Always follow the most up-to-date local, municipal and building
regulations and codes.
i
Ensure the boiler room complies with the requirements in these technical instructions. Boiler room
must be frost-proof and well ventilated. Boiler has to be positioned so that it can be properly connected
to the chimney and simultaneously, enabling tending of boiler and additional equipment, control during
operation, and cleaning and maintenance. No combustible materials may be stored in the boiler room.
Boiler may only be placed on fire and temperature resistant floor. No temperature-sensitive pipes or
lines may be installed in the floor beneath the heating boiler. The minimum distance to the walls
required according to point „Minimum distance from the boiler room walls”. The fresh air supply
required according to point „Opening for fresh air”. The temperature in the boiler room must not exceed
+40°C while system is in operation. The temperature in the boiler room must not fall below +10°C while
the system is in operation.
Boiler must not operate in flammable and explosive environment.
The boiler has to be put on the previously prepared concrete fundament which minimum height is
200-300 mm. The upper fundament surface has to be smooth and exactly horizontal.
The room has to be frost proof and adequately ventilated. The boiler has to be situated in order its
connection to the chimney can be performed correctly; its cleaning and handling should be convenient.
If there is planned an cyclone and fan connection, the boiler has to be situated to have all its parts easily
accessible. The casing has to be assembled after the boiler has been connected to the chimney and to
the central heating system, according to the instructions attached. Before connecting to the instalation
the boiler has to be put exactly in the horizontal position.
Hot water boiler
EKO-CKS P UNIT
can be fired with
wood pellets (C1
by EN 303-5:2012;
A1
by ISO
17225-2:2014).
FUEL CHARACTERISTICS
- heating value: >= 5 kWh/kg (18 MJ/kg)
- diameter: <= 6 mm
- max. moisture content: <= 12 %
- max. dust content: <= 1,5 %.
3.0. FUEL
4.0. ASSEMBLAGE OF THE BOILER
4.1. BOILER ROOM