22
REVO SX
User’s manual
Internal Fuse
The thyristor unit must be protected against short circuit by High speed fuses.
The Fuses must have I²t 20% less than thyristor’s I²t.
The warranty of thyristor is null if no proper fuses are used.
Change the Fuses:
8
Caution:
High speed fuses are used only for the thyristor protection and can not be used to
protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses are used (see table).
Spare Fuse Order Code:
REVO 4x3,5A
FU5X20-4
Only one pcs.
Type 5x20 4A 250V fast 0324004
REVO 3x4,5A
FU5X20-5
Only one pcs.
Type 5x20 6A 250V fast 0324005
REVO 2x7A
FU5X20-8
Only one pcs.
Type 5x20 10A 250V fast 0325008
Press, turn in counter-clockwise and release
Extract the fuse
Содержание REVO SX Series