HE1 Models VN-M1000/1500/2000HE1.
HE1 models do not have the same “Dip Switches”, configuration is very similar to
standard Toshiba split systems.
On the “Header Unit” the “CN71” link needs removing.
The “CN71” link remains in position on follower units.
Configuration is generally automatic, with “CN71” link removed on the header, apply
power to the units within the “Group”, addressing will be carried out automatically.
If manual addressing is required.
Using the RBC-NRC01HE remote controller, with power on.
Press and HOLD
, for 4 seconds;
“
TEST, SET and CL
”.
The controller will display “
10
” on the right-hand display.
Using the
Temp up/down
buttons, scroll
10
to
13
.
Change the left-hand display using the “
Time
” Up/down buttons
Selecting a unique number between 1 (Header) – 64 (Follower),
Groups can comprise of up to 8 units.
Press “
SET
” then Press “
TEST
”
When you press the “
Unit
” button the middle window will
Display, the system number, always fixed at 31, and the indoor
unit number between 1 to 64, pressing the “
Unit
” button again
will display the next unit in the group, 31 – 2 etc.