Ceiec Electric Technology
In this example, P2 of the PMC-1302 ESG is used. The PMC-660’s serial port has been configured
with the following parameters:
1.
Type = RS-485
2.
Baud rate = 9600
3.
Data Bits = 8
4.
Parity = Even
5.
Stop Bits = 1
It is important for the communications parameters of the PMC-1302 ESG’s P2 to be programmed to
match those of the PMC-660V1.2. The IP Port Number for P2 is 20000.
After the P2 settings of the PMC-1302 ESG has been correctly configured, click
Restart
menu item on
the left-hand pane to open the page and then click on the
Restart
button to complete the PMC-1302
ESG programming. The PMC-1302 ESG will perform a reboot operation with the new configuration.
When the Log-In page returns, the PMC-1302 ESG is now ready.
5.3 Configuring PecStar
In PecStar’s
Systemconfig
interface, select
Site 1
on the left-hand pane and then click on the