Examples of Input Connection Methods
Single without EOL and without TAMPER Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to
the input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following figure. This setup will not support WIRE CUT or WIRE SHORT
supervision, but will generate an alarm condition when the state of
the input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: NO
Single with WIRE SHORT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to
the input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following figure. This setup will not support WIRE CUT supervision but
offers WIRE SHORT supervision and will generate an alarm condition
when the state of the input isbreached.
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
WIRE CUT supervision: NO
Single with WIRE CUT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to
the input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following figure. This setup will support WIRE CUT supervision but
will not offer WIRE SHORT supervision and will generate an alarm
condition when the state of the input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: YES (Detected as INPUT CUT)
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K
Tamper Input 1
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Input 1
1K
EOL
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS