Page 13
For technical questions, please call 1-888-866-5797.
Item 61615
Troubleshooting
Problem
Possible Causes
Likely Solutions
Compressor does
not start or restart
1. Tank(s) already pressurized.
2. Power cord not plugged in properly.
3. No power at outlet.
4. Fuse blown.
5. Building power supply circuit tripped
or blown fuse.
6. Cord wire size is too small or
cord is too long to properly
power compressor.
7. Compressor needs service.
1. No problem. Compressor will start when needed.
2. Check that cord is plugged in securely.
3. Reset circuit breaker, or have outlet
serviced by a qualified technician.
4. Check and replace Fuse as needed.
5. Reset circuit or replace fuse. Check for low voltage
conditions. It may be necessary to disconnect
other electrical appliances from the circuit or
move the compressor to its own circuit.
6. Use larger diameter or shorter extension cord or
eliminate extension cord. See Recommended Wire
Gauge for Extension Cords in Safety section.
7. Have unit inspected by a qualified technician.
Compressor not
building enough
air pressure
1. Air filters need cleaning/replacing.
2. Check Valve needs service.
3. Compressor not large enough for
job.
4. Loose fittings.
5. Hose or hose connections
too narrow.
6. High altitude reducing air output.
1. Check inlet and outlet filters.
Clean and/or replace as needed.
2. Have technician clean or replace, as needed.
3. Check if accessory CFM is met by Compressor.
If Compressor cannot supply enough air flow (CFM),
you need a larger Compressor.
4. Reduce air pressure, then check all fittings with
a soap solution for air leaks and tighten as needed.
Do not overtighten.
5. Replace with wider hose and/or hose connections.
6. Higher altitudes require compressors with greater output.
Overheating
1. Unusually dusty environment.
2. Cord is too small of a gauge or too
long to handle compressor.
3. Unit not on level surface.
1. Move unit to cleaner environment.
2. Increase cord size or use shorter length extension
cord, or eliminate extension cord. See Recommended
Wire Gauge for Extension Cords in Safety section.
3. Reposition unit on a level surface.
Compressor
starts and stops
excessively
1. Loose fittings.
2. Compressor not large
enough for job.
1. Reduce air pressure, then check all fittings with a soap
solution for air leaks and tighten as needed.
Do not overtighten.
2. Check if accessory CFM is met by Compressor.
If Compressor doesn’t reach accessory
CFM, you need a larger Compressor.
Excessive noise
Loose fittings.
Reduce air pressure, then check all fittings with a soap solution
for air leaks and tighten as needed. Do not overtighten.
Moisture in
discharge air
Too much moisture in air.
Install inline air filter/dryer, and/or relocate
to less humid environment.
Safety Valve “pops”
Safety valve needs service.
Pull on test ring of safety valve. If it still pops, replace.
Air leaks from
pump or fittings
Loose fittings.
Reduce air pressure, then check all fittings with a soap solution
for air leaks and tighten as needed.
Do not overtighten.
Air leaks from tank
Defective or rusted tank.
Have tank replaced by a qualified technician.
Drain moisture from tank daily to prevent future corrosion.
Follow all safety precautions whenever diagnosing or servicing the compressor.
Disconnect power supply before service.
SAFETY
OPERA
TION
MAINTENANCE
SETUP