Celsior 35 BF Скачать руководство пользователя страница 7

7

ENG

The installation must conform to the require-
ments of the Authority having jurisdiction or, 
in the absence of such requirement, to the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54 
and, or CAN/CGAB149 Installation Code. Where 
required by the Authority having jurisdiction, the 
installation must conform to the Standard for 
Controls and Safety Devices for Automatically 
Fired Boilers, ANSI/ASME CSD-1. All boilers 
must be installed with a proper pressure relief 
valve. Pressure relief valves must be installed 
to confirm to ANSI/ASME Boiler and Pressure 
Vessel Code, Section IV, or CSA B51, as applicable. 
If the boiler is installed above the radiation level, 
or as required by the Authority having jurisdiction, 
the installer must provide a low water cut-off 
device at a time of installation. The boiler must be 
installed in a fixed location and only by a qualified 
installer, service agency or the gas supplier and is 
familiar with the requirement that are contained 
in this manual. Furthermore, the installation 
must be in accordance with current standars 
and regulations. The boiler must not be installed 
on carpeting. The boiler when used in connection 
with a refrigeration system, must be installed so 
the chilled medium is piped  in parallel with the boi-
ler with appropriate valves to prevent the chilled 
medium from entering the boiler. The boiler piping 
system of a hot water boiler connected to heating 
coils located in air handling units where they may 
be exposed to refrigerated air circulation must 
be equipped with flow control valves or other 
automatic means to prevent gravity circulation of 
the boiler water during the cooling cycle. Service 
instructions and recommended frequency gui-
delines periodic examination of venting systems 
every six months. Venting systems, the vent-air 
intake  system, screens in the vent terminal 
should be checked  and cleaned every six months. 
Low water cutoff  should be checked  and cleaned 
every six months. Remove small  cover retaining 
screw  and remove the cover. When the pump 
is running and water is flowing around the boiler 
, the actuator lifts off the micro switch.  Check  
that the  operation  of the actuator ; Ensure that 
it is free and that it lifts and returns. If necessary 
lubricate  the pivot  point of the actuator. Flue gas 
passageways should be checked  and cleaned 
every six months. The burner should be checked  
and cleaned every six months. Inspect the  burner  
and if necessary  clean using a soft brush and a 
vacuum cleaner, taking  care not to damage the 
front  insulation. Check the ignition /ionisation 
electrode, check the ignition spark  gap (3.5 mm 
+/- 0.5 mm) (0.138 in. +/- 0.02 in.). Before reas-
sembly inspect all seals and replace as required. 
Furthermore, the installation must be in accor-
dance with current standards and regulations.

2.1 

VENTILATION OF BOILER ROOM

When using air from the boiler room, an ade-
quate air supply shall by provided for combu-
stion of this boiler. An insufficient supply can 
result in poor combustion and possible sooting 
of the burner, combustion chamber or flue 
passageway. 

The boilers installed using inside air 

supply must provide provisions for Combustion 
Air and Ventilation Air in accordance with section 

53, Air for Combustion and Ventilation, of the 
National Flue Gas Code, ANSI Z 223,1/NFPA 
54, or section 7,2, 7.3, or 7.4, of CAN/CGA B 
149, Installation Codes, or local codes having 
jurisdiction. Where an exhaust fan or any other 
air consuming appliance is installed in the same 
space as the boiler, sufficient air openings must 
be available to provide fresh air when all appliance 
are operating simultaneously. It is essential that 
in rooms where the boiler are installed at least 
as much air can arrive as required by normal 
combustion of the gas consumed by the various 
appliances. Consequently, it is necessary to make 
openings in the walls for the air inlet into the 
rooms. These openings must meet the following 
requirements:

1.  Have a total free section of a  least 2225 

mm

every kW (1 in

2

 for every 1000 Btu/

hr) of heat input, with a minimum of 100 
cm

2

 (15.5 in

2

);

2.  They must by located not more than 18 in 

or less than 6 in above the floor level, not 
prone to obstruction and protected by a 
grid which does not reduce the effective 
section required for the passage of air;

3.  Where requide by jursdiction or when 

required for additional opening must be 
provided at the highest elevation practical.

With a hermetically sealed combustion chamber 
and air supply circuit from outdoors, may be 
installed in any room in the home. Keep boiler 
area clear and free from combustible materials, 
gasoline and other flammable vapors and liquids.

2.2 INSTALLATION 

PLATE 

The installation plate code 6246958 is supplied 
with the boiler.
The optional installation plate code 8075416 
is supplied with an instruction sheet for the 
fixing.

2.2.1 Isolating 

valves 

kit

To fit the isolating valves, supplied with the boiler, 
use figure 4 for assembly.

