Electrical “Dip Switches” and their purpose
HE Models
There are 4 “Banks of “Dip Switches. Two banks of two
and two banks of four.
SW301 - “Terminal – End of Line” resister. ON = 100Ω.
OFF = None
SW701 – Pulse/Static ON = Pulse.
OFF = Static
.
SW702 – (1 to 4) Indoor unit address. (See chart)
SW703 – (1 to 2) Indoor unit address
.
(Factory default ALL OFF indoor address No 1.)
(3) Central controller address. ON = Fix,
OFF = Auto
(Leave value OFF)
(4) ON = Header (Individual)
OFF = Follower
(Factory default follower)
A “group” can comprise of up to 8
units of any combination, RAV, VRF,
VN-M indoor units.
Wiring is the same as above.
When a “group” is controlled via
two remote controllers, the
quantity of units drops to a
maximum of 7.
Wiring is the same as above.