4.1. DESCRIPTION OF SIGNALLING LEDS

LED

Description

PWR Signalling of Power Supply

RX

Signalling of data receiving through  ADA-1020 converter from Current Loop port.

TX

Signalling of data transmitting from ADA-1020 converter through Current Loop port.

ATTENTION !

AT BAUD RATE ABOVE 38.4 KBPS THE LED'S TX, RX WILL LIGHT WEAKLY DURING DATA TRANSMISSION

5. RS232 INTERFACE – PIN DESCRIPTION OF  DSUB-9F-DCE SOCKET

Pin Signal

Description

ADA-1020

1 (DCD)

Level of receiver signal

Connected with DSR

2 (TxD) 

Data transmission via ADA-1020

Transmitter

3 (RxD) 

Data receiving via ADA-1020

Receiver

4 (DSR) 

Readiness of a device to receiving/transmitting date

Connected with DTR

5 (SG) 

Signal ground

GND

6 (DTR) 

Readiness of the ADA1020 to receiving/transmitting date

Connected with DSR

7 (CTS) 

The device confirm receiving RTS signal from ADA-1020

Connected with RTS

8 (RTS)

The ADA-1020 confirm readiness of date receiving to device

Connected with CTS

9 (RI)

Call rate

NC

6. VERSIONS

ADA-1020 - 

-

-

-

-

Order example:
Product Symbol: 

ADA-1020-1-1-2-3

1

 – Current  Loop Voltage 24VDC

1

 – Current Loop Type ± 20mA

2

 – 1kV=  galvanic isolation

3

 – cover without inlets, plug-in screw 

terminal block.
Power supply 10 – 30VDC

Product Symbol: 

ADA-1020-1-1-2-3-48

1

 – Current  Loop Voltage 24VDC

1

 – Current Loop Type ± 20mA

2

 – 1kV= galvanic isolation

3

 – cover without inlets, plug-in screw 

terminal block .

48

 - power supply 10 - 48VDC

Current Loop Voltage:

24VDC

1

12VDC

2

Current Loop Type:

± 20mA (active transmitter, passive receiver)

1

0 – 20mA (active/ passive transmitter, passive receiver)

2

Galvanic isolation:

1kV=, 3-way

2

3kV=, 3-way

3

Terminal & Terminal Cover:

Cover without inlets, screw terminal block

1

Cover with inlets, screw terminal block

2

Cover without inlets, plug-in screw terminal block

3

Power supply :

From 10 to 30VDC stable

From 10 to 48VDC stable

48

7. SPECIFICATION

TECHNICAL DATA

Transmission Parameters

Interface

RS-232

Current Loop

Connector

 DSUB-9 female

Screw terminal, wire max. Ø 2,5mm

2

.

Line length

15 m

Depend on baud rate eg. for BUS made

by UTP cable Cat.5E 4x2x05 (24 AWG)

and baud rate 300 bits/s can be 15 km.

Maximum number of connected device

1

1

11

ADA-1020

Содержание ADA-1020

Страница 1: ...User manual ADA 1020 RS 232 to Current Loop converter 1 io_ada 1020_v3 26_en Copyright 2001 2020 CEL MAR sp j ADA 1020...

Страница 2: ...PORT DTE TYPE COMPUTER 6 3 2 2 CONNECTION OF DEVICES WITH RS232 PORT DCE TYPE MODEM 6 3 3 CONNECTION OF THE CURRENT LOOP INTERFACE DEVICES 7 3 3 1 CONNECTION OF THE CURRENT LOOP LINE TO ADA 1020 CONVE...

Страница 3: ...he supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This may result to short circuit and damage...

Страница 4: ...nsmitter of Current Loop 0 20mA can work as ACTIVE or Passive the selection is made by the TX switch on the front panel see Fig 1 The passive transmitter can be used only for creation of current loop...

Страница 5: ...le of adequate cross section due to voltage drops for converter powering not supply converter from power circuit device that generates large impulse interference such as transmitters contactors 3 1 AS...

Страница 6: ...e is shown below Fig 6 DCE type connection of ADA 1020 to device with RS232 interface eg modem 6 ADA 1020 RxD 2 TxD 3 DTR 4 DSR 6 RTS 7 CTS 8 PC SG 5 RS232 DTE DB 9M ADA 1020 Current Loop Vss Vss Powe...

Страница 7: ...ple connection of two ADA 1020 together The line length less than 500m 7 ADA 1020 Current Loop Line 2 pair twisted ADA 1020 Current Loop Vss Vss Power Supply RS232 DCE DB 9F CTS 7 RTS 8 GND 5 Vss Vss...

Страница 8: ...232 INTERFACE DEVICES TO CURRENT LOOP BUS In this case example the Current Loop bus is created by one ADA 1020 converter MASTER active transmitter and one ADA 1020 converter SLAVE active transmitter t...

Страница 9: ...urrent loop receiver of overvoltage arising Current Loop bus The number of the SLAVE converters can be less for long lines Example of connection is shown below 9 ADA 1020 GND RS232 Current Loop Bus MA...

Страница 10: ...roperly green LED PWR on front panel of converter should light if not check polarization of power connection and if RX red LED is lighted check the correctness of connection of the Current Loop transm...

Страница 11: ...VERSIONS ADA 1020 Order example Product Symbol ADA 1020 1 1 2 3 1 Current Loop Voltage 24VDC 1 Current Loop Type 20mA 2 1kV galvanic isolation 3 cover without inlets plug in screw terminal block Power...

Страница 12: ...ssion of disruptions according to the standard PN EN 55022 Safety requiring According to the PN EN60950 norm Environment Commercial and light industrial Environmental Parameters Operating temperature...

Отзывы: