______________________________________________________________________________________
10
ES-30
Field Installation Manual
Recommended Parts List
Item
Make
Part No.
Qnty.
Main Wire
2 AWG Str. 600v
Any *
UL1015
As required
CT Wire
18-22 AWG Str. 600v
Any *
UL1015
As required
Bonding Wire
8 AWG Str. 600v
Any *
UL 1015
As required
CT (Current Sensor)
Megnelab
SCT-1250-600
1
Wall Plug (pin type)
Size 10 x 75 mm
Any
---
4
1/2” Conduit Connector
Any *
---
As required
1/2” Tube/Conduit
Any *
---
As required
*All the Parts used in installation must be UL recognized or UL listed.
NOTE
Installation of material and workmanship at the customer’s Main Breaker Panel shall be
the responsibility of the qualified Electrician in accordance with NEC. Any and all
connections exterior to the ES-30 unit shall be the responsibility of the qualified Electrician.