![Cellartec 1/2 Ton-SSL Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/cellartec/1-2-ton-ssl/1-2-ton-ssl_installation-operation-and-care-manual_2580337014.webp)
- 13 -
Fig. 13 Fixed Pressure Control
8.
Use of the condenser fan control (if applicable for low ambient kit)
Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig
It may need to adjust the setting in the field to avoid fan short cycle.
9.
Use of the crankcase heater (if applicable for low ambient kit)
The crankcase heater is installed around the lower part of the compressor and
shall be turned on all the time. The heater is self-regulated.
10. Pressure, Superheat and Subcooling Readings
CAUTION:
THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.
Complaint Possible
Causes
a. High suction pressure and low head pressure
b. High suction pressure and low head pressure
Low superheat and low subcooling
c. High suction pressure and high head pressure
Low superheat and high subcooling
d. High to normal suction pressure and high head pressure
Low subcooling
e. High suction pressure and high head pressure
Low subcooling
f.
High suction pressure and high head pressure
High superheat
g. Low suction pressure and low head pressure
High superheat and low subcooling
h. Low suction pressure and low to normal head pressure
High superheat and high subcooling
i.
Low suction pressure and low head pressure
Low subcooling
j.
Low suction pressure and low head pressure
Low superheat and low subcooling
k. Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
a. Compressor may be bad
b. Expansion valve opened, too
much oil
c. Overcharge
d. Non-condensable
gas
e. Air restricted, dirty condenser,
bad condenser fans
f. High room temperature, high
evaporator load
g. Undercharge
h. Liquid line restricted after
receiver, solenoid valve
restricted
i.
Suction line restricted
j. Air restricted at evaporator,
evaporator iced
k. Evaporator
restricted
Содержание 1/2 Ton-SSL
Страница 6: ...5 Fig 3 WM150 450SCU Condensing Unit Fig 4 WM 650SCU Condensing Unit...
Страница 17: ...16 Fig 15 CellarTec 1 8 1 3 Ton SSL Wiring Diagram...
Страница 18: ...17 Fig 16 CellarTec 1 2 Ton SSL Electrical Wiring Diagram...
Страница 19: ...18 Fig 17 Low Ambient Temperature CellarTec 1 8 1 3 Ton SSL Electrical Wiring Diagram...
Страница 20: ...19 Fig 18 Low Ambient Temperature CellarTec 1 2 Ton SSL Electrical Wiring Diagram...