Remove the Offset tube from the Gas Valve and
unscrew the Offset Connector and transfer to the
new Gas Valve.

 

NB Coil resistances, 2.8k and 1.6k ohms.

 

Release the Gas Valve from the Venturi by
undoing three screws. (

See Fig.14.3

)

IMPORTANT

 Ensure the rubber seal (and orifice if

Propane) is transfered from the old Valve and placed
between the Venturi and Gas Valve before assembly.

 

Replacement is the reverse.

 

Fire the Heater and check for gas leaks.

 

After five minutes check the rate and combustion
is correct to the Datatable. (inside cover). Adjust
using the throttle on the Gas Valve, 

(See Fig.

14.3)

.

Fan

  (

See Fig.14.2

)

 

Remove the two electrical connectors on the Fan.

 

Remove the two screws holding the Venturi to the
Fan.

 

Undo the four nuts holding the Fan to the Heat
Exchanger and withdraw. (

See Fig.14.2

)

 

Transfer the Venturi gasket to the new fan.

 

Replacement is the reverse.

Venturi

(

See Fig.14.2

)

 

Remove the Ignition Control and Gas Valve, see
above.

 

Pull off the Air Tube (

See Fig.14.3

)

 

Undo the two screws holding the Venturi to the
Fan and remove.

 

Ensure the gasket is transferred to the new
venturi or positioned on the Fan before position
ing the replacement.

 

Replacement is the reverse.

 

Fire the Heater and check for gas leaks.

 

After five minutes check the rate and combustion
is correct to the Datatable. (inside cover). Adjust
using the throttle on the Gas Valve if required.

(See Fig.14.3)

.

IMPORTANT. The following components require
the draining of the primary. It is recommended
that it is re-filled with one litre Sentinel X500
Inhibitor/Anti-freeze to provide winter protection.
It is essential that all the air is removed from the
Heat Exchanger before the Heater is fired. Run-
ning the Heater with air still in it will damage the
Heat Exchanger and invalidate the warranty.

Pump

  (

See Fig.14.0

)

 

Drain the primary waterside of the Heater.

 

Disconnect the Pump mains lead from the six way
connector in the Electrical Chassis.

 

Undo the two water connections of the pump and
remove.

 

Transfer the mains lead to the new Pump.

 

Replacement is the reverse.

Expansion Vessel 

(

See Fig.14.0

)

 !

Remove the single screw holding the retaining

strap.

 !

Release the flexible hose connection to the

Vessel and remove it.

 !

Replacement is the reverse.

Heat Exchanger

  (

See Fig.14.0

)

 !

Remove the Expansion Vessel

 !

Remove the spacer below the Secondary Heat

Exchanger by removing the two screws and
pulling forward.

 !

Release both the Heat Exchanger Demountable

connections. (

See Fig.14.5

)

 !

Undo the screws holding the panels around the

Demountable connections. (

See Fig.14.5

)

 

Lower the pipework away from the Heat Ex-
changer.

 

Remove the Front Top Panel and disconnect the
Flue Thermostat connections.

 

Pull the Air Duct and Flue up and away from the
Heater Flue Adapter.

 

Disconnect the Heat Exchanger Combustion
Sensor by pressing the latch and pulling off.

 

Remove the four screws holding the Rear Top
Panel.

 

Lift the Rear Top Panel with the Flue
Adapter clear of the Heat Exchanger.

 

Remove the Fan, Gas Valve and Ignition Control-
ler.

 

The Heat Exchanger is now only retained by the
two side brackets and releasing the four front
screws will enable it to be pulled forward. Before
releasing ensure there is support available.

 

Replacement is the reverse.

IMPORTANT: If the unit is fitted outdoors it is
recommended that it is re-filled with a
suitable anti-freeze, the manufacturer
recommends Sentinal X500.

Secondary Heat Exchanger

 (

See Fig.14.0

)

 

Drain the pool side sufficiently so that the
Heaters Pool Connections can be released.

 

Remove the Case retaining Plates around the
Heater’s Pool Connections.

 

Drain the primary system with the draincock
provided. Ensure an air vent is open to fully
release the water.

 

Remove the Pool Sensor from the Secondary
Heat Exchanger.

 

Remove the Expansion Vessel.

 

Remove the two fixing screws holding the
Spacer below the Secondary.

 

Pull out forwards the Spacer and remove.

 

Undo the primary Compression connections on
the Secondary Heat Exchanger and allow it to
drop off its connections and remove.

 

Remove the four screws fixing the Secondary
Heat Exchanger to its mounting plate.

 

Replacement is the reverse.

IMPORTANT: If the unit is fitted outdoors it is

recommended that it is filled with a suitable
anti-freeze, the manufacturer recommends
Sentinal X500.

Содержание MB35S

Страница 1: ...trical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions Installation and service must be performed by a Corgi registered installer A page is included on the inside back page of this booklet for recording commissioning and service details Operating Installation and Servicing Instructions for Condensing Po...

Страница 2: ...AXIMUM RATE CO 3 3 3 0 3 COMBUSTION SETTINGS NG CO2 3 2 3 2 3 3 OFFSET SETTING pA 3 3 3 3 ORIFICE mm 4 5 6 7896 2 2 GENERAL SPECIFICATIONS WATER CONTENT MB35S MB50S 956 00 2 956 WEIGHT net MB35S MB50S 1 A A DIMENSIONS OVERALL 1 BB C9 BB D BB E9 E SERVICE CLEARANCE BB F5 G9 E5 HA I BB J F6 5 CORE DRILL DIAMETER 1 BB MINIMUM FLOW RATE KB 1 DB MAX PRIMARY WATER PRESSURE L A 6 1 D 9 INTERNAL PUMP SETT...

Страница 3: ...2 0 Hydraulic Resistance Graph Fig 3 0 Outdoor Terminal Fixing 0 Fig 3 1 Service Access Pipe Connections 1 Fig 3 2 Wall Terminal Dimensions 1 Fig 3 3 Outdoor Terminal Dimensions Fig 3 4 Roof Terminal Dimensions Fig 4 0 Wall Terminal Installation Fig 4 1 Extended Wall Terminal Installation Fig 4 2 Extended Vertical Roof Installation Fig 4 3 Outdoor Terminal Installation Fig 5 0 Pressure Switch Fig ...

Страница 4: ...CTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE This appliance is equipped with an ignition device which automatically lights the burner BEFORE OPERATING after a prolonged time off smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SM...

Страница 5: ...is not a fault but part of the design It will reduce for the final degree up to set temperature CAUTION Elevated water temperature can be hazardous and the U S Consumer Product Safety Commission recommends the following guidelines 1 Spa or hot tub water temperatures should never exceed 40 C 104 F A temperature of 38 C 100 F is considered safe for a healthy adult Special caution is suggested for yo...

Страница 6: ...m containing a bath or shower then the appliance and any electrical switch or appliance control utilising mains electricity should be so situated that it Condensing Pool Heater 3 12 08 09 INTRODUCTION These Instructions cover a range of indirect floor mounted gas fired condensing pool heaters which are room sealed and fan assisted The flue system available is concentric left right rear and vertica...

Страница 7: ...5 D Conversion 4 0 1 5 6 6 33 1 C 10 6 3 C 5 2 D P 0 1 0 1 6 C 1 2 C 66 1 3 1 Y 3 0 C 0C 6 C C C D F C 1 6 0 3 C 6 16 3 0 1 1 1 0 1 D Flueing Y1 2 3 0 5 1 1 0 3 6 2 C J 1 3 0 C 6 6 C C 10 D N 6 0 55 16 1 3 3 1 1 1 FDZ AQ LC 3 1 1 1 16 6 3 1 6O 10 D 1 3 C 5 3 5 C 3 16 C 1 33 0 0 1 C 6 0 1 2D 2 LC 3 0 1 S 1 6 8 3 8 C C 3 C 10 8 never 6 1 6 D 3 LC 6 C 0C 1 3 D P 0 1 3 6 C A 5 R 1 1 C 3 10 1 0 3 8 C 4...

Страница 8: ...2 00 16 6 0 1 C D Note EC 1 6 1 5 0 1O 1 1 C 8 C 10 8 12 0 O 0 0C 10 0 1 1 5 1 0 0 2 C 6 6 C 0 11 0C 6D 16 1 1 5 AZ AZ AI Condensate Drain See Fig 7 0 and 7 1 7 HZ55 0 16 1 6 6 1 C 16 3 0 2 C 1 0 11 0 6 F S 2 8 T 8 b 1 S 16 P1 1 N 1 2 5 D 7 S 16 3 1 1 C 0 16 1 6 1 2 5 JKFL 5 6 3 08 1 C 2 0 2 C R 6 D No other materials may be used LC S C 6 1 6 3 1 3 6 D LC 6 1 1 C Q 40 mm Hunter waste pipe Pool Pum...

Страница 9: ...1 0 16 8 1 1 8 C 1 5 1 8 1 C 1 5 6D LC 0 1 See Fig 8 1 3 1 C 5 1 18 16 C 0C 1 C 6 D L C J 1 5 0 11 0 6 16 1D 8 L 3 S D 9D b 0 C 0 0 16 1 D Assembly of the Outdoor Terminal 7 0 3 0 Y 6 L L 5 1 5 6 3 1 6 1 1D LC 5 GAA55 0 10 16 C 5 1 16 0 5 0 O 10 D LC Y 6 L L 5 1 C 3 1 C 4 76 16 0S 6 1 1 C 0 5 1 1 D See Fig 3 0 3 3 P3 0 1 R 6 1 2 1 1 0 1 C 6 6D 16 1 1 6 AB All Other Flue Systems LC 5 M 5 5 4 R 1 _ ...

Страница 10: ... M 1 1 U A W F T F 2 O 55 G F 3 2 9 Y O Z55 H 16 1 N 1 O he A55 1 0 I 4 5 O de ZA 55 0 N 5 1 4 1 Fig 3 2 Service Access Left Right or Above XAA55 In Front BAA55 b 4 _ 3 b C 4 Horizontal Wall Terminal Dimensions Horizontal Wall Terminal MBHT F G H I FE EL EL XG BB I X a I X a AGZ AGZ Z 55 AAA55 Xa I A IBA XH HB IA HHX X GZ X X I 7 XAH ZXX For Serial Nos below 099201 ...

Страница 11: ... 1 U A W F T F 2 O 55 G F 3 2 9 Y O Z55 H 16 1 N 1 O he A55 1 0 I 4 5 O de ZA 55 0 N 5 1 4 1 Fig 3 2 Service Access Left Right or Above XAA55 In Front BAA55 b 4 _ 3 b C 4 Horizontal Wall Terminal Dimensions Horizontal Wall Terminal MBHT F G H I FE EL EL XG BB I X a I X a AGZ AGZ Z 55 AAA55 Xa I A IBA XH HB IA HHX X ZX U_ W X X I 7 XAH ZXX GZ Ub W For Serial Nos 099201 onward ...

Страница 12: ...minal MBOT Fig 3 4 Clamp Assembly Screw 0C 6 b 3 P1 1 Vertical Roof Terminal Dimensions 4 b 3 P1 1 Use Seldeck Flashing System for all Roof Installations Vertical Roof Terminal MBVT 1 metre Horizontal Vertical Extension Pipe MBHVE 45 degree bends MB45DB ZZA ZAA ZAA ...

Страница 13: ...1 1 1 Y 1 Y 1 MBVT 9 0 b 3 L 5 1 1 1 i MBOT Y 6 L 5 1 i 1 1 MB45DB Z 6 16 1 Y 1 Y 1 MB90DB IA 6 16 1 Y 1 1 Outdoor Terminal Extended Horizontal Wall Terminal Extended Vertical Roof Terminal Horizontal Wall Terminal J YL J IAN J 9 J L U1 C 1W LY Y44F L KF J ZN J IAN J L U1 C 1W J 9L J 9 LY Y44F L KF J ZN Fig 4 3 Fig 4 0 Fig 4 1 Fig 4 2 N 5 1 C 2 3 4 2 5 2 R 16 0C 3 5 C 3 S Q ...

Страница 14: ...T 1 E L 5 1 XDI5 MBHVE 5 D 9 0 M 1 1 DA5 MBVT 9 0 b 3 L 5 1 XDX5 MBOT Y 6 L 5 1 1 MB45DB Z 6 16 U W D 5 MB90DB IA 6 16 DZ5 4 R 1 _ 1 C U5W LC J M 5 5 4 R 1 _ 1 C U4 _W 5 6 A 5 8 C 1 0 D LC 4 j O C 4 _ 3 0C 0 5 1 1 D 766 C 4 _g 6 1 2 6 1 16 0C 0S C C 6 1 M0 6 A 5 D see page 6 U 16W ...

Страница 15: ...bing LC C R 3 16 O 2D P 5 C 3 1 6 6 1O 5 3 C 3 16 5 D 7 2 0 1 1 5 6 3 Q 1 LC 5 5 6 C 1 3 C 4 D 2 LC 6 3 C 4 C 1 5 6 C 1 3 C D 3 LC 3 C 5 6 C 1 1 C D LC 5 8 4 16 5 6 1 D P3 1 0 2 1 1 C 1 C Fig 5 0 C 1 0 55 16 6 C 3 0C 1 6 16 1 0S 6 C C 2D LC 5 0 6 C 12 S 1 6 5 C 0 3 6 0 1 D LC 1 R 5 1 3 C C 1 0 11 0 1 C 8 5 1 0 1 5 6 1 16 6 0 de ZA55 3 5 C 6 6 5 1 K C 0C 1 Z 0 32 5 D 11 0 1 C 0 1 5 6 3 5 C 3 C 8 C ...

Страница 16: ... C 5 1 3 0 16 33 M 6 C M 1 D Gas Connection LC 55 0 0 11 0 1 6 6 0 1 1 6 M C 3 5 C C 3 C C D 7 5 1 5 5 3 A5 D UVTW8 XH5 U 1 W B 5 U 1 W 5 C 1 8 C C 16 C 0 11 0 6 O 10 3 1 D NB If the gas valve test point is used there is a 2 2 5 mbar drop for the Genie 50 at full rate C 0S 3 C 1 U DFD GBI Q IBBW 1 S 1 5 1 5 DUSee Fig 6 2W T 16 0 5 1 161 C 1 C C 6 0C 0S 6 1 1 3 5 16 S 6 0 1 3 6D C 0S C 5 M 5 5 16 0...

Страница 17: ... D C 0S 6 1 0 55 1 1 C C S 3 S 1 0 11 0 1 3 5 C C 6 1D LC 5 2 6 C 0 3 2 5 1 C 3 16 0C 0S 5 C 6 1D LC 3 C 62 3 1D LC nT 6 C 16 1 1 7 5 1 0 6 3 N 1 e 0 1 3 6 8 C Q D 11 1 D D S 1 16 3 O 1 1 ZX ZZB DC 5 Electrical Connections WARNING The appliance MUST be earthed 7 1 3 C 16 2 5 0 1 JKFL 0 13 5 PD D D E 1 b 1 8 16 S C 6 6 1 5 8 3 C 1 1 28 28 FC 0 16 b 10 CD LC 2 5 C C 0 55 1 8 6 X7 3 6 1 0C C 0 1 0 1 ...

Страница 18: ...ind vessel can be removed for Winterisation Condensate Syphon 75 mm 16 1 1 14 AB Fig 7 1 Removable Plate Use to close off unused Waste exit on panels 1 20 Fall 2 5 Degrees Strap On Boss 200mm Land Drain Filled with Lime chippings 400mm deep Insulate against freezing Note Do not reduce the pipe size below the 40mm provided Fig 7 0 Soakaway Stack Attachment Soil Pipe or Drain ...

Страница 19: ...3 0 2 3 V T 16 3 6 C 5 0 1 1 16 C 1 C 0 0S 18 5 1 0 11 0 6 16 C F 0C 0 6 2 C 5 D U3 6 C 1 1 0 1 C J 1 1 10 0 18 4 N 1 W Fig 8 0 _ T 5 6 R 5 6 3 6 6 0 6 1 D P 0 55 16 6 C C 0 16 1 3 3 3 3 1 D P3 C 3 C C C 6 1 16 2 1D P C 3 Z 5 16 C 1 0S D LC C C Red _ N 16 GAS 1 C 6 2D C _ 0S b 1 1 C Z 5 D P C C 3 1 6 33 C 1 C 1 C C C C D See Fig 8 2 73 C 1 C 1 3 3 5 1 C 16 0 5 1 C 6 0C 0S 68 C Technical Data on In...

Страница 20: ...1 6 Q L 1 1 F 0C Y44 C 1 0S YV C 1 C _ 0S b 1D L 1 C L 5 1 j1 1 C 6 2 C F C _ 0S b 1 10 16 C 6 2 C C F 0C C 1 F 0C Y44 C 1 0S YV 1D LC 1 1 6 2 1 1 6 D _ 0S b 1 Y1 Y33 F 0C L 5 N 2 L 5 1 j1 Fig 9 0 User Setup Mode Setting Factory Setting Alternative Display Indicator 1 Display units F Fahrenheit C Centigrade F or C 2 Maximum temperature 32 C 90 F 41 C 106 F PL or SPA 3 Software Version e g 011 T ...

Страница 21: ...C 3 5 C J 1 C 1 5 C L 1 16 C 0 0 C D b 5 LC 5 1 j1 b 5 LC 5 6 2 5 1 1 1 16 0 3 2 6 1 3 2 00 D UFig 10 0W 3 2 3 C 76 1 C 0 C 16 C L 5 D N 2 1 C 6 UFig 10 0W 1 1 C C M 1 1 C 6 C C C 16 6 3 C 76 168 C C 0 0S 1 1 1 0 D b 3 LC 5 6 16 j1 D b W 16 W 3 C D K 1 C 6 0 8 C 5 C C C 1 55 16 6 2 0C 1 C 76 C D LC 3 16 1 C f0C 1g C L 5 1 3 C 1 6 0S D LC 6 33 1 0 6 L 5 1 8 C 2 0 1 1 C C 3 D V D 1 C 0 11 0 3 2 C 5 ...

Страница 22: ... C 1 0C 1 C D 73 C 3O C J C 6 C C 0 5 8 16 C F C 6 C nOOOeD P3 F 0 1 1 C 5 1 6 2 3 6 C C 16 0 1 0 0 2 0 11 0 6 C J 8 0C 0S C P1 0 11 0 1 0 3 2 C 5 D b 0 C 1 D Fig 10 2 P3 F C 4 3 C 0C F 0C 6 0 C 1 55 6 2 16 C 4 _ N C D P 1 1 C D P C 1 0C 0S 2 X 5 1 3 C 5 C 1 0 0 68 C 4 _ N D P 3 0S 1 C 3 3 3 0 2D LC J 6 2 0 1 6 1 F J 6 S 1 D U GW K1 S 1 8 C 1 5 6 1 3 16 6 1 D Displays LC J 6 2 S 1 D 7 F 6 2 nOOOe ...

Страница 23: ...the Wall Mounting Kit Kit Part Code MBWMK35 50 Instructions Select a suitable wall and position to mount the Heater Note the Heater weighs 53kg Screw the Top Wall Mounting Bracket level to the wall Fig 10 4 Attach the Top Handle Bracket to the rear of the Heater by using the 3 M4 screws supplied Fig 10 5 Attach the Bottom Wall Mounting Bracket to the rear of the Heater by using the existing 3 gold...

Страница 24: ... 20 AB Fig 10 5 YLLYJ E7__ JYKVLPVT b7j L b JY9 N JYKVL7 _ YY_ 4PLLPVTF 4Yb LL b NbP__ 7 FF LY E7__ JYKVLPVT b7 j L _Y 7LPVT FLKNF U _ oFW TY_N F b EF FK _P N UX _ oFW J F b EF FK _P N UX _ oFW LY 7VN_ b7 j L ...

Страница 25: ...D i I A C5 D X S p D D A DH DI D 4 XA9 ZA _ V F_ _PVjQ b 5 3 0C 6 6 6 E7L b b FFKb FEPL T2 S Y 9 b T2 S T2 9 T i b b S b T2 b S E E T T S S Y 9 7L N J7VN _Y jYKL 7_7bJ 47V XA _ V V 47V L7 Y b F L l P _PJPL P _PJPL 47V EJ JYNK_7LPYV l b F L O 47V l 47V O b T2 S i N S 0S T2 T 2 T2 S T 2 0S 1 1S 9 9 i i b b 6 Y Y 1 E EC T i T 1 i b b 6 T T 1 T2 9 JYNK_7LPYV O T i KJ KJ b _7i T2 S _ 5 E T2 KJ bPJ b 9 ...

Страница 26: ... 6 C 1 3 C 1 16 1 3 0 16 1 8 1 6 3 5 K F J 6 D b LC 5 S1 3 2 0 0S C C 3 1 1 5 D C _ 0S b 1 3 X 0 16 D LC 0 1 1 1 F 0 J 6 D P 1 0C 1 5 3 C 1 g 5 D L C C 58 C LC 5 1 5 D L 0C 1 C 58 C b _ 0S 1 L M 8 1 C 1 F 0C 33 C 1 0S 1 1D 16 1 1 22 H A AI Test Temperature Display Mode 1 td1 L 5 6 2 6 AD 6 18 1 C 1 5 6 D LC 6 2 1 C 0C 1 5 16 020 16 C 5 3 0C 3 C _ 0S b 1D D L 5 1 5 2 6 2 6D LC T 1 _ N C D D L 5 6 2...

Страница 27: ...LC T 1 _ N C D XD M0C 1 4 L 5 D LC i _ N 3 C 6 2D D M0C 1 5 1 L 5 D LC b 6 _ N 3 C 6 2D b 1 C 1 5 0C 1 C 5 D 1 16 C 6 1 C 1 C 1 3 C 5 6 2 6 f 0S 1 0Sg 1 C 6 2 3 0 1 1 1D FAULT FINDING Service Mode Setting Factory Setting Reset press Display Indicator 1 Pressure Log Number of Operations Resets to zero Yellow LED ON 2 Unused Red LED ON 3 Combustion Gas Log Number of Operations Resets to zero Count R...

Страница 28: ...neering Mode Reset with Button GAS Gas Control Lockout Unable to light burner reset with Button OR Flue or Water Stat tripped reset on stat OR Fan resistor open cicuit investigate cause OR Valve Coils faulty replace valve FRONT PANEL ON PCB EXPLANATION OFF no mains supply or failed power supply Flashing HI Condensate level high Blocked Clear obstruction and allow control to auto reset SEr alternat...

Страница 29: ...ONT PANEL ON PCB EXPLANATION O I 8 O 0I P 2 0 01 OR Q 5 0 3 B 1 2 O I 8 O00I P 0 01 ORI 8 O 0I P K S70 8 R 2 0 01 OKI 8 O 0I P K S70 8 F1 2 0 01 OKI 8 O00I P K S70 8 F1 0 01 ORI 8 O00I P K S70 8 R 0 01 OS I 8 OTI P 2 2 0 01 OS I 8 OUI P 2 0 01 R 3 F E 6 1 339 0 0 2 F 1 F 05 8 2 4 2 F 6 ...

Страница 30: ...cular installation and usage but in general every 2000 hours of operation should be the maximum It is law that any service work should be carried out by Registered personnel 1 Clean burner and combustion chamber 2 Replace Heat Exchanger silicone door seal every 4000 hours 3 Check condition of ignition spark and sensing probe 4 Check boiler pipework joints for leaks 5 Check the Air duct and Flue se...

Страница 31: ...See Fig 14 4Y 8 K 26 MD M_ M A 0 2 3 0 0 6 3 21 0 0 0 0 2 0 0 2 F 05 6 Heat Exchanger Pool Sensor 0 2 05 OR I 3 0 4 K S70 8 6 XSee Fig 14 6 1 1 8 22 9 21 1 6 0 0 3 7 4 2 S 0 0 6 2 0 E 6 Water Pressure Switch 0 H 0 0 0 4 K S70 8 E 1 8 3 K 6 XSee Fig 14 6Y 1 33 S 0 0 0 A 0 3 0 4 K S70 8 6 2 0 E 6 H3 1 0 a1 8 CL 3 6 Control Thermostat 0 b1 0 0 3 K S70 8 6 XSee Fig 14 4Y A 0 2 3 0 0 6 3 21 0 0 0 0 2 0...

Страница 32: ... the new Pump Replacement is the reverse Expansion Vessel See Fig 14 0 Remove the single screw holding the retaining strap Release the flexible hose connection to the Vessel and remove it Replacement is the reverse Heat Exchanger See Fig 14 0 Remove the Expansion Vessel Remove the spacer below the Secondary Heat Exchanger by removing the two screws and pulling forward Release both the Heat Exchang...

Страница 33: ...003 Gas Valve M2140 SPMBG004 Ignition Control M2141 SPMBG005 Pool Thermostat PCB M2746 SPMBG057 Relay M2688 SPMBG054 Pressure Gauge M4240 SPCOH2 003 Water Pressure Switch 651284 SPCOH2 014 HT Lead M2142 SPMBG006 Condensate Syphon M2143 SPMBG007 Condensate Pressure Switch M2144 SPMBG008 Spark Sense Electrode M2146 SPMBG010 Flue Thermostat M2875 SPMBG060 Control Thermostat M2667 SPMBG055 High Limit ...

Страница 34: ...e Venturi Heat Exchanger Flow Sensor Heat Exchanger Control Thermostat Demountable Pool Connections Fig 14 5 Condensate Pressure Switch Flue Adapter Gas Valve HT Lead Spark Sense Electrode Condensate Syphon Combustion Sample Point Air Tube Throttle Hi Limit Thermostat Condensate Pipe Safety Valve Outlet Expansion Vessel Secondary Heat Exchanger Drain Fill point with NR Isolation valve Safety Valve...

Страница 35: ... 8 K 30 LL CL MN 2 8 F 4 3 F 5 ...

Страница 36: ... 8 K 31 LL CL MN 2 8 F 4 3 F 5 ...

Страница 37: ...INSTALLATION SERVICE HISTORY B V V GU V UM QV V c 1 b bL E 0 K 4 8 H 8 Q d 5 8 2 1 F b 22 bL e H 10 A 2 c f Q Tick appropriate c 1 b bL c 1 b bL 8 K LL CL MN ...

Страница 38: ... H 1 S 4 b7 6 Tel 01993 778855 Fax 01993 703407 LL CL MN ...

Отзывы: