Page 14
Installation and Operation Requirements - S250
ENGLISH
3.1.3
With Heat Shield AC02762 and Lowered Ceiling
To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used . Refer to the booklet in the screen options to obtain the dimensions to
be respected.
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
USA
A
2 ½" (64 mm)
2 ½" (64 mm)
B
2 ½" (64 mm)
2 ½" (64 mm)
C
2 ½" (64 mm)
2 ½" (64 mm)
L
72" (1829 mm)
72" (1829 mm)
Ve
Ho
L
DISTANCES
19
FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTOR
Canada
USA
D
5 ¾" (146 mm)
5 ¾" (146 mm)
E
8 ¼" (210 mm)
8 ¼" (210 mm)
F
9" (229 mm)
9" (229 mm)
A
B
E
D
CAN
48"
122 cm
US
36"
92 cm
48"
Flush
F
F
C
If the clearance reduction is on the same side as the door handle, position the stove at
a minimum of 6 inches from the side wall (clearance B), otherwise it may be located at
the clearance shown in the table above.
19
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.
Содержание CB00025
Страница 4: ...Page 4 Wood Stove Owner s Manual ENGLISH ...
Страница 32: ...Page 4 Installation and Operation Requirements S250 ENGLISH 1 Certification Plate ...
Страница 57: ...Page 29 Installation and Operation Requirements S250 ENGLISH 8 Exploded Diagram and Parts List ...
Страница 61: ...Page 33 Installation and Operation Requirements S250 ENGLISH ...