9

ENG

pressure, with the system cold, must be betwe-
en 

and

 1.2 bar 

(14.5 and 17.4 psi). During 

system filling you are recommended to keep the 
main switch turned OFF. Filling must be done 
slowly so as to allow any air bubbles to be bled off 
through the air valves. Should the pressure have 
risen well above the limit expected, discharge 
the over pressure by opening the pressure-
relief valve. Bleed pump by loosen plug at back 
of motor. Once air is removed re-tighten plug. It 
may be necessary to free the pump motor befo-
re filling the system. This is done by removing 
the pump plug and turning the pump shaft loose. 
Do not forget to re-tighten pump plug before 
filling system.
See typical piping in the figure below.

2.4.1 Emptying 

the 

system 

(fig. 5)

Use the drain tap to empty the system (9).

Turn off the boiler before doing this.

2.5 FLUES/CHIMNEYS

The flue or chimney used to release the pro-
ducts of combustion into the atmosphere must 
comply with current standards and regulations. 
Horizontal vent lengths must be supported 
every I meter (39 in) or less to prevent sagging.

2.5.1 

Passing flue pipes through 

 

an existing chimney

When renovating or passing flue pipes through an 
existing chimney, use only flues which are decla-
red suitable for the purpose by the manufacturer, 
following the instructions for installation and use 
provided by the manufacturer.

2.6 

INSTALLATION COAXIAL PIPE 

(fig. 6)

The air inlet-smoke outlet assembly ø 60/100 
is supplied in a kit code 8084811 complete with 
mounting instructions. 

With the curve supplied in the kit the maximum 
horizontal length of the flue must not exceed 4 
m (13 ft). 

The diagrams in fig. 6 illustrate a number of exam-
ples of different coaxial outlets.

2.6.1 Coaxial 

flue 

diaphragm

 (fig. 6/a)

The boiler is supplied as standard with a ø 
86 diaphragm. With outlet type C12, install 
diaphragm  ø 84 mm (3.3 inch) only if the coaxial 
flue is less than 1 metres (3.3 ft) long. 
For C32 discharge options, it is necessary to 
order the optional diaphragm separately and use 
it in accordance with the instructions provided in 
figure 6/a.

2.7 

INSTALLATION SEPARATE PIPES

The smoke pipe must be certified ø 3” catego-
ry III venting. When installing the pipes, follow 
closely the requirements of the current stan-
dards and regulations, as well as the following 
practical pointers:

1.  With direct intake from outside, when the 

pipe is longer than 1 m (3.3 ft), you are 
recommended to insulate the piping so as 
to prevent formation of dew on the out-
side of the piping during particularly hard 
periods of the year.

2.  With the outlet pipe outside the building or 

in cold indoor environments, insulation is 
necessary to prevent burner failure during 
trial for ignition. In such cases, provide 
for a condensate-collector system on the 
piping.

3.  If a segment of the flue passes through a 

flammable wall, this segment must be insu-
lated with a glass wool pipe insulator 30 
mm (1 in) thick, with a density of 50 kg/
m

3

 (3lb/ft

3

) or follow vent manufacturers 

instructions for clearances to combusti-
bles.

TYPICAL PIPING

COLD WATER

SUPPLY

HOT

 WATER

SUPPLY

COLD

 WATER

SUPPLY

BOILER LOOP

LOW 

TEMPERATURE 

LOOP

HIGH 

TEMPERATURE 

LOOP

Содержание 35 BF

Страница 1: ...Combi Gas Fired Boiler Water Heater Model 35 BF Installation and Operating Instructions CLIOM 1 315 Oser Avenue Hauppauge NY 11788 Tel 631 694 1800 Fax 631 694 1832 www embassyind com...

Страница 2: ...act zone between drinking water and the water used for the heating system d clare que a Les mat riels utilis s l int rieur de la chaudi re sont idoines pour l utilisation de l eau potable b Dans la fa...

Страница 3: ...VALVE 28 5 EXPLODED VIEWS 29 WARNING If the information in this manual is not followed exactly a fire of explosion may result causing property damage personal inju ry or loss of life Do not store or u...

Страница 4: ...e following checks 1 Make sure that there are no liquids or inflammable materials in the immedia te vicinity of the boiler 2 Make sure that the electrical connec tions have been made correctly and tha...

Страница 5: ...3 5 43 5 Maximum C H temperature C 85 85 F 185 185 Expasion vessel Water content l 8 8 USgal 2 1 2 1 Expasion vessel Pre charged bar 1 1 psi 14 5 14 5 C H setting range C 40 80 40 80 F 104 176 104 176...

Страница 6: ...Water flow switch 15 Tridicator 16 Automatic by pass 17 D H W filter 18 C H return cock 19 C H flow cock 20 D H W cock 21 Gas cock 22 Aqua Guard Filter System Figure 3 KEY 1 Control panel 3 Combustio...

Страница 7: ...s or local codes having jurisdiction Where an exhaust fan or any other air consuming appliance is installed in the same space as the boiler sufficient air openings must be available to provide fresh a...

Страница 8: ...initiate a call for heat see user instructions verify red led Ignition lock out light is on after ignition boiler reset boiler by rotating the function knob to chimney sweep and stay at least one sec...

Страница 9: ...8084811 complete with mounting instructions With the curve supplied in the kit the maximum horizontal length of the flue must not exceed 4 m 13 ft The diagrams in fig 6 illustrate a number of exam ple...

Страница 10: ...Diaphragm Diaphragm Without Diaphragm None 86 3 4 87 5 3 44 diaphragm 87 5 3 44 diaphragm cod 6028623 cod 6028624 cod 6028624 L min 1 3 m L min 2 5 m L min 4 m L min 2 5 m 4 27 ft 8 2 ft 13 1 ft 8 2...

Страница 11: ...ams in fig 9 a illustrate a num ber of examples of different types of sepa rate outlets 2 8 POSITIONING OF OUTLET TERMINALS fig 11 The outlet terminal must be flush with the wall and the inlet termina...

Страница 12: ...inches KEY 1 Separate flue kit code 8089909 2a 90 elbow MF 2b Isolated 90 elbows MF 3a Extension L 1000 mm 39 4 inch 3b Insulated extension L 1000 mm 39 4 inch 3c Extension L 500 mm 19 7 inch 4 Outlet...

Страница 13: ...n 900 mm 3 ft of a window or door that can be opened in any building of any non mechanical air supply inlet to any building or of any combustion air inlet of any other appliance h Underneath a veranda...

Страница 14: ...nd two family dwellings a venting system that extends through any zone above that on which the connected appliance is located shall be provided with an enclosure having a fire resistance rating equal...

Страница 15: ...poisoning 1 Align pipes and push them together as far as they will go to indent or at least 1 75 inches 2 Tighten gear clamp to a minimum torque of 40 in lbs and a maximum of 50 in lbs NOTE Some flue...

Страница 16: ...all This applies to both combustible and non combustible walls 3 The system must be supported along its horizontal length at all elbow locations and joints every forty eight inches or less using strap...

Страница 17: ...tible floor or ceiling The opening must be framed for the support since the support also serves as a firestop 5 The roof flashing can now be installed Where the vent passes through the roof a flashing...

Страница 18: ...Install the Guy Band below the Rain Cap using the 10 24 screw and nut provided 2 Attach stainless steel or galvanized cable with a minimum rated capacity of 500 lbs 227 kgf to each of the four anchor...

Страница 19: ...pe length and attach top support to pipe Leave 6 150 mm of pipe protruding from flashing so that rain cap may be installed and to allow for any adjustment to line up base tee pro perly 3 Fasten flashi...

Страница 20: ...per ope ration after servicing Remove the three screws 9 locking the con trol panel in place and pull the panel forward until it can be tilted downward To access the components of the electrical panel...

Страница 21: ...n electrode TRA Ignition transformer TS 100 C 212 F safety stat PA Water pressure switch FL Flowmeter TF Smokes stat OP Time programmer Nota The room stat or the programmable thermostat must be connec...

Страница 22: ...ations described above be carried out by authorized technical staff 3 2 TEMPERATURE SENSOR Antifreeze system made up of the NTC hea ting sensor that activates when the water temperature reaches 6 C 43...

Страница 23: ...al of the ignition transfor mer The electrode is earthed or very worn and needs to be substituted The control box is defective When there is a sudden voltage failure the bur ner shuts out immediately...

Страница 24: ...eir local valves will be connected Connect micro switches or relay contacts on terminals 15 16 of the TA connector of the electronic card after removing the existing jumper fig 18 CR1 CR Connettore TA...

Страница 25: ...5 SIGMA HONEYWELL VK 4105M SIEMENS VGU 50 gas valve fig 21 The gas valve is set at two pressure values maximum and minimum According to the type of gas burnt these correspond to the values given in Ta...

Страница 26: ...djust maximum pressure using the nut 3 fig 22 a with a wrench to the maxi mum pressure value indicated in Table 4 7 Do not adjust minimum pressure until you have adjusted maximum pressure 8 Turn off t...

Страница 27: ...sits every 6 months it is recommended to periodically inspected the intake and the exhaust terminal for debris or snow removed from blocking the termination Any dirt within the vent shall be removed w...

Страница 28: ...tch is working and that the relative contact is in the rest position 2 Check whether connection tubes of smoke pressure switch are obstructed and if necessary clean away impurities or condensate 3 The...

Страница 29: ...29 ENG 5 EXPLODED VIEWS VUES CLAT ES...

Страница 30: ...1 Panneau c t gauche chambre combustion Combust chamber left hand side panel 16 6139773 Isolation arri re chambre de comb Combustion chamber rear insulation 17 6139792 Calorifuge lat ral chambre combu...

Страница 31: ...plaques 16 plate heat exchanger kit 55 6281504 Vanne de d viat pression d eau Divertor valve 56 6119355 Bouchon pour groupe en Technyl Brass plug for hydraulic group 57 6226607 Ressort de fixation tu...

Страница 32: ...310 Porte ant rieur chambre tanche Sealed chamber front panel 93 6001210 Regard de flamme Peephole 94 6287331 Jaquette Casing 95 2013302 Plaquette pour vis t le Fastener for self tapping screw 96 2004...

Страница 33: ...onnecteur 90 Connector 90 6299994 Connecteur 4 bornes Lumberg 4 pole Lumberg cable connector 6299995 Connecteur 14 bornes Lumberg 14 pole Lumberg cable connect 6299996 Connecteur 6 bornes Stocko 6 pol...

Страница 34: ...34 ENG...

Страница 35: ...35 ENG...

Страница 36: ...315 Oser Avenue Hauppauge NY 11788 Tel 631 694 1800 Fax 631 694 1832 www embassyind com...

Отзывы: