C750 & C750R User
Manual Page 46
(1)
Site wiring fault function is only for single phase bypass input. If the utility power is IT system, the site wiring fault
function should be disabled.
Setting
Options on the display
Default
Auto restart
[Enabled], [Disabled]
Enabled
Short circuit auto clear
[Enabled], [Disabled]
Disabled
Overload pre-alarm
50%~105%
105%
Battery
DC Start
[Enabled], [Disabled]
Enabled
Battery Auto Test
[Every cycle] [Disabled]
Every cycle
Deep discharge
protection
[Enabled], [Disabled]
Enabled
Low bat warning
0%~100%
0%
Low remaining time
warning
0-999min
0min
Restart battery level
0~100%
0%
Charger current
[1-13A]
[4A] for 10-20KS
[1.4A] for 15K
[2A] for 10K/20K
External battery setting
[Auto detection], [Manual AH setting]
Manual AH setting: [9-300AH]
[Auto detection]
/
Communica
tion
Dry in
[No function] [Start UPS] [Remote shut down]
[Maintenance bypass]
No function
Dry out
[load powered] [on battery] [Low battery] [No
Battery] [Bypass] [ups OK]
load powered
IoT function
[Enabled], [Disabled]
Disabled
Modbus TCP
[Enabled], [Disabled]
Disabled
Password
Control Menu password
[Enabled], [Disabled]
Enabled
Setting Menu password
[Enabled], [Disabled]
Enabled
Change Password
Old password
New password
Confirm password
[4314]