- 10 -
1 - Process & Manometer; 2 – Receiver Discharge)/Compressor Suction
3 – Liquid Line/Suction Line; 4 - Pressure Control
3. Evaporator Unit
•
The WM15-65SFCL evaporator units shall be installed for ceiling mount
with the air supply towards horizontally and air return on the bottom.
•
Supply air flow shall be unobstructed for at least 12” for free installation or
2” for deflector installation and return air shall be unobstructed for 6”.
•
There is a gravity drain line and the unit shall be installed level or with a
slight angle toward the drain connection. If rise-up is needed, a
condensation pump must be used.
4. Thermostat and Air Sensor
CAUTION:
USE 18 GAUGE THERMOSTAT WIRE.
•
The thermostat with a built-in air sensor can be installed in the wine room
5 ft above the floor in an area with good air circulation at average temp.
•
If the thermostat is mounted outside the wine room, a remote air sensor is
required inside the wine room. The air sensor can be located in a well
circulated or in the return air area, but not the supply air or air dead area.
5. Piping, Evacuating, Charging and Starting
CAUTION:
•
ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE
READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED
CHARGES ARE FOR REFERENCE ONLY.
•
CHARGE 15% MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS
EQUIPPED WITH A LOW AMBIENT CONDITION KIT.
NOTES:
•
THE VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE
CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY
THE SAME AS THE ABOVE LISTED LINE SIZES.
•
IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORATOR
UNIT, USE THE SUCTION LINE ONE LISTED SIZE SMALLER.
•
EXPANSION AND SOLENOID VALVES ARE INSTALLED ON LIQUID LINE.
•
The installation order starts from condensing unit (including the receiver,
discharge valve), liquid line filter-drier, moisture-liquid indicator/sight glass,
liquid line, to evaporator unit (including liquid line connection, solenoid
valve, expansion valve, and suction line connection), returning to insulated
suction line, suction valve and then condensing unit.
Содержание 1/2 Ton-SSL
Страница 6: ...5 Fig 3 WM150 450SCU Condensing Unit Fig 4 WM 650SCU Condensing Unit...
Страница 17: ...16 Fig 15 CellarTec 1 8 1 3 Ton SSL Wiring Diagram...
Страница 18: ...17 Fig 16 CellarTec 1 2 Ton SSL Electrical Wiring Diagram...
Страница 19: ...18 Fig 17 Low Ambient Temperature CellarTec 1 8 1 3 Ton SSL Electrical Wiring Diagram...
Страница 20: ...19 Fig 18 Low Ambient Temperature CellarTec 1 2 Ton SSL Electrical Wiring Diagram...