15
Fig. 11 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff valve from your dealer.
The installer must supply an external regulator. The
external regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to between 11
and 14 inches of water. If you do not reduce incoming
gas pressure, heater regulator damage could occur.
Install external regulator with the vent pointing down
as shown in Fig. 12. Pointing the vent down protects
it from freezing rain or sleet.
Install sediment trap in supply line as shown in Fig. 11.
Place sediment trap where it is within reach for
cleaning. Place sediment trap where trapped matter is
not likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is installed
wrong, heater may not run properly.
Installation of Base Feet
Before installing heater to the base, please make sure
you have the following items:
(2) Base Feet, (4) Sheet Metal Screws. (Fig.13)
I
nstallation Procedure:
1. Set back of heater on table with the bottom of heater
extending outside the table edge.
2. Fasten Base Feet to heater using Sheet Metal
Screws.
Fig. 12 - External Regulator with Vent
Pointing Down
Fig. 13
3 in Minimum
14 in
3 in. Minimum
Test
Gauge
Connection *
Sediment
Trap
Tee Joint
Reducer
Bushing to
1/8 in NPT
1/8 in NPT
Plug Tap
Tee Joint
Pipe Nipple
Gap
3/8 in NPT
Pipe Nipple
Ground Joint
Union
Equipment
Shutoff
Valve
Inlet Pipe From Gas
Meter (11 in W. C. to
14 in W. C. Pressure)
Propane/LP
Supply Tank
External
Regulato
r
Vent Pointing Down
Base Feet
Sheet Metal
Screws