REVO C
3PH from 1100A to 2100A
User’s manual
49
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Alm Out Fn
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!:
The power controller monitors for heater
break or short circuit condition only when included
in the option selected for Alarm Output Function
1
34
Read
Write
Option
Description
Bit
Heater Break
Heater Break
0
Short Circuit
Short circuit
1
Current Limit
Current Limit
2
Therm
SCR is over temperature
3
Communication
Communication watchdog error
4
FAN
Indicate that a fan is not working properly or not supplied
7
DEFAULT
None
Alarm Bitwise is allowed
Parameter Name
Description
Default
Modbus
Address
Par.
Type
IL SP Src
Choose how the current limit is set
16
14,bit 4
Read
Write
Option
Description
Value
Local / Comms
Set point set via keypad or communication
16
Analog In 2
Set point set via analog input
0
DEFAULT:
local
16