3. SYSTEM DESCRIPTION
1. Power Switch:
- To turn on the UPS, press the button more than three seconds
- To turn off the UPS, press and hold this button until you hear the UPS
beep ceases.
2. UPS Test/ Alarm Silence:
- The battery is fully charged during in line mode. To perform self-test
function, press and hold the
button for five seconds.
- To disable alarm buzzer, press this button for a second that will turn off
the alarm buzzer. Each time a new alarm event is encountered the
alarm that will sound and press this button to turn off the alarm.
Note: Unable to disable alarm buzzer as below conditions: Low
Battery, Overload, Fan Failed, Fan Fault Time Out, Over
Temperature.
3. Configure:
To reconfigure the internal UPS setup options, follow the procedure as
below:
Step 1:
Press the Configure
button more than three seconds. Then
UPS will transfer from configure mode to “output voltage mode”.
Step2:
Press the Configure
button more than one second, the UPS
allows you to select the “output voltage mode” one by one.
Step3:
After selecting the mode, press the Enter
button more than
three seconds, the “output voltage mode” is configured.
Step4:
UPS will automatically transfer from configure mode to “operating
mode”.
Step5:
Press the Configure
button more than one second; the UPS
will allow you to select the “operating mode” one by one.
Step6
: After selecting the mode, press the
button more than three
seconds, the “operating mode” is configured.
4. Enter:
Press the
button after you choose the mode.
7