C300R User Manual
Page 25
SHOR
Inverter short
Check UPS output for possible short circuit
ISFT
Inverter soft start fail
Contact your service representative
bSFT
Bus soft start fail
Contact your service representative
OVTP
Over temperature fault
Ensure adequate ventilation and ambient temperature
INVL
Inverter voltage low
Contact your service representative
INVH
Inverter voltage high
Contact your service representative
bUSH
BUS overvolt
Contact your service representative
bUSL
BUS under volt
Allow time for the Batteries to charge
Contact your service representative
bUSS
BUS short circuit
Contact your service representative
NTCO
Inverter NTC open
Contact your service representative
EPO
Emergency power off
EPO connection has changed state
SILENCING THE ALARM
•
Press the button for one second. Seconds to silence the alarm.
Check the alarm condition and perform the applicable action to resolve the condition.
If an alarm status changes the alarm will need to be silenced again.
TESTING THE BATTERIES
When initiating a battery test
•
Ensure the batteries are fully charged
•
The UPS must be in normal mode with no active alarms
•
Do not connect or disconnect equipment
To start the battery test
•
Connect the UPS to mains power for at least 48 hours to charge the batteries
•
Press and hold the
button for 10 seconds to start the battery test. The status display string will show
“TEST”