2.2.2 System 

connection 

unions

The follow is available to facilitate water and gas 
connection of the boiler with the heating system: 
for assembly of the unions to see fig. 1.

2.3 CONNECTING 

UP 

SYSTEM

To protect the heat system from damaging cor-
rosion, flakes or deposits, before installation it is 
extremely important to clean the system using 
suitable products such as, descaler or slug re-
moving solution. For long-term protection against 
corrosion and deposits, the use of inhibitors is re-
quired for new installations and after cleaning the 
system. It is important to check the concentration 
of the inhibitor after each system modification and 
during maintenance following the manufacturer’s 
instructions (specific tests are available at your 
dealer). The safety valve drain must be connected 
to a collection funnel to collect any discharge du-
ring interventions. 

If the heating system is on a 

higher floor than the boiler, install the on/off taps 
supplied in kit on the heating system delivery/re-
turn pipes. 

WARNING: Failure to clean the heat system or 
add an adequate inhibitor invalidates the devi-
ce’s warranty.

2.3.1 Gas 

Requirements

Read the date plate to be sure the water he-
ater is made for the type of gas being used. 
An adhesive data plate is stuck inside the front 
panel, it contains all the technical data iden-
tifying the boiler  and the type of gas for which 
the boiler is arranged. If the information does 
not agree with the type of gas available, do not 
install or operate the water heater. Call your 
dealer. The gas piping must be installed accor-
ding to all local and state codes, or in absence 
of local and state codes, with the latest “Natu-
ral gas and propane installation code”, CAN/
CSA-B 149.1 or “National Flue Gas Code”, 
ANSI Z223.1 (NFPA 54). Consult the “Natural 
gas and propane installation code” or “Natio-
nal Flue Gas Code” for the recommended gas 

2 INSTALLATION

Figure 4

R C.H. 

return

M C.H. 

supply

G   Gas connection 
E   D.H.W. inlet
U D.H.W. 

outlet 

Содержание 35 BF

Страница 1: ...Combi Gas Fired Boiler Water Heater Model 35 BF Installation and Operating Instructions CLIOM 1 315 Oser Avenue Hauppauge NY 11788 Tel 631 694 1800 Fax 631 694 1832 www embassyind com...

Страница 2: ...act zone between drinking water and the water used for the heating system d clare que a Les mat riels utilis s l int rieur de la chaudi re sont idoines pour l utilisation de l eau potable b Dans la fa...

Страница 3: ...VALVE 28 5 EXPLODED VIEWS 29 WARNING If the information in this manual is not followed exactly a fire of explosion may result causing property damage personal inju ry or loss of life Do not store or u...

Страница 4: ...e following checks 1 Make sure that there are no liquids or inflammable materials in the immedia te vicinity of the boiler 2 Make sure that the electrical connec tions have been made correctly and tha...

Страница 5: ...3 5 43 5 Maximum C H temperature C 85 85 F 185 185 Expasion vessel Water content l 8 8 USgal 2 1 2 1 Expasion vessel Pre charged bar 1 1 psi 14 5 14 5 C H setting range C 40 80 40 80 F 104 176 104 176...

Страница 6: ...Water flow switch 15 Tridicator 16 Automatic by pass 17 D H W filter 18 C H return cock 19 C H flow cock 20 D H W cock 21 Gas cock 22 Aqua Guard Filter System Figure 3 KEY 1 Control panel 3 Combustio...

Страница 7: ...s or local codes having jurisdiction Where an exhaust fan or any other air consuming appliance is installed in the same space as the boiler sufficient air openings must be available to provide fresh a...

Страница 8: ...initiate a call for heat see user instructions verify red led Ignition lock out light is on after ignition boiler reset boiler by rotating the function knob to chimney sweep and stay at least one sec...

Страница 9: ...8084811 complete with mounting instructions With the curve supplied in the kit the maximum horizontal length of the flue must not exceed 4 m 13 ft The diagrams in fig 6 illustrate a number of exam ple...

Страница 10: ...Diaphragm Diaphragm Without Diaphragm None 86 3 4 87 5 3 44 diaphragm 87 5 3 44 diaphragm cod 6028623 cod 6028624 cod 6028624 L min 1 3 m L min 2 5 m L min 4 m L min 2 5 m 4 27 ft 8 2 ft 13 1 ft 8 2...

Страница 11: ...ams in fig 9 a illustrate a num ber of examples of different types of sepa rate outlets 2 8 POSITIONING OF OUTLET TERMINALS fig 11 The outlet terminal must be flush with the wall and the inlet termina...

Страница 12: ...inches KEY 1 Separate flue kit code 8089909 2a 90 elbow MF 2b Isolated 90 elbows MF 3a Extension L 1000 mm 39 4 inch 3b Insulated extension L 1000 mm 39 4 inch 3c Extension L 500 mm 19 7 inch 4 Outlet...

Страница 13: ...n 900 mm 3 ft of a window or door that can be opened in any building of any non mechanical air supply inlet to any building or of any combustion air inlet of any other appliance h Underneath a veranda...

Страница 14: ...nd two family dwellings a venting system that extends through any zone above that on which the connected appliance is located shall be provided with an enclosure having a fire resistance rating equal...

Страница 15: ...poisoning 1 Align pipes and push them together as far as they will go to indent or at least 1 75 inches 2 Tighten gear clamp to a minimum torque of 40 in lbs and a maximum of 50 in lbs NOTE Some flue...

Страница 16: ...all This applies to both combustible and non combustible walls 3 The system must be supported along its horizontal length at all elbow locations and joints every forty eight inches or less using strap...

Страница 17: ...tible floor or ceiling The opening must be framed for the support since the support also serves as a firestop 5 The roof flashing can now be installed Where the vent passes through the roof a flashing...

Страница 18: ...Install the Guy Band below the Rain Cap using the 10 24 screw and nut provided 2 Attach stainless steel or galvanized cable with a minimum rated capacity of 500 lbs 227 kgf to each of the four anchor...

Страница 19: ...pe length and attach top support to pipe Leave 6 150 mm of pipe protruding from flashing so that rain cap may be installed and to allow for any adjustment to line up base tee pro perly 3 Fasten flashi...

Страница 20: ...per ope ration after servicing Remove the three screws 9 locking the con trol panel in place and pull the panel forward until it can be tilted downward To access the components of the electrical panel...

Страница 21: ...n electrode TRA Ignition transformer TS 100 C 212 F safety stat PA Water pressure switch FL Flowmeter TF Smokes stat OP Time programmer Nota The room stat or the programmable thermostat must be connec...

Страница 22: ...ations described above be carried out by authorized technical staff 3 2 TEMPERATURE SENSOR Antifreeze system made up of the NTC hea ting sensor that activates when the water temperature reaches 6 C 43...

Страница 23: ...al of the ignition transfor mer The electrode is earthed or very worn and needs to be substituted The control box is defective When there is a sudden voltage failure the bur ner shuts out immediately...

Страница 24: ...eir local valves will be connected Connect micro switches or relay contacts on terminals 15 16 of the TA connector of the electronic card after removing the existing jumper fig 18 CR1 CR Connettore TA...

Страница 25: ...5 SIGMA HONEYWELL VK 4105M SIEMENS VGU 50 gas valve fig 21 The gas valve is set at two pressure values maximum and minimum According to the type of gas burnt these correspond to the values given in Ta...

Страница 26: ...djust maximum pressure using the nut 3 fig 22 a with a wrench to the maxi mum pressure value indicated in Table 4 7 Do not adjust minimum pressure until you have adjusted maximum pressure 8 Turn off t...

Страница 27: ...sits every 6 months it is recommended to periodically inspected the intake and the exhaust terminal for debris or snow removed from blocking the termination Any dirt within the vent shall be removed w...

Страница 28: ...tch is working and that the relative contact is in the rest position 2 Check whether connection tubes of smoke pressure switch are obstructed and if necessary clean away impurities or condensate 3 The...

Страница 29: ...29 ENG 5 EXPLODED VIEWS VUES CLAT ES...

Страница 30: ...1 Panneau c t gauche chambre combustion Combust chamber left hand side panel 16 6139773 Isolation arri re chambre de comb Combustion chamber rear insulation 17 6139792 Calorifuge lat ral chambre combu...

Страница 31: ...plaques 16 plate heat exchanger kit 55 6281504 Vanne de d viat pression d eau Divertor valve 56 6119355 Bouchon pour groupe en Technyl Brass plug for hydraulic group 57 6226607 Ressort de fixation tu...

Страница 32: ...310 Porte ant rieur chambre tanche Sealed chamber front panel 93 6001210 Regard de flamme Peephole 94 6287331 Jaquette Casing 95 2013302 Plaquette pour vis t le Fastener for self tapping screw 96 2004...

Страница 33: ...onnecteur 90 Connector 90 6299994 Connecteur 4 bornes Lumberg 4 pole Lumberg cable connector 6299995 Connecteur 14 bornes Lumberg 14 pole Lumberg cable connect 6299996 Connecteur 6 bornes Stocko 6 pol...

Страница 34: ...34 ENG...

Страница 35: ...35 ENG...

Страница 36: ...315 Oser Avenue Hauppauge NY 11788 Tel 631 694 1800 Fax 631 694 1832 www embassyind com...

Отзывы: