16
cdvigroup.com
EN
ADH10
ATRIUM - Schlage Integration Module (Control up to 10 Schlage Door Handles)
INSTALLATION MANUAL
EN
ADH10
ATRIUM - Schlage Integration Module (Control up to 10 Schlage Door Handles)
INSTALLATION MANUAL
Connecting the Box Tamper Switches
Connecting the tamper switches allows the ADH10 Controller to detect when the cabinet door is opened and/or
when the cabinet is removed from the wall. To install the tamper switches, see “Installing the Tamper Switches”.
To use both switches:
1.
Connect one end of the supplied wire to the door tamper switch
terminal and the other end to the wall tamper switch terminal.
2.
Connect the other terminal of the door tamper switch to the “TMP” terminals using
the supplied wire.
3.
Connect the other terminal of the wall tamper switch to the “GND” terminals using
the supplied wire.
To use only one switch:
1.
Connect one terminal of the tamper switch to the “TMP” terminals using the supplied wire.
2.
Connect the other terminal of the same tamper switch to the “GND” terminals using
the supplied wire.
If you do not use the tamper switch, connect a wire between the “TMP” and “GND” terminals.
LOCAL
BUS
POWER
SUPPL
Y
BA
TT
.
TAMPER
Metal Box
Door
Tamper Switch
(N.C.)
Metal Box
Wall
Tamper Switch
(N.C.)