3.3
Special Functions and other useful information
Programming EQUALIZATION (Eq)
“Eq” parameter can be called onto the display.
Equalisation charge occurs 15 times sequentially; 5 minutes active cycle (ON) and 60 minutes sleeping cycle (OFF).
Preservation/Maintenance charge. if selected can continue indefinitely; 5 minutes in active cycle (ON) followed by 15 hours
sleeping cycle (OFF).
When Eq<>0 it means preservation active if the charger is ON.
Eq 0: no equalisation / no preservation (no Eq. no Con)
Eq 1: Equalisation after all cycles.
Eq 2: Equalisation every 5 cycles (full n/5) i.e.. once a week.
Eq 3: Equalisation every 20 cycles (full n/20) i.e.. once a month.
Display gives “Equl” message when funciton is on. while Leds are in 0011 0 position
(Eq) parameter can be changed when necessary. For instance. If equalisation setting Eq1=always active and you would like to
set it to "never active" here is how you have to proceed:
Go to parameter Equalisation pressing the key >> and up to "Eq 1".
Press M key (the first digit of the display starts flashing).
Scroll backwards until display shows "Eq0" (never active) then press M for confirmation.
NOTE: It is possible to select other types of equalizations (Eq4, Eq5 and Eq6) in addition to the standard ones (Eq1, 2 and 3).
They are complex equalizations. If you are interested, ask for the specific document that explains them to our assistance
service
Programming DELAY START (dELy)
System is enabled to set delayed starts up to 24h by intervals of 15 MINUTES each.
Power up the charger and scroll until “dELy” parameters (which enables to set up the delay time)
Press Button 1 (M). “dELY” disappears and a “00.00” clock is shown.
Increase/decrease time value by Buttons 2 and 3 (< and >) and confirm with M (for example: value 01:00 corresponds to 1
hour delay before the charging cycle start).
Press M again: clock disappears and “dELy” is shown again
Press Button 3 (>) forward to view the delay time set (for example 01:00)
Delay start countdown begins. Remaining time reduction will be shown (for example 00.59 and so on).
Call up “Navigator” parameter again and “UAIT” message will appear. which means “waiting”.
Once remaining minutes will have gone by. charger will start its regular charging cycle.
WARNING:
delay start time remains saved for the following charging cycles as well!
To disenable the delay start. call “dELY” parameter and set a 00.00 value!
Main differences between 5DTM and 5DTT
1 - 5DTM is a single phase charger, while 5DTT is three phase
2 - 5DTM does not have an auxiliary transformer that powers the main board and the display, therefore it is not possible to
obtain information without connecting the battery.
For this reason, some indications on the display may differ
Repeated attempts to restart in case of failure
The charger is programmed to attempt to restart every minute in case of non-blocking errors due to current, thermal and
network errors. Here they are: cur, ter, terc and E_AC
The battery charger, on the other hand, remains blocked in the event of errors due to the battery or exceeding a maximum
time. Here they are: bat5, bat9, time, E_t2 and tout.
You will need to disconnect the battery to reset a blocking error.
The reason is that this error must be thoroughly evaluated before attempting a new charge
We remind you that "bat" is not an error but means "waiting for the battery" or "Battery disconnected"
Also "bat1" is not an error, but a warning, the charger is on, but the battery voltage is below the rated value and the current
output is very high. This situation should also be carefully considered
Indications on the display with special hardware
1 - Pilot Contact: If this option is present and the contact is open, the display shows the message "open"
2 - AT58 expansion card: If this card is present and there is no communication with the AT12 main card, the display will show
"Mbus"
3 - Air insufflation pump: If this option is present and the pressure sensor measures a low pressure, the display will show
"Air"