Fig. 13 Fixed Pressure Control 

 

8. 

Use of the condenser fan control (if applicable for low ambient kit)

 

 

Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig 
 
It may need to adjust the setting in the field to avoid fan short cycle. 

 

9. 

Use of the crankcase heater (if applicable for low ambient kit)

 

 
The crankcase heater is installed around the lower part of the compressor and 
shall be turned on all the time.  The heater is self-regulated. 

 

10. Pressure, Superheat and Subcooling Readings 

 

CAUTION:  
THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY. 

 

Complaint Possible 

Causes 

a.  High suction pressure and low head pressure 
b.  High suction pressure and low head pressure 
       Low superheat and low subcooling 
c.  High suction pressure and high head pressure 
       Low superheat and high subcooling 
d.  High to normal suction pressure and high head pressure 
       Low subcooling 
e.  High suction pressure and high head pressure 
       Low subcooling 
f. 

High suction pressure and high head pressure 

      High superheat  
g.  Low suction pressure and low head pressure 
      High superheat and low subcooling 
h.  Low suction pressure and low to normal head pressure 
      High superheat and high subcooling 
 
i. 

Low suction pressure and low head pressure 

      Low subcooling 
j. 

Low suction pressure and low head pressure 

      Low superheat and low subcooling 
k.  Low suction pressure and low to normal head pressure 
      High superheat and normal to high subcooling 

a.  Compressor may be bad 
b.  Expansion valve opened, too 

much oil 

c. Overcharge 
 
d. Non-condensable 

gas 

 
e.  Air restricted, dirty condenser, 

bad condenser fans 

f.  High room temperature, high 

evaporator load 

g. Undercharge 
 
h. Liquid line restricted after 

receiver, solenoid valve 
restricted 

i. 

Suction line restricted 

 
j.  Air restricted at evaporator, 

evaporator iced 

k. Evaporator 

restricted 

 

Содержание 1/2 Ton-SSL

Страница 1: ...Care Manual CellarTec 1 8 Ton SSL CellarTec 1 4 Ton SSL CellarTec 1 3 Ton SSL CellarTec 1 2 Ton SSL w ww ww w a ap pe ex xw wi in ne ec ce el ll la ar rs s c co om m w ww ww w c ce el ll la ar rt te e...

Страница 2: ...Safety Information 2 Features Specifications 3 Cellar Construction 7 Installer s Instruction 8 Electrical Wiring 15 Temperature Control Humidity Adjustment 20 Care Guide 24 User Troubleshooting 25 Cu...

Страница 3: ...2 Important Safety Information WARNING DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED CIRCUIT IS REQUIRED 15 AMP FOR 1 8 1 3 Ton SSL AND 20 AMP FOR 1 2 Ton SSL...

Страница 4: ...ties are specified as follows MODEL EVAP UNIT W xD xH COND UNIT L xD xH Btu h CFM 55 90 F BOTTLE CAPACITY 55 75 F REFRIGERANT ELECTRICAL EVAP UNIT COND UNIT WEIGHT lb EVAP UNIT COND UNIT CellarTec 1 8...

Страница 5: ...4 Fig 1 WM15 25SFCL Evaporator Unit Fig 2 WM45 65SFCL Evaporator Unit NOTE LEAVE MINIMUM 3 CLEARANCE FOR ELECTRICAL WIRING AND REFRIGERATION PIPING...

Страница 6: ...5 Fig 3 WM150 450SCU Condensing Unit Fig 4 WM 650SCU Condensing Unit...

Страница 7: ...6 Fig 5 Liquid Filter Fig 6 Sight Glass CAUTION LOW AMBIENT TEMPERATURE KIT IS REQUIRED IF THE INSTALLATION AREA WILL BE BELOW 50 F...

Страница 8: ...ature surrounding the enclosure shall not exceed the temperature of the enclosure by more than 25 F No enclosure wall shall receive direct sun or strong wind Lighting shall be of low wattage with a ti...

Страница 9: ...on and proper operation of the system must be warranted by the installer Installation of the system must be done in accordance with all state and local building and electrical codes The condensing uni...

Страница 10: ...for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side CAUTION IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT DO NOT TURN ON THE COMPRESSOR UNTIL TH...

Страница 11: ...nside the wine room The air sensor can be located in a well circulated or in the return air area but not the supply air or air dead area 5 Piping Evacuating Charging and Starting CAUTION ALWAYS USE TH...

Страница 12: ...5 F wine room temperature The superheat at the evaporator unit shall be around 9 18 F under low high heat load at normal ambient temperatures If the superheat is high check the subcooling first to kno...

Страница 13: ...ng Cut out 230 psig Cut in 150 psig Differential 80 psig It may need to adjust the setting in the field to get the right cycle time A Single Control Fig 11 Single Adjustable Pressure Control B Dual Co...

Страница 14: ...h subcooling d High to normal suction pressure and high head pressure Low subcooling e High suction pressure and high head pressure Low subcooling f High suction pressure and high head pressure High s...

Страница 15: ...ansion valve restricted m Both evaporator and condenser restricted n Liquid line restricted before receiver o Condenser restricted 11 Condensing Unit Troubleshooting Unit not running a Incorrect power...

Страница 16: ...E FOR THERMOSTAT AND SENSOR IF EQUIPPED WITH LOW AMBIENT CONDITION KIT USE LOW AMBIENT TEMPERATURE WIRING DIAGRAMS TURN OFF THE COMPRESSOR BEFORE POWER THE CONDENSING UNIT ONLY TURN ON THE COMPRESSOR...

Страница 17: ...16 Fig 15 CellarTec 1 8 1 3 Ton SSL Wiring Diagram...

Страница 18: ...17 Fig 16 CellarTec 1 2 Ton SSL Electrical Wiring Diagram...

Страница 19: ...18 Fig 17 Low Ambient Temperature CellarTec 1 8 1 3 Ton SSL Electrical Wiring Diagram...

Страница 20: ...19 Fig 18 Low Ambient Temperature CellarTec 1 2 Ton SSL Electrical Wiring Diagram...

Страница 21: ...required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temper...

Страница 22: ...side of the center blank key for approximately five seconds until screen matches the screen below 3 Press UP DOWN advance keys to select setup number press UP DOWN change keys to change settings 4 Pre...

Страница 23: ...re Display 0 fahrenheit 1 celsius 0330 Daylight Savings 0 off 1 on 0340 Remote Air Sensor 0 no 3 indoor 0380 Indoor Dehumidification 0 no 0580 Min Compressor Off 5 five minutes off 0610 Min Cool Temp...

Страница 24: ...system setup and set 670 2 to lock screen then exit 4 Temperature Setting 1 Enter the system setup and set 670 0 to unlock screen then exit 2 Press UP DOWN keys to modify temperature 3 Enter the syst...

Страница 25: ...need to be cleaned at least every 6 months Unplug the system or disconnect power Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug cooling system or re...

Страница 26: ...re is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temper...

Страница 27: ...fresh air intake side c Check for excessive size d Check for installation location or increase setting e Clean condenser 7 Evaporator freezing up a Evaporator air flow restriction b Unit not stopping...

Страница 28: ...high ambient temperatures or airflow restriction d Malfunctioning components a Add support to improve installation b Check fans cabinet washers tubing contact and loose screws c Check for airflow bloc...

Страница 29: ...28 Customer Support If you still have problems please contact us at Apex 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info groupapex com...

Страница 30: ...press or implied including any of fitness for a particular purpose In no event shall APEX be responsible for any consequential damages what is so ever Any modification of APEX products shall void this...

Страница 31: ...LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NO...

Отзывы: