9. SPECIFICATION
MODEL
750/1000VA
1500/2000VA
3000VA
CAPACITY
Watt 500W/700W
1050W/1340W
2100W
Voltage
110/120/127VAC or 220/230/240VAC
Acceptable
Voltage Range
0-160VAC / 0-300VAC
Line Low
Transfer(Wide
mode)
77/84/89VAC ± 4% or 154/161/168VAC ± 4%
Voltage
Range
Line High
Transfer
132/144/152VAC ± 2% or 264/276/288VAC ± 4%
Frequency Range
50/60Hz ±5Hz for Normal Mode; >40Hz for Generator
Mode
INPUT
Surge Rating ( LV/HV )
320 / 230 Joules 430 / 250 Joules
500 / 640 Joules
Voltage
110/120/127VAC or 220/230/240VAC
Voltage Regulation (Batt.
Mode)
±5% RMS for entire battery voltage range
Frequency
50Hz or 60Hz
Frequency Regulation
(Batt. Mode)
±0.1Hz
OUTPUT
Waveform Pure
Sinewave
Line Mode
110% -0%, +8%; shutdown after 3 minutes. 150% -0%,
+10%; shutdown after 10 cycles
OVERLOAD
RATING
Battery Mode
110% ± 6%; shutdown after 30 seconds. 120 % ± 6 %;
Shutdown after 5 cycles
TRANSFER
TIME
Typical
2-4ms Typical, 6 ms max ; 13ms max. for generator
mode
Battery Type*
12V/7AH ;
12V/9Ah
12V/7Ah; 12V/9Ah
12V/5Ah
Battery Number
2 pcs
4pcs
8 pcs
Backup Time (at full load)
5 minutes min.
BATTERY
Recharge Time
4 hours to 90%
after discharged
3 hours to 90% after discharged