Cedar Ridge MTF30TBU Скачать руководство пользователя страница 9

www.usaprocom.com

9

200006-01B

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

 _______

Btu/Hr (maximum can support)

 

 _______

Btu/Hr (actual amount used)

 

Example:

 51,200  Btu/Hr  (maximum  the 

space can support)

 

 

56,000 Btu/Hr (actual amount 

of Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You  must  provide  additional  fresh  air. 

Your options are as follows:
A.  Rework  worksheet,  adding  the  space 

of an adjoining room. If the extra space 

provides  an  unconfined  space,  remove 

door to adjoining room or add ventilation 

grills between rooms. See 

Ventilation Air 

From Inside Building, 

page 10

.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors, 

page 10.

C.  Install a lower Btu/Hr heater, if lower Btu/

Hr size makes room unconfined. If the ac-

tual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space 

is an unconfined space. You will need no 

additional fresh air ventilation.

 WARNING: If the area in which 

the  heater  may  be  operated  is 

smaller  than  that  defined  as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the National Fuel Gas Code, 

ANSI Z223.1/NFPA 54, the In-

ternational Fuel Gas Code, or 

applicable local codes.

AIR FOR COMBUSTION AND VENTILATION

 

30,000

  26,000

  56,000

Determining if You Have a Confined 

or Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space:

 Includes the room in which you will 

install heater plus any adjoining rooms with 

doorless  passageways  or  ventilation  grills 

between the rooms.
1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. 

ft. (volume of space)

 

Example:

  Space  size  20  ft.  (6.1  m) 

(length)  x  16  ft.  (4.88  m)  (width)  x

 

8 ft. (2.44 m) (ceiling height) = 2560 cu. 

ft. (72.49 m

3

) (volume of space)

 

If additional ventilation to adjoining room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space.

2.  Multiply the space volume by 20 to deter-

mine the maximum Btu/Hr the space can 

support.

 

 ________

(volume  of  space)  x  20  = 

(Maximum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (72.49 m

3

) (volume 

of space) x 20 = 51,200 (maximum Btu/

Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appli-

ances in the space.

 

Vent-free heater 

 _________

Btu/Hr

 

Gas water heater* 

 _________

Btu/Hr

 

Gas furnace 

 _________

Btu/Hr

 

Vented gas heater 

 _________

Btu/Hr

 

Gas fireplace logs 

 _________

Btu/Hr

 

Other gas appl

 _______

Btu/Hr

 

Total 

=

 ________

Btu/Hr

 

*  Do  not  include  direct-vent  gas  appli-

ances.  Direct-vent  draws  combustion 

air  from  the  outdoors  and  vents  to  the 

outdoors.

 

Example:

 

 

Gas water heater 

 __________

Btu/Hr

 

Vent-free heater 

+

 _________

Btu/Hr

 

Total 

=

 _________

Btu/Hr

Содержание MTF30TBU

Страница 1: ...ury or loss of life Do not store or use gasoline or other flammable va pors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup...

Страница 2: ...om in which it is installed Provisions for ad equatecombustionandventilationairmustbeprovided Refer to Air For Combustion and Ventilation section on page 8 of this manual WARNING Improper installation adjustment al teration service or maintenance can cause injury or property damage Refer to this manual for correct in stallation and operational procedures For assistance or additional information co...

Страница 3: ... serviced Some people are more af fected by carbon monoxide than others These include pregnant women people with heart or lung disease or anemia those under the influ ence of alcohol and those at high altitudes NATURALAND PROPANE LP GAS Natural and Propane LP gas are odorless An odor making agent is added to the gas The odor helps you detect a gas leak However the odor added to the gas can fade Ga...

Страница 4: ...heater off If heated the vapors from these prod ucts may create a white powder residue within burner box or on adjacent walls or furniture 8 Do not use heater if any part has been under water Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water 9 Turn off and unplug heater and let coo...

Страница 5: ... or similar coverings Arrange cord away from traffic areas and where it will not be tripped over 9 To disconnect heater turn controls to OFF then remove plug from outlet 10 Connect to properly grounded outlets only 11 When this appliance is installed it must be electrically grounded in accordance with local codes with the current CSA C22 1 Canadian local codes for USA installa tions Follow local c...

Страница 6: ... 9101 This heater is designed for vent free op eration State and local codes in some areas prohibit the use of vent free heaters State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas sachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the...

Страница 7: ...er WATER VAPOR A BY PRODUCT OF UNVENTED ROOM HEATERS Water vapor is a by product of gas combus tion An unvented room heater produces ap proximately one 1 ounce 30 mL of water for every 1 000 BTUs 0 3 KWs of gas input per hour Unventedroomheatersarerecommended as supplemental heat a room rather than a primary heat source an entire house In most supplemental heat applications the water vapor does no...

Страница 8: ... that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or...

Страница 9: ...NFPA 54 the In ternational Fuel Gas Code or applicable local codes AIR FOR COMBUSTION AND VENTILATION 30 000 26 000 56 000 Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the room...

Страница 10: ...door into adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings one within 12 of the ceiling and one within 12 of the floor Connect these items dir...

Страница 11: ...moke aromaticcandles cleaning fluids oil or kerosene lamps etc in the air exist may cause walls to discolor Figure 4 Mounting Clearances as Viewed From Front of Heater IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form too much moisture See Air for Combustion and Ventilation pages 8 thro...

Страница 12: ... bracket is located on back panel of heater see Figure 7 It has been taped there for shipping Remove mounting bracket from back panel 1 Pull out the sensing bulb from the two clips located in the shipping position There is no need to take out the two bulb clips 2 Take out the bulb clip from the hardware package and insert it into the square hole Then insert the sensing bulb into the bulb clip see ...

Страница 13: ... solid walls concrete or masonry 1 Drill holes at marked locations using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep 2 Fold wall anchor as shown in Figure 9 WARNING Maintain mini mumclearancesshowninFigure 4 page 11 If you can provide greater clearances from floor and joining wall 2 Mark screw locations on wall see Fig ure 8 Note Mark only last hole on each end of moun...

Страница 14: ...tching means shall not be opened while the heater is in operation CAUTION To avoid gas leakage at the inlet of regulator a qualified installer or service technician must use supplied hex plug with sealant WARNING Do not attempt to access or change the setting of the fuel selection means Access to and adjustment of the fuel selection means must only be performed by a qualified service person when c...

Страница 15: ...move hex plug with wrench provided from natural gas inlet of regulator see Figure 15 Install hex plug into LP inlet of regulator Install gas line into NG inlet of regulator Use thread sealant to ensure that there are no leaks For changing from natural gas supply to propane supply 1 Remove top screw from cover plate lo cated on back of heater see Figure 16 Rotate to expose fuel selection device 2 F...

Страница 16: ...fittings CAUTION Use pipe joint sealant that is resistant to gas Propane LP or Natural Gas Before installing heater make sure you have the items listed below piping check local codes sealant resistant to natural gas and pro pane LP gas equipment shutoff valve test gauge connection sediment trap tee joint pipe wrench flexible gas hose check local codes A CSA design certified equipment shutoff valve...

Страница 17: ...e 19 2 Pressurize supply piping system by either using compressed air or opening gas sup ply valve 3 Check all joints from gas supply see Figure 20 or 21 page 18 to equipment shutoff valve Apply a noncorrosive leak detection fluid to all joints Bubbles form ing show a leak 4 Correct all leaks at once IMPORTANT Install an equipment shutoff valve in an accessible location The equip ment shutoff valv...

Страница 18: ...n or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water PRESSURE TESTING HEATER GAS CONNECTI...

Страница 19: ...ooting pages 25 though 27 Also contact a qualified service technician or gas supplier for repairs Until repairs are made light pilot with match To light pilot with match see Manual Lighting Procedure page 20 LIGHTING INSTRUCTIONS Figure 22 Control Knob in the OFF Position Ignitor Button Control Knob 7 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release contro...

Страница 20: ...control knob clockwise to the OFF position Shutting Off Burner Only pilot stays lit Turn control knob clockwise to the PILOT position MANUAL LIGHTING PROCEDURE 1 Remove front panel 2 Follow steps 2 through 5 under Lighting Instructions page 19 3 With control knob pressed in strike match Hold match to pilot until pilot lights 4 Keep control knob pressed in for 30 sec onds after lighting pilot After...

Страница 21: ...l or cover the extension cord Electrical outlet wiring must complywithlocalbuildingcodes andotherapplicableregulations to reduce the risk of fire electri cal shock and injury to persons Do not use this heater if any part of it has been under water Immediately call a qualified ser vice technician to inspect the fireplace and replace any part of the electrical system which has been under water GROUN...

Страница 22: ...lowed CAUTION Label all wires prior to disconnection when servicingcontrols Wiringerrors cancauseimproperanddanger ous operation Verify proper operation after servicing If any of the original wire as supplied with the appli ance must be replaced it must be replaced with a wire of at least a 105º C temperature rating 1 Power Supply Cord 2 Electrical Wire Connector 3 Rocker Switch 1 4 Rocker Switch ...

Страница 23: ...is will cause the ther mocouple to cool which shuts the heater off If pilot flame pattern is incorrect as shown in Figure 28 turn heater off see To Turn Off Gas to Ap pliance page 20 see Troubleshooting pages 25 through 27 WARNING If yellow tipping occurs your heater could pro duce increased levels of carbon monoxide If the burner flame pattern shows yellow tipping follow instructions at bottom of...

Страница 24: ...e pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes 2 Remove four screws securing front panel 3 Pull front panel forward 4 Inspect burner and pilot for dust and dirt 5 Blow air through the ports slots and holes in the burner 6 Replace front panel using screws re moved ODS PILOT Periodically inspect all burner flame holes with the heater runni...

Страница 25: ...ressed in there is no spark at ODS pilot 1 Ignitor electrode is posi tioned wrong Ignitor elec trode is broken 2 Ignitor electrode is not con nected to ignitor cable 3 Ignitor cable is pinched or wet 4 Broken ignitor cable 5 Bad piezo ignitor 6 Low battery 1 Replace electrode 2 Replace ignitor cable 3 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 4 Replace ignitor cab...

Страница 26: ...g thermocouple which allows thermocouple to cool caus ing pilot flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged 1 Press in control knob fully 2 After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shutoff valve 4 Hand tighten until s...

Страница 27: ...fter burner is lit or shut off 1 Metal is expanding while heating or contracting while cooling 1 This is common with most heaters If noise is exces sive contact qualified ser vice technician White powder residue forming within burner box or on adjacent walls or furniture 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue 1 Turn heater off when usi...

Страница 28: ...www usaprocom com 200006 01B 28 PARTS MODEL MTF30TBU F a n O N O N O F F O F F E le c tr ic H e a ti n g 5 2 4 3 6 7 8 10 9 11 12 13 15 19 18 17 1 14 16 ...

Страница 29: ... 5 NDD0308 600 MU30 ODS Pilot 1 6 PF120820 Hex Plug 2 7 RV83FI 4 9 Gas Regulator 1 8 UBD30T 250B Burner Assembly 1 9 ML073 01 Ignitor Cable 1 10 UBD30T 108 Left Burner Bracket 1 11 PIMSC1 01 Ignitor Assembly 1 12 UBD30T 270B Thermostat Valve Assembly 1 13 UBD30T 101 Body Panel 1 14 UBD30T 180B Fuel Selection Device Cover 1 15 MB060 01 Mounting Bracket 1 16 UBD30T 300B E Blower Heater Assembly 1 17...

Страница 30: ...UNTING STAND For locating heater on the floor away from a wall Complete installation instructions pro vided with floor mounting stand Model and serial number of your heater How heater was malfunctioning Type of gas used Propane LP or Natural gas NG Purchase date Usually we will ask you to return the defective part to the factory Note Use only original replacement parts This will protect your warra...

Страница 31: ...ied heat propane LP gas supply might be low propane LP units only You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact ProCom Heating Inc at 1 866 573 0674 When calling please have your model and serial numbers of your heater ready ...

Страница 32: ...aller in accordance with all local codes and instructions furnished with the unit WHAT IS NOT COVERED This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any an...

Отзывы: