32
REVEX
1PH 280A
User’s manual
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
HB Delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
50 (2,5
sec)
0 to 255
(0 to 12,75
sec)
28
Read
Write
Htr Bake
Enable or disable the heater bakeout
feature
0
140
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0