GB

System pressure safety

The system pressure is checked electronically and needs 
to be between 0,5 and 2,3 bar. If this is not the case, 
the pellet  boiler    signalises  an  alarm  and  shows  the 
words “

A l a r   P r e s s

” on the display.

Press” on the display. Check the system pressure keeping 
the key 

 pressed for some seconds. You will read the 

bar value on the display.
The  safety  valve  keeps  anyway  the  value  under  2,5  bar 
letting the exceeding water flow out automatically.

Intervention in case of danger

In  case  of  fire,  disconnect  the  power  supply,  use  a  fire 
extinguisher in accordance with, and if necessary, call the 
fire department and then contact an authorised qualified 
technical assistance

Failed light-up

If the flame does not light up during the switching on or if 
the smokes temperature does not reach a suitable value 
in the foreseen time gap, the 

boiler

 switches off and you 

will read the words “

A l a r   N o   A c c

” on the display.

 

Press 

the key “On/Off” to reset the alarm. Wait until the cooling 
phase  is  completed,  clean  the  brazier  and  start  a  new 
light-up.

Switching off while working

The 

boiler

  suddenly  switches  off  while  working  (for 

example  because  it  has  run  out  of  pellets  in  the  tank  or 
because  the  motor  reducer  for  pellets  loading  got 
broken). The 

boiler

 continues working until the pellets left 

in  the  brazier  ends.  You  will  then  read  the  words  “

A l a r

N o   F i r e

” on the display and the 

boiler

 switches off. Press 

the key “On/Off” to reset the alarm. Wait until the cooling 
phase  is  completed.  Clean  the  brazier  and  start  a  new 
light-up.

These alarms remind you that the brazier must be 
cleaned  and  installed  correctly  before  switching 
on the 

boiler

.

There is no power supply

In the event of a power drop longer than one minute, 
the 

boiler

 can exhaust some smoke in the room: this 

causes no risks.
As  soon  as  you  have  the  power  supply  again,  the 

boiler

  will  have  the  words  “

C o o l   F i r e

”  on the 

display.  After  completing  the  cooling  phase,  the 

boiler

  will  start  up  again  automatically  according to the 

previous settings.

Manual restart thermostat

Do  not  attempt  to  start  the 

boiler

 

before  the  required  time  or  it  may 
get blocked. If this occurs, switch off 
the 

switch  on  the  back  of  the  pellet  boiler    for  1 
minute,  set  it  on  again  and  wait  10  minutes 
before starting the 

boiler

 again.

The  power  socket  where  the 

boiler

  is 

connected  should  be  fitted  with  “earth 
connection complying with regulations in 

force.” The Manufacturer shall not be held respon-
sible for damage to things or people resulting from 
negligent installation.

Restart

Water

Содержание CentroPelet ZVB 16

Страница 1: ...UE CentroPelet ZVB 16 20 24 32 TURZVB 01 2017 ENG Centrometal d o o Glavna 12 40306 Macinec Croatia tel 385 40 372 600 fax 385 40 372 611 TECHNICAL INSTRUCTIONS for installation use and maintenance of...

Страница 2: ...an reach high temperatures Therefore pay attention and use the proper precautions above all in the presence of children elderly or disabled persons and animals Assembly must be performed by authorized...

Страница 3: ...e every responsibility derived from improper use of the boiler from incorrect use by the user from un authorized modifications and or repairs from the use of replacement parts that are not original fo...

Страница 4: ...upervision or instruction concerning use of the appliance Do not use the boiler as a ladder or scaffold Do not put clothes to dry on the boiler Any clothes hangers and suchlike must be kept a suitable...

Страница 5: ...ammable maintain a minimum distance of 10 cm at the rear A di 40 cm at the side B and 150 cm at the front If the room contains objects which are believed to be particularly delicate such as drapes sof...

Страница 6: ...ess steel pipe must not be used At the bottom of the flue pipe provide an inspection cap to allow periodic checking and cleaning which must be done annually Make a gas tight connection to the flue pip...

Страница 7: ...must be a wind proof type and must be above the ridge Eventual structures or other obstacles that are higher than the chimney cap must not be too close to the chimney cap itself Fig 5 Characteristics...

Страница 8: ...Water amount in stove Autonomy Power supply Power consume at nominal power Dimensions width depth height Net weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 16 4 29 14 4 1 02 3 37 89 11 87 87 80...

Страница 9: ...t weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 20 5 21 17 51 1 2 3 88 92 13 88 82 80 50 65 50 54 16 5 230 50 100 300 610x785x1240 250 ZVB 24 Technical characteristics CentroPelet ZVB 20 24 80...

Страница 10: ...in stove Autonomy Power supply Power consume at nominal power Dimensions width depth height Net weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 32 6 34 29 14 1 43 6 48 91 64 90 65 100 60 85 60 38...

Страница 11: ...e LED is on when the parameter UT01 on the menu is not on OFF and the weekly or daily programming are set SET LED SYMBOL DESCRIPTION The LED starts up every time the boiler is loading pellets The LED...

Страница 12: ...the water temperature press the key only once You will see the words Set H2o blinking on the upper display You will read the water temperature on the lower display To set the room temperature press th...

Страница 13: ...ntrol panel for example 18 C and a sufficient shut down time has elapsed the boiler will come back on automatically and continue running until again reaching 20 C Regardless of the operation of the ex...

Страница 14: ...ystem through the inlet pipe causing a phenomenon of oxygen that is highly damaging to life of the boiler To prevent this phenomenon it is possible to apply the following measures lower the speed of t...

Страница 15: ...adjustment UT06 From 00 00 to 23 50 with 10 minute steps Boiler first shutdown time adjustment UT07 Between on off for days from 1 to 7 Week day selection first time activation UT08 From 00 00 to 23...

Страница 16: ...day Day 6 Saturday Day 7 Sunday OFF Heating timer thermostat disabled UT07 Week day selection Press button o select the days of the week Press button to enable ON or disable OFF the pellet boiler boil...

Страница 17: ...Other fuses to protect the electronic boards are to be found on the boards themselves Reduction motor if the motor stops the boiler continues to function until the flame goes out for lack of fuel and...

Страница 18: ...or Check the water sensor is connected Contact an Authorized Assistance Center ALAR ALAR ALAR ALAR ALAR ALAR COOL ALAR ALAR ALAR ALAR SERV Hot temp The smokes temperature exceeds 280 C Smokes sensor f...

Страница 19: ...of pellets in the tank or because the motor reducer for pellets loading got broken The boiler continues working until the pellets left in the brazier ends You will then read the words Alar No Fire on...

Страница 20: ...idual combustion in the contact zone between the edges of the crucible and the support surface on the door crucible Parts Everyday Every 2 3 days Every week Every 15 days Every 30 days Every 60 90 day...

Страница 21: ...Check every 60 90 days Cleaning the interior baffle smoke fan compartment Inside the compartment where there is the ash tray there is a second cover fixed by the cockerels which gives access to the co...

Страница 22: ...s a fuse holding compartment which is located underneath the supply socket With a screwdriver open the cover of the fuse holding compartment and replace the fuse if necessary 3 15 AT delayed type Plug...

Страница 23: ...lar Do not touch the boiler body and the various components do not approach the door it could cause burns Do not touch the exhaust fumes Do not perform any type of cleaning Do not dump the ashes Do no...

Страница 24: ...other non original The operations marked in bold type must be carried out by specialised personnel Any kind of tampering or unauthorized substitution of non original of the boiler can be hazardous to...

Страница 25: ...closed properly or gaskets worn 5 Boiler temperature is too high 6 Unsuitable pellets 7 Low pellet feed rate 8 Combustion chamber dirty 9 Smoke outlet obstructed 10 Smoke extraction motor failed 11 Pr...

Страница 26: ...k the motor and capacitor and replace if necessary 3 Replace electronic board 4 Replace the control panel In the automatic position the boiler always runs at full power 1 Room thermostat set to maximu...

Страница 27: ...of the boiler 1 It been set to a value of thermostat too high 2 It was set too much power to the implant 1 Lower the temperature in the boiler 2 Reduce the value of operating power The boiler goes in...

Страница 28: ...2 fax 385 40 372 621 Centrometal d o o shall not be responsible for possible incorrect data caused by printing errors or error made in transcription and all figures and diagrams are for explanatory pu...