided for the heater to be fixed to the
floor.
It is IP 44 Rated and can be installed out of doors in
a suitable position. In all cases the choice of position
should take into account the flue, the plume and the
condensate drainage.

IMPORTANT NOTICE.

If the Heater is to be fitted in a timber framed build-
ing it should be fitted in accordance with the British
Gas publication ‘Guide for Gas Installations in
Timber Frame Housing’, reference DM2. If in doubt,
advice must be sought from the Local Gas Region of
British Gas.

The Heater may be installed in any room or internal
space. Particular attention is drawn to the require-
ments of the current I.E.E Wiring regulations and, in
Scotland, the electrical provisions of the Building
Regulations applicable to Scotland with respect to
the installation of the boiler in a room or internal
space containing a bath or shower.

Where a room sealed appliance is installed in a
room containing a bath or shower then the appliance
and any electrical switch or appliance control,
utilising mains electricity should be so situated that it

Condensing Pool Heater

     

3

           12/08/09

  INTRODUCTION

These Instructions cover a range of indirect, floor
mounted, gas fired, condensing pool heaters which
are room sealed and fan assisted. The flue system
available is concentric, left, right, rear, and vertical,
all up to 20 metres ‘FEL’. There is also an Outdoor
Top terminal for use where the Heater is installed
out of doors. The ignition system is fully automatic.

There are two models with different outputs - see
the 

Technical Data on Inside Cover 

for details.

Both can be installed in multiples to obtain a larger,
combined output.

The casing is of green and black polyester powder
coated mild steel. The Heaters use a high perform-
ance stainless steel heat exchanger and are suit-
able for connection to pools using chlorinated and
salt chorinated water provided the following levels of
chemicals are maintained.

pH

7.2 to 7.8

Total Alkalinity

80 to 140 ppm

Calcium Hardness

200 to 400 ppm

Salt maximum

30000 ppm

Free Chlorine

1 to 4 ppm

All chemicals must be introduced and completely
diluted into the pool water before being circulated
through the heater. Do not place chlorine tablets or
bromine sticks in the skimmer, high chemical
concentrations will result when the pump is not
running.

Chlorinators must feed downstream of the heater
and have an anti-siphoning device to prevent
chemical back-up into the heater when the pump is
shut off.

NOTE:

High chemical concentrates from feeders

and chlorinators that are out of adjustment will
cause  corrosion to the heat exchanger in the
heaters. Such damage is not covered under the
warranty.

Gas Safety (Installation and Use)
Regulations, (as amended).

It is the law that all gas appliances are installed by a
competent person (e.g. a registered operative) in
accordance with the above Regulations. Failure to
install appliances correctly could lead to prosecu-
tion.

It is in your own interest, and that of safety, to
ensure that the law is complied with. The installation
of the Heater MUST also be in accordance with the
current I.E.E.. Wiring Regulations, the Local Build-
ing Regulations, Building Standards (Scotland), the
Bye Laws of the Local Water Undertaking, any
relevant requirements of the Local Authority, and

Содержание MB35S

Страница 1: ...trical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions Installation and service must be performed by a Corgi registered installer A page is included on the inside back page of this booklet for recording commissioning and service details Operating Installation and Servicing Instructions for Condensing Po...

Страница 2: ...AXIMUM RATE CO 3 3 3 0 3 COMBUSTION SETTINGS NG CO2 3 2 3 2 3 3 OFFSET SETTING pA 3 3 3 3 ORIFICE mm 4 5 6 7896 2 2 GENERAL SPECIFICATIONS WATER CONTENT MB35S MB50S 956 00 2 956 WEIGHT net MB35S MB50S 1 A A DIMENSIONS OVERALL 1 BB C9 BB D BB E9 E SERVICE CLEARANCE BB F5 G9 E5 HA I BB J F6 5 CORE DRILL DIAMETER 1 BB MINIMUM FLOW RATE KB 1 DB MAX PRIMARY WATER PRESSURE L A 6 1 D 9 INTERNAL PUMP SETT...

Страница 3: ...2 0 Hydraulic Resistance Graph Fig 3 0 Outdoor Terminal Fixing 0 Fig 3 1 Service Access Pipe Connections 1 Fig 3 2 Wall Terminal Dimensions 1 Fig 3 3 Outdoor Terminal Dimensions Fig 3 4 Roof Terminal Dimensions Fig 4 0 Wall Terminal Installation Fig 4 1 Extended Wall Terminal Installation Fig 4 2 Extended Vertical Roof Installation Fig 4 3 Outdoor Terminal Installation Fig 5 0 Pressure Switch Fig ...

Страница 4: ...CTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE This appliance is equipped with an ignition device which automatically lights the burner BEFORE OPERATING after a prolonged time off smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SM...

Страница 5: ...is not a fault but part of the design It will reduce for the final degree up to set temperature CAUTION Elevated water temperature can be hazardous and the U S Consumer Product Safety Commission recommends the following guidelines 1 Spa or hot tub water temperatures should never exceed 40 C 104 F A temperature of 38 C 100 F is considered safe for a healthy adult Special caution is suggested for yo...

Страница 6: ...m containing a bath or shower then the appliance and any electrical switch or appliance control utilising mains electricity should be so situated that it Condensing Pool Heater 3 12 08 09 INTRODUCTION These Instructions cover a range of indirect floor mounted gas fired condensing pool heaters which are room sealed and fan assisted The flue system available is concentric left right rear and vertica...

Страница 7: ...5 D Conversion 4 0 1 5 6 6 33 1 C 10 6 3 C 5 2 D P 0 1 0 1 6 C 1 2 C 66 1 3 1 Y 3 0 C 0C 6 C C C D F C 1 6 0 3 C 6 16 3 0 1 1 1 0 1 D Flueing Y1 2 3 0 5 1 1 0 3 6 2 C J 1 3 0 C 6 6 C C 10 D N 6 0 55 16 1 3 3 1 1 1 FDZ AQ LC 3 1 1 1 16 6 3 1 6O 10 D 1 3 C 5 3 5 C 3 16 C 1 33 0 0 1 C 6 0 1 2D 2 LC 3 0 1 S 1 6 8 3 8 C C 3 C 10 8 never 6 1 6 D 3 LC 6 C 0C 1 3 D P 0 1 3 6 C A 5 R 1 1 C 3 10 1 0 3 8 C 4...

Страница 8: ...2 00 16 6 0 1 C D Note EC 1 6 1 5 0 1O 1 1 C 8 C 10 8 12 0 O 0 0C 10 0 1 1 5 1 0 0 2 C 6 6 C 0 11 0C 6D 16 1 1 5 AZ AZ AI Condensate Drain See Fig 7 0 and 7 1 7 HZ55 0 16 1 6 6 1 C 16 3 0 2 C 1 0 11 0 6 F S 2 8 T 8 b 1 S 16 P1 1 N 1 2 5 D 7 S 16 3 1 1 C 0 16 1 6 1 2 5 JKFL 5 6 3 08 1 C 2 0 2 C R 6 D No other materials may be used LC S C 6 1 6 3 1 3 6 D LC 6 1 1 C Q 40 mm Hunter waste pipe Pool Pum...

Страница 9: ...1 0 16 8 1 1 8 C 1 5 1 8 1 C 1 5 6D LC 0 1 See Fig 8 1 3 1 C 5 1 18 16 C 0C 1 C 6 D L C J 1 5 0 11 0 6 16 1D 8 L 3 S D 9D b 0 C 0 0 16 1 D Assembly of the Outdoor Terminal 7 0 3 0 Y 6 L L 5 1 5 6 3 1 6 1 1D LC 5 GAA55 0 10 16 C 5 1 16 0 5 0 O 10 D LC Y 6 L L 5 1 C 3 1 C 4 76 16 0S 6 1 1 C 0 5 1 1 D See Fig 3 0 3 3 P3 0 1 R 6 1 2 1 1 0 1 C 6 6D 16 1 1 6 AB All Other Flue Systems LC 5 M 5 5 4 R 1 _ ...

Страница 10: ... M 1 1 U A W F T F 2 O 55 G F 3 2 9 Y O Z55 H 16 1 N 1 O he A55 1 0 I 4 5 O de ZA 55 0 N 5 1 4 1 Fig 3 2 Service Access Left Right or Above XAA55 In Front BAA55 b 4 _ 3 b C 4 Horizontal Wall Terminal Dimensions Horizontal Wall Terminal MBHT F G H I FE EL EL XG BB I X a I X a AGZ AGZ Z 55 AAA55 Xa I A IBA XH HB IA HHX X GZ X X I 7 XAH ZXX For Serial Nos below 099201 ...

Страница 11: ... 1 U A W F T F 2 O 55 G F 3 2 9 Y O Z55 H 16 1 N 1 O he A55 1 0 I 4 5 O de ZA 55 0 N 5 1 4 1 Fig 3 2 Service Access Left Right or Above XAA55 In Front BAA55 b 4 _ 3 b C 4 Horizontal Wall Terminal Dimensions Horizontal Wall Terminal MBHT F G H I FE EL EL XG BB I X a I X a AGZ AGZ Z 55 AAA55 Xa I A IBA XH HB IA HHX X ZX U_ W X X I 7 XAH ZXX GZ Ub W For Serial Nos 099201 onward ...

Страница 12: ...minal MBOT Fig 3 4 Clamp Assembly Screw 0C 6 b 3 P1 1 Vertical Roof Terminal Dimensions 4 b 3 P1 1 Use Seldeck Flashing System for all Roof Installations Vertical Roof Terminal MBVT 1 metre Horizontal Vertical Extension Pipe MBHVE 45 degree bends MB45DB ZZA ZAA ZAA ...

Страница 13: ...1 1 1 Y 1 Y 1 MBVT 9 0 b 3 L 5 1 1 1 i MBOT Y 6 L 5 1 i 1 1 MB45DB Z 6 16 1 Y 1 Y 1 MB90DB IA 6 16 1 Y 1 1 Outdoor Terminal Extended Horizontal Wall Terminal Extended Vertical Roof Terminal Horizontal Wall Terminal J YL J IAN J 9 J L U1 C 1W LY Y44F L KF J ZN J IAN J L U1 C 1W J 9L J 9 LY Y44F L KF J ZN Fig 4 3 Fig 4 0 Fig 4 1 Fig 4 2 N 5 1 C 2 3 4 2 5 2 R 16 0C 3 5 C 3 S Q ...

Страница 14: ...T 1 E L 5 1 XDI5 MBHVE 5 D 9 0 M 1 1 DA5 MBVT 9 0 b 3 L 5 1 XDX5 MBOT Y 6 L 5 1 1 MB45DB Z 6 16 U W D 5 MB90DB IA 6 16 DZ5 4 R 1 _ 1 C U5W LC J M 5 5 4 R 1 _ 1 C U4 _W 5 6 A 5 8 C 1 0 D LC 4 j O C 4 _ 3 0C 0 5 1 1 D 766 C 4 _g 6 1 2 6 1 16 0C 0S C C 6 1 M0 6 A 5 D see page 6 U 16W ...

Страница 15: ...bing LC C R 3 16 O 2D P 5 C 3 1 6 6 1O 5 3 C 3 16 5 D 7 2 0 1 1 5 6 3 Q 1 LC 5 5 6 C 1 3 C 4 D 2 LC 6 3 C 4 C 1 5 6 C 1 3 C D 3 LC 3 C 5 6 C 1 1 C D LC 5 8 4 16 5 6 1 D P3 1 0 2 1 1 C 1 C Fig 5 0 C 1 0 55 16 6 C 3 0C 1 6 16 1 0S 6 C C 2D LC 5 0 6 C 12 S 1 6 5 C 0 3 6 0 1 D LC 1 R 5 1 3 C C 1 0 11 0 1 C 8 5 1 0 1 5 6 1 16 6 0 de ZA55 3 5 C 6 6 5 1 K C 0C 1 Z 0 32 5 D 11 0 1 C 0 1 5 6 3 5 C 3 C 8 C ...

Страница 16: ... C 5 1 3 0 16 33 M 6 C M 1 D Gas Connection LC 55 0 0 11 0 1 6 6 0 1 1 6 M C 3 5 C C 3 C C D 7 5 1 5 5 3 A5 D UVTW8 XH5 U 1 W B 5 U 1 W 5 C 1 8 C C 16 C 0 11 0 6 O 10 3 1 D NB If the gas valve test point is used there is a 2 2 5 mbar drop for the Genie 50 at full rate C 0S 3 C 1 U DFD GBI Q IBBW 1 S 1 5 1 5 DUSee Fig 6 2W T 16 0 5 1 161 C 1 C C 6 0C 0S 6 1 1 3 5 16 S 6 0 1 3 6D C 0S C 5 M 5 5 16 0...

Страница 17: ... D C 0S 6 1 0 55 1 1 C C S 3 S 1 0 11 0 1 3 5 C C 6 1D LC 5 2 6 C 0 3 2 5 1 C 3 16 0C 0S 5 C 6 1D LC 3 C 62 3 1D LC nT 6 C 16 1 1 7 5 1 0 6 3 N 1 e 0 1 3 6 8 C Q D 11 1 D D S 1 16 3 O 1 1 ZX ZZB DC 5 Electrical Connections WARNING The appliance MUST be earthed 7 1 3 C 16 2 5 0 1 JKFL 0 13 5 PD D D E 1 b 1 8 16 S C 6 6 1 5 8 3 C 1 1 28 28 FC 0 16 b 10 CD LC 2 5 C C 0 55 1 8 6 X7 3 6 1 0C C 0 1 0 1 ...

Страница 18: ...ind vessel can be removed for Winterisation Condensate Syphon 75 mm 16 1 1 14 AB Fig 7 1 Removable Plate Use to close off unused Waste exit on panels 1 20 Fall 2 5 Degrees Strap On Boss 200mm Land Drain Filled with Lime chippings 400mm deep Insulate against freezing Note Do not reduce the pipe size below the 40mm provided Fig 7 0 Soakaway Stack Attachment Soil Pipe or Drain ...

Страница 19: ...3 0 2 3 V T 16 3 6 C 5 0 1 1 16 C 1 C 0 0S 18 5 1 0 11 0 6 16 C F 0C 0 6 2 C 5 D U3 6 C 1 1 0 1 C J 1 1 10 0 18 4 N 1 W Fig 8 0 _ T 5 6 R 5 6 3 6 6 0 6 1 D P 0 55 16 6 C C 0 16 1 3 3 3 3 1 D P3 C 3 C C C 6 1 16 2 1D P C 3 Z 5 16 C 1 0S D LC C C Red _ N 16 GAS 1 C 6 2D C _ 0S b 1 1 C Z 5 D P C C 3 1 6 33 C 1 C 1 C C C C D See Fig 8 2 73 C 1 C 1 3 3 5 1 C 16 0 5 1 C 6 0C 0S 68 C Technical Data on In...

Страница 20: ...1 6 Q L 1 1 F 0C Y44 C 1 0S YV C 1 C _ 0S b 1D L 1 C L 5 1 j1 1 C 6 2 C F C _ 0S b 1 10 16 C 6 2 C C F 0C C 1 F 0C Y44 C 1 0S YV 1D LC 1 1 6 2 1 1 6 D _ 0S b 1 Y1 Y33 F 0C L 5 N 2 L 5 1 j1 Fig 9 0 User Setup Mode Setting Factory Setting Alternative Display Indicator 1 Display units F Fahrenheit C Centigrade F or C 2 Maximum temperature 32 C 90 F 41 C 106 F PL or SPA 3 Software Version e g 011 T ...

Страница 21: ...C 3 5 C J 1 C 1 5 C L 1 16 C 0 0 C D b 5 LC 5 1 j1 b 5 LC 5 6 2 5 1 1 1 16 0 3 2 6 1 3 2 00 D UFig 10 0W 3 2 3 C 76 1 C 0 C 16 C L 5 D N 2 1 C 6 UFig 10 0W 1 1 C C M 1 1 C 6 C C C 16 6 3 C 76 168 C C 0 0S 1 1 1 0 D b 3 LC 5 6 16 j1 D b W 16 W 3 C D K 1 C 6 0 8 C 5 C C C 1 55 16 6 2 0C 1 C 76 C D LC 3 16 1 C f0C 1g C L 5 1 3 C 1 6 0S D LC 6 33 1 0 6 L 5 1 8 C 2 0 1 1 C C 3 D V D 1 C 0 11 0 3 2 C 5 ...

Страница 22: ... C 1 0C 1 C D 73 C 3O C J C 6 C C 0 5 8 16 C F C 6 C nOOOeD P3 F 0 1 1 C 5 1 6 2 3 6 C C 16 0 1 0 0 2 0 11 0 6 C J 8 0C 0S C P1 0 11 0 1 0 3 2 C 5 D b 0 C 1 D Fig 10 2 P3 F C 4 3 C 0C F 0C 6 0 C 1 55 6 2 16 C 4 _ N C D P 1 1 C D P C 1 0C 0S 2 X 5 1 3 C 5 C 1 0 0 68 C 4 _ N D P 3 0S 1 C 3 3 3 0 2D LC J 6 2 0 1 6 1 F J 6 S 1 D U GW K1 S 1 8 C 1 5 6 1 3 16 6 1 D Displays LC J 6 2 S 1 D 7 F 6 2 nOOOe ...

Страница 23: ...the Wall Mounting Kit Kit Part Code MBWMK35 50 Instructions Select a suitable wall and position to mount the Heater Note the Heater weighs 53kg Screw the Top Wall Mounting Bracket level to the wall Fig 10 4 Attach the Top Handle Bracket to the rear of the Heater by using the 3 M4 screws supplied Fig 10 5 Attach the Bottom Wall Mounting Bracket to the rear of the Heater by using the existing 3 gold...

Страница 24: ... 20 AB Fig 10 5 YLLYJ E7__ JYKVLPVT b7j L b JY9 N JYKVL7 _ YY_ 4PLLPVTF 4Yb LL b NbP__ 7 FF LY E7__ JYKVLPVT b7 j L _Y 7LPVT FLKNF U _ oFW TY_N F b EF FK _P N UX _ oFW J F b EF FK _P N UX _ oFW LY 7VN_ b7 j L ...

Страница 25: ...D i I A C5 D X S p D D A DH DI D 4 XA9 ZA _ V F_ _PVjQ b 5 3 0C 6 6 6 E7L b b FFKb FEPL T2 S Y 9 b T2 S T2 9 T i b b S b T2 b S E E T T S S Y 9 7L N J7VN _Y jYKL 7_7bJ 47V XA _ V V 47V L7 Y b F L l P _PJPL P _PJPL 47V EJ JYNK_7LPYV l b F L O 47V l 47V O b T2 S i N S 0S T2 T 2 T2 S T 2 0S 1 1S 9 9 i i b b 6 Y Y 1 E EC T i T 1 i b b 6 T T 1 T2 9 JYNK_7LPYV O T i KJ KJ b _7i T2 S _ 5 E T2 KJ bPJ b 9 ...

Страница 26: ... 6 C 1 3 C 1 16 1 3 0 16 1 8 1 6 3 5 K F J 6 D b LC 5 S1 3 2 0 0S C C 3 1 1 5 D C _ 0S b 1 3 X 0 16 D LC 0 1 1 1 F 0 J 6 D P 1 0C 1 5 3 C 1 g 5 D L C C 58 C LC 5 1 5 D L 0C 1 C 58 C b _ 0S 1 L M 8 1 C 1 F 0C 33 C 1 0S 1 1D 16 1 1 22 H A AI Test Temperature Display Mode 1 td1 L 5 6 2 6 AD 6 18 1 C 1 5 6 D LC 6 2 1 C 0C 1 5 16 020 16 C 5 3 0C 3 C _ 0S b 1D D L 5 1 5 2 6 2 6D LC T 1 _ N C D D L 5 6 2...

Страница 27: ...LC T 1 _ N C D XD M0C 1 4 L 5 D LC i _ N 3 C 6 2D D M0C 1 5 1 L 5 D LC b 6 _ N 3 C 6 2D b 1 C 1 5 0C 1 C 5 D 1 16 C 6 1 C 1 C 1 3 C 5 6 2 6 f 0S 1 0Sg 1 C 6 2 3 0 1 1 1D FAULT FINDING Service Mode Setting Factory Setting Reset press Display Indicator 1 Pressure Log Number of Operations Resets to zero Yellow LED ON 2 Unused Red LED ON 3 Combustion Gas Log Number of Operations Resets to zero Count R...

Страница 28: ...neering Mode Reset with Button GAS Gas Control Lockout Unable to light burner reset with Button OR Flue or Water Stat tripped reset on stat OR Fan resistor open cicuit investigate cause OR Valve Coils faulty replace valve FRONT PANEL ON PCB EXPLANATION OFF no mains supply or failed power supply Flashing HI Condensate level high Blocked Clear obstruction and allow control to auto reset SEr alternat...

Страница 29: ...ONT PANEL ON PCB EXPLANATION O I 8 O 0I P 2 0 01 OR Q 5 0 3 B 1 2 O I 8 O00I P 0 01 ORI 8 O 0I P K S70 8 R 2 0 01 OKI 8 O 0I P K S70 8 F1 2 0 01 OKI 8 O00I P K S70 8 F1 0 01 ORI 8 O00I P K S70 8 R 0 01 OS I 8 OTI P 2 2 0 01 OS I 8 OUI P 2 0 01 R 3 F E 6 1 339 0 0 2 F 1 F 05 8 2 4 2 F 6 ...

Страница 30: ...cular installation and usage but in general every 2000 hours of operation should be the maximum It is law that any service work should be carried out by Registered personnel 1 Clean burner and combustion chamber 2 Replace Heat Exchanger silicone door seal every 4000 hours 3 Check condition of ignition spark and sensing probe 4 Check boiler pipework joints for leaks 5 Check the Air duct and Flue se...

Страница 31: ...See Fig 14 4Y 8 K 26 MD M_ M A 0 2 3 0 0 6 3 21 0 0 0 0 2 0 0 2 F 05 6 Heat Exchanger Pool Sensor 0 2 05 OR I 3 0 4 K S70 8 6 XSee Fig 14 6 1 1 8 22 9 21 1 6 0 0 3 7 4 2 S 0 0 6 2 0 E 6 Water Pressure Switch 0 H 0 0 0 4 K S70 8 E 1 8 3 K 6 XSee Fig 14 6Y 1 33 S 0 0 0 A 0 3 0 4 K S70 8 6 2 0 E 6 H3 1 0 a1 8 CL 3 6 Control Thermostat 0 b1 0 0 3 K S70 8 6 XSee Fig 14 4Y A 0 2 3 0 0 6 3 21 0 0 0 0 2 0...

Страница 32: ... the new Pump Replacement is the reverse Expansion Vessel See Fig 14 0 Remove the single screw holding the retaining strap Release the flexible hose connection to the Vessel and remove it Replacement is the reverse Heat Exchanger See Fig 14 0 Remove the Expansion Vessel Remove the spacer below the Secondary Heat Exchanger by removing the two screws and pulling forward Release both the Heat Exchang...

Страница 33: ...003 Gas Valve M2140 SPMBG004 Ignition Control M2141 SPMBG005 Pool Thermostat PCB M2746 SPMBG057 Relay M2688 SPMBG054 Pressure Gauge M4240 SPCOH2 003 Water Pressure Switch 651284 SPCOH2 014 HT Lead M2142 SPMBG006 Condensate Syphon M2143 SPMBG007 Condensate Pressure Switch M2144 SPMBG008 Spark Sense Electrode M2146 SPMBG010 Flue Thermostat M2875 SPMBG060 Control Thermostat M2667 SPMBG055 High Limit ...

Страница 34: ...e Venturi Heat Exchanger Flow Sensor Heat Exchanger Control Thermostat Demountable Pool Connections Fig 14 5 Condensate Pressure Switch Flue Adapter Gas Valve HT Lead Spark Sense Electrode Condensate Syphon Combustion Sample Point Air Tube Throttle Hi Limit Thermostat Condensate Pipe Safety Valve Outlet Expansion Vessel Secondary Heat Exchanger Drain Fill point with NR Isolation valve Safety Valve...

Страница 35: ... 8 K 30 LL CL MN 2 8 F 4 3 F 5 ...

Страница 36: ... 8 K 31 LL CL MN 2 8 F 4 3 F 5 ...

Страница 37: ...INSTALLATION SERVICE HISTORY B V V GU V UM QV V c 1 b bL E 0 K 4 8 H 8 Q d 5 8 2 1 F b 22 bL e H 10 A 2 c f Q Tick appropriate c 1 b bL c 1 b bL 8 K LL CL MN ...

Страница 38: ... H 1 S 4 b7 6 Tel 01993 778855 Fax 01993 703407 LL CL MN ...

Отзывы